Plan Review Details - Permit 16060592
Plan Review Stops For Permit 16060592
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-16 Cont ID  
Sent By jwitmer Date 2016-08-16 Time 11:40 Rev Time 0.00
Received By jwitmer Date 2016-08-16 Time 10:08 Sent To  
Notes
2016-08-16 11:40:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060592
 ADD: 8146 OKEECHOBEE BLVD.
 CONT: J.J. MALLEY ENTERPRISES
 TEL: 561-843-5325
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. AUGUST 16/ 2016
 ACTION: DENIED
  
 1) 2ND REQUEST. SHEET SP-1 CODE REFERENCES: LIST THIS
 TENANT FIT-UP AS A LEVEL LL ALTERATION AND THE BUILDING
 STRUCTURE BEING BUILT UNDER THE ORIGINAL PERMIT AS A
 SHELL BUILDING. THIS TENANT FIT UP IS THE 1ST
 OCCUPANCY. THE DESIGN DOCUMENTS LIST THIS AS A LEVEL LL
 ALTERATION, PLEASE NOTE AS THE 1ST TENANT FIT UP TO THE
 SHELL BUILDING THIS IS CONSIDERED NEW CONSTRUCTION, NOT
 A LEVEL II ALTERATION AND SHOULD RECEIVE A CERTIFICATE
 OF OCCUPANCY.
 SEE 2014 EXISTING 101.4.1. BUILDINGS NOT PREVIOUSLY
 OCCUPIED. A BUILDING OR PORTION OF A BUILDING THAT HAS
 NOT BEEN PREVIOUSLY OCCUPIED OR USED FOR ITS INTENDED
 PURPOSE IN ACCORDANCE WITH THE LAWS IN EXISTENCE AT THE
 TIME OF ITS COMPLETION SHALL COMPLY WITH THE PROVISIONS
 OF THE FLORIDA BUILDING CODE, BUILDING OR FLORIDA
 BUILDING CODE, RESIDENTIAL, AS APPLICABLE, FOR NEW
 CONSTRUCTION OR WITH ANY CURRENT PERMIT FOR SUCH
 OCCUPANCY.
  
 2) COMPLIED.
  
 3A) SEMI-COMPLIED. OVERHEAD DOORS AND STOREFRONT FRAMES
 ARE NOW PART OF THIS PERMIT.
  
 3B) 2ND REQUEST. SHEET A-2 HAS NOTES LABELED
 SUPPLEMENTAL NOTES THAT ARE REQUIRING OVERHEAD DOOR AND
 STOREFRONT DOOR, HOLLOW METAL DOORS AND LINTELS. THE
 DESIGNER OF RECORD IN RESPONSE INDICATES THE CONTRACTOR
 WILL SUBMIT TO THE BUILDING DEPARTMENT.
 PLEASE SUBMIT THE LISTED PRODUCT APPROVALS, THIS WAS
 DECLARED A DEFERRED SUBMITTAL UNDER 107.3.4.2.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, LINTELS
  
 3C) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4-7) COMPLIED.
  
 8) BUILDING PROVISO:
 SHELL PERMIT : 13060228
 8146 OKEECHOBEE BLVD.
 MEMO: FROM KUOPPALA & ASSOC.
 DATED: 05/14/15
 BUILD: 5& 6
 ADDENDUM A ITEM # 1. DELETE ALL CONCRETE FLOOR SLABS,
 SHALL BE POURED WITH INTERIOR BUILD OUT.
 FLOOD ZONE CERTIFICATES, 2014 FBC BUILDING 1612 AND
 CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "AH" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES OF ELEVATION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
  
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. COMPLETED WITH PLAN REVIEW FOR SHELL BUILDING.
  
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 9) IMPACT FEES, IMPACT FEES MAY BE DUE EVEN THOUGH THIS
 IS 1ST TIME OCCUPANCY. TO DATE ZONING HAS NOT SEEN IF
 THERE HAS BEEN AN UPDATED TRAFFIC CONCURRENCY STUDY
 COMPLETED. THE P.B. COUNTY CONCURRENCY STUDY WILL NEED
 TO BE REVIEWED BY THE W. P. B. ZONING DEPARTMENT TO SEE
 AT WHAT STUDENT CAP WILL BE PUT ON THIS PROJECT. FROM
 THAT POINT THE PLANS WOULD GO TO PALM BEACH COUNTY
 IMPACT FEE OFFICE FOR ASSESSMENT.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-14 Cont ID  
Sent By jwitmer Date 2016-06-14 Time 11:07 Rev Time 0.00
Received By jwitmer Date 2016-06-13 Time 15:03 Sent To  
Notes
2016-06-14 11:07:40BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060592
 ADD: 8146 OKEECHOBEE BLVD.
 CONT: J.J. MALLEY ENTERPRISES
 TEL: 561-843-5325
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. JUNE 14, 2016
 ACTION: DENIED
  
 1) SHEET SP-1 CODE REFERENCES: LIST THIS TENANT FIT-UP
 AS A LEVEL LL ALTERATION AND THE BUILDING STRUCTURE
 BEING BUILT UNDER THE ORIGINAL PERMIT AS A SHELL
 BUILDING. THIS TENANT FIT UP IS THE 1ST OCCUPANCY. THE
 DESIGN DOCUMENTS LIST THIS AS A LEVEL LL ALTERATION,
 PLEASE NOTE AS THE 1ST TENANT FIT UP TO THE SHELL
 BUILDING THIS IS CONSIDERED NEW CONSTRUCTION AND SHOULD
 RECEIVE A CERTIFICATE OF OCCUPANCY.
 SEE 2014 EXISTING 101.4.1. BUILDINGS NOT PREVIOUSLY
 OCCUPIED. A BUILDING OR PORTION OF A BUILDING THAT HAS
 NOT BEEN PREVIOUSLY OCCUPIED OR USED FOR ITS INTENDED
 PURPOSE IN ACCORDANCE WITH THE LAWS IN EXISTENCE AT THE
 TIME OF ITS COMPLETION SHALL COMPLY WITH THE PROVISIONS
 OF THE FLORIDA BUILDING CODE, BUILDING OR FLORIDA
 BUILDING CODE, RESIDENTIAL, AS APPLICABLE, FOR NEW
 CONSTRUCTION OR WITH ANY CURRENT PERMIT FOR SUCH
 OCCUPANCY.
  
 2) SHEET A1 THE DEMOLITION PLAN SHOWS NEW OPENINGS IN
 THE EXTERIOR WALL OR OPENINGS BEING MADE WIDER. SHEET
 A3 SHOWS A DETAIL FOR A NEW LINTEL AND FILLED CELL ON
 EACH SIDE OF THE NEW DOORWAY & FRAME. THERE IS NO
 DETAIL FOR OPENING 39 & 40 IF DEPICTED IS TO BLOCK WORK
 BETWEEN THE 2 DOOR WAYS 24 INCHES OF BLOCK, IT APPEARS
 TO BE 3 CELLS? IF SO WILL THERE BE (2) SINGLE LINTELS
 OR ONE LONG LINTEL? HOW MANY VERTICAL REBARS IN THE 3
 CELL BLOCKWORK, 2 OR 3? ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3A) SHEET A-2 HAS NOTES LABELED SUPPLEMENTAL NOTES THAT
 ARE REQUIRING OVERHEAD DOOR AND STOREFRONT DOOR AND
 FRAMES TO BE UNDER SEPARATE PERMIT. THEN PLEASE REMOVE
 THIS WORK FROM THIS PLAN. 107.2.4 EXTERIOR WALL
 ENVELOPE. CONSTRUCTION DOCUMENTS FOR ALL BUILDINGS
 SHALL DESCRIBE THE EXTERIOR WALL ENVELOPE IN SUFFICIENT
 DETAIL TO DETERMINE COMPLIANCE WITH THIS CODE. THE
 CONSTRUCTION DOCUMENTS SHALL PROVIDE DETAILS OF THE
 EXTERIOR WALL ENVELOPE AS REQUIRED, INCLUDING FLASHING,
 INTERSECTIONS WITH DISSIMILAR MATERIALS, CORNERS, END
 DETAILS, CONTROL JOINTS, INTERSECTIONS AT ROOF, EAVES
 OR PARAPETS, MEANS OF DRAINAGE, WATER-RESISTIVE
 MEMBRANE AND DETAILS AROUND OPENINGS. THE CONSTRUCTION
 DOCUMENTS SHALL INCLUDE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS THAT PROVIDE SUPPORTING DOCUMENTATION THAT
 THE PROPOSED PENETRATION AND OPENING DETAILS DESCRIBED
 IN THE CONSTRUCTION DOCUMENTS MAINTAIN THE WEATHER
 RESISTANCE OF THE EXTERIOR WALL ENVELOPE. THE
 SUPPORTING DOCUMENTATION SHALL FULLY DESCRIBE THE
 EXTERIOR WALL SYSTEM WHICH WAS TESTED, WHERE
 APPLICABLE, AS WELL AS THE TEST PROCEDURE USED.
  
 3B) SHEET A-2 HAS NOTES LABELED SUPPLEMENTAL NOTES THAT
 ARE REQUIRING OVERHEAD DOOR AND STOREFRONT DOOR, HOLLOW
 METAL DOORS AND LINTELS TO BE SUBMITTED TO THE BUILDING
 DEPARTMENT PRIOR TO CONSTRUCTION.
 PLEASE SUBMIT THE LISTED PRODUCT APPROVALS, THIS WAS
 DECLARED A DEFERRED SUBMITTAL UNDER 107.3.4.2.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, LINTELS
  
 3C) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) SHEET A2 THE BOYS RESTROOM PARTITION TYPE # 4 IS
 SHOWN TO HAVE 5/8 INCH DURAROCK 2 FOOT HIGH? IS THE
 DURAROCK TO BE IN THE RESTROOM SIDE OF THE WALL?
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 5) SHEET A2 NOR A4 RESTROOM DETAIL INDICATE CODE
 COMPLIANCE WITH 2014 FBC-B 1210.2.2 WALLS AND
 PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 6) SHEET A2 NOR A4 RESTROOM DETAIL SHOW THE TYPE OF
 WALL CONSTRUCTION FOR THE WALLS BETWEEN CLASSROOM #9
 AND THE GIRLS RESTROOM AS WELL AS THE BOYS RESTROOM.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) SHEET A3 ROOM FINISH SCHEDULE INDICATES THE USE OF
 SEALED CONCRETE FLOORS AND 4 INCH VINYL BASE IN THE
 RESTROOMS. SECTION 1210.2.1 FLOORS & WALL BASES ONLY
 REQUIRE A SMOOTH, HARD, NONABSORBENT VERTICAL BASE THAT
 EXTENDS UPWARD ONTO THE WALLS NOT LESS THAN 4 INCHES .
 THE CODE DOES NOT REQUIRE THE SAME MATERIAL FOR THE
 FLOOR AND BASE ONLY THAT THERE IS AN ADEQUATE SEAL
 BETWEEN MATERIALS TO RESTRICT MOISTURE FROM GETTING
 BEHIND THE SURFACE MATERIAL AND INTO THE WALL
 CONSTRUCTION. PLEASE PROVIDE COMPLIANCE.
 8) IMPACT FEES, IMPACT FEES MAY BE DUE EVEN THOUGH THIS
 IS 1ST TIME OCCUPANCY. TODATE ZONING HAS NOT SEEN IF
 THERE HAS BEEN AN UPDATED TRAFFIC CONCURRENCY STUDY
 COMPLETED. THE P.B. COUNTY CONCURRENCY STUDY WILL NEED
 TO BE REVIEWED BY THE W. P. B. ZONING DEPARTMENT TO SEE
 AT WHAT STUDENT CAP WILL BE PUT ON THIS PROJECT. FROM
 THAT POINT THE PLANS WOULD GO TO PALM BEACH COUNTY
 IMPACT FEE OFFICE FOR ASSESSMENT.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-24 Cont ID  
Sent By vperez Date 2016-08-24 Time 08:23 Rev Time 0.00
Received By vperez Date 2016-08-24 Time 08:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-16 Cont ID  
Sent By vperez Date 2016-06-16 Time 14:23 Rev Time 0.00
Received By vperez Date 2016-06-16 Time 11:56 Sent To  
Notes
2016-06-16 14:59:28INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS (GATES), CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. ELECTRICAL NOTES, PLEASE REVISE TYPO TO INDICATE NEC
 2011 NOT 2012 AS SHOWN.
 3. PLEASE LABEL THE RECEPTACLE OUTLET IN STAFF LOUNGE
 AREA WITHIN 6FT OF SINK TO BE GFCI PROTECTED. SEE REF
 OUTLET. NEC 210.8B5
 4. LABEL GFCI ALL RECEPTACLES FOR THE DRINKING FOUNTAIN
 SHOWN ON CIRCUIT B2 THRU B10 PER NEC 422.52
 5. PROVIDE PHOTOMETRIC FOR EXTERIOR AND INTERIOR AREAS.
 FBC 107.3.5 AND FBC SECTION 468 .3.7 LIGHTING
 REQUIREMENTS
 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-08-19 Cont ID  
Sent By wjolin Date 2016-08-19 Time 10:08 Rev Time 0.00
Received By wjolin Date 2016-08-19 Time 09:53 Sent To  
Notes
2016-08-19 10:08:178146 OKEECHOBEE BOULEVARD
 PERMIT #16060592
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: PROVIDE A TRAFFIC SITE PLAN INDICATING
 FIRE LANES, FIRE HYDRANTS AND VEHICLE STACKING LOCATION
 (CHILD DROP-OFF/PICK UP). NOTE FIRE LANES ARE REQUIRED
 TO BE 20 FEET IN CLEAR, UNOBSTRUCTED (NO
 PARKING/WAITING) WIDTH.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By wjolin Date 2016-06-15 Time 16:00 Rev Time 0.00
Received By wjolin Date 2016-06-15 Time 15:07 Sent To  
Notes
2016-06-15 15:46:488146 OKEECHOBEE BOULEVARD
 PERMIT #16060592
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COVER SHEET AND SHEET SP-1 INDICATES FLOOR AREAS OF
 11,900 SQ.FT. AND 1,440 SQ.FT. SEPARATED WITH A 4-HOUR
 CMU WALL (FIRE WALL?), HOWEVER, UTILITIES AND EGRESS
 ARE SHARED BETWEEN THE TWO SPACES. EDUCATIONAL
 OCCUPANCY BUILDINGS 12,000 SQ.FT. SHALL BE PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 SHEET LS-1: DISTANCE BETWEEN EXIT SIGNS IN CORRIDOR
 EXCEEDS 100 FEET. PER NFPA 101-7.10.1.5.2 NEW SIGN
 PLACEMENT SHALL BE SUCH THAT NO POINT IN AN EXIT ACCESS
 CORRIDOR IS IN EXCESS OF THE RATED VIEWING DISTANCE OR
 100 FEET, WHICHEVER IS LESS, FROM THE NEAREST SIGN.
  
 COULD NOT LOCATE ANY DOOR PANIC HARDWARE. PER NFPA
 101-14.2.2.2.2 ANY DOOR IN A REQUIRED MEANS OF EGRESS
 FROM AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH
 OR LOCK ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE.
  
 PER NFPA 1-8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE
 AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE A TRAFFIC SITE PLAN INDICATING FIRE LANES, FIRE
 HYDRANTS AND VEHICLE STACKING LOCATION (CHILD
 DROP-OFF/PICK UP). NOTE FIRE LANES ARE REQUIRED TO BE
 20 FEET IN CLEAR, UNOBSTRUCTED (NO PARKING/WAITING)
 WIDTH.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-24 Cont ID  
Sent By gjohnson Date 2016-08-24 Time 16:23 Rev Time 0.00
Received By gjohnson Date 2016-08-08 Time 14:04 Sent To  
Notes
2016-08-08 14:04:48C34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-21 Cont ID  
Sent By gjohnson Date 2016-06-21 Time 13:43 Rev Time 0.00
Received By gjohnson Date 2016-06-09 Time 13:51 Sent To  
Notes
2016-06-09 13:51:38C30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-06-14 Cont ID  
Sent By jwitmer Date 2016-06-14 Time 11:06 Rev Time 0.00
Received By jwitmer Date 2016-06-14 Time 11:06 Sent To  
Notes
2016-06-14 11:06:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060592
 ADD: 8146 OKEECHOBEE BLVD.
 CONT: J.J. MALLEY ENTERPRISES
 TEL: 561-843-5325
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. JUNE 14, 2016
 ACTION: DENIED
  
 1) IMPACT FEES, IMPACT FEES MAY BE DUE EVEN THOUGH THIS
 IS 1ST TIME OCCUPANCY. TODATE ZONING HAS NOT SEEN IF
 THERE HAS BEEN AN UPDATED TRAFFIC CONCURRENCY STUDY
 COMPLETED. THE P.B. COUNTY CONCURRENCY STUDY WILL NEED
 TO BE REVIEWED BY THE W. P. B. ZONING DEPARTMENT TO SEE
 AT WHAT STUDENT CAP WILL BE PUT ON THIS PROJECT. FROM
 THAT POINT THE PLANS WOULD GO TO PALM BEACH COUNTY
 IMPACT FEE OFFICE FOR ASSESSMENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-22 Cont ID  
Sent By ccole Date 2016-08-22 Time 12:01 Rev Time 0.00
Received By ccole Date 2016-08-22 Time 08:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-13 Cont ID  
Sent By ccole Date 2016-06-13 Time 16:42 Rev Time 0.00
Received By ccole Date 2016-06-13 Time 15:03 Sent To  
Notes
2016-06-13 17:30:211ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16060592
 6/13/16
  
 1) SHEET M-1: FIRE DAMPERS MISSING AT DUCT DROPS
 THROUGH RATED CORRIDOR CEILINGS.
  
 2) M-1: PROVIDE A RETURN AIR GRILL SYMBOL FOR RTU-1.
  
 3) M-1: EXHAUST FANS EF-4 & EF-5 ARE UNDERSIZED IN
 CAPACITIES PER TABLE 403.3 FOOTNOTE E.
  
 4) M-1 & M-2: PROVIDE AN EXHAUST AIR CALCULATION FOR
 EF-6 IN THE STAFF LOUNGE.
  
 5) M-1: PROVIDE NOTE #7 AT RTU'S 8,9,10, & 11.
  
 6) M-1: CORRECT NOTE #17 INDICATING 3/4" CONDENSATE
 PIPING- THE PLAN INDICATES 2"
  
 7) M-1: PROVIDE O/A DAMPERS WITH AUTOMATIC CONTROL FOR
 THE RTU'S- SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  
 8) M-1: PROVIDE A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE EXHAUST OUTLET LOUVERS- SEE NOTE #12
  
 9) M-1: PROVIDE NOTE #15 AT FLEX DUCT PENETRATING THE
 RATED OFFICE #5 WALL, AND A DETAIL SHOWING HOW THE
 ACCESS TO THE DAMPER WILL BE PROVIDED
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2016-08-16 Cont ID  
Sent By jwitmer Date 2016-08-16 Time 11:38 Rev Time 0.00
Received By jwitmer Date 2016-08-16 Time 11:38 Sent To  
Notes
2016-08-16 11:38:22) BUILDING PROVISO:
 SHELL PERMIT : 13060228
 8146 OKEECHOBEE BLVD.
 MEMO: FROM KUOPPALA & ASSOC.
 DATED: 05/14/15
 BUILD: 5& 6
 ADDENDUM A ITEM # 1. DELETE ALL CONCRETE FLOOR SLABS,
 SHALL BE POURED WITH INTERIOR BUILD OUT.
 FLOOD ZONE CERTIFICATES, 2014 FBC BUILDING 1612 AND
 CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "AH" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES OF ELEVATION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
  
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. COMPLETED WITH PLAN REVIEW FOR SHELL BUILDING.
  
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2016-08-10 Cont ID  
Sent By shill Date 2016-08-10 Time 15:57 Rev Time 0.00
Received By shill Date 2016-08-10 Time 15:57 Sent To  
Notes
2016-08-10 15:59:39A PLAN REVIEW WILL BE PERFORMED WHEN PLANS ARE
 AVAILABLE.
 NOT IN BIN 8/10/16
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-08-24 Cont ID  
Sent By gjohnson Date 2016-08-24 Time 16:22 Rev Time 0.00
Received By gjohnson Date 2016-08-24 Time 16:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-21 Cont ID  
Sent By gjohnson Date 2016-06-21 Time 13:29 Rev Time 0.00
Received By gjohnson Date 2016-06-21 Time 13:29 Sent To  
Notes
2016-06-21 13:35:461ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE WATER RISER DIAGRAM.PER WPB AMEND TO
 FBC SEC. 107.3.5.1.3(13)
  
 2. SHT. P-1 SLAB PATCH DETAIL REBAR PINS EXTENDING INTO
 EXISTING CONCRETE REQUIRED. WPB AMEND.TO FBC 107.2.1

Review Stop Z ZONING
Rev No 2 Status F Date 2016-08-16 Cont ID  
Sent By eschneid Date 2016-08-16 Time 16:52 Rev Time 0.75
Received By eschneid Date 2016-08-16 Time 15:45 Sent To  
Notes
2016-08-16 16:52:07FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) REPEAT COMMENT: THE LATEST PALM BEACH COUNTY TRAFFIC
 PERFORMANCE STANDARDS REVIEW LETTER ISSUED ON APRIL 21,
 2014, APPROVED 29,012 SF OF MEDICAL OFFICE (OR ANY
 COMBINATION OF GENERAL AND MEDICAL OFFICES), 3,820 SF
 BANK WDT, AND 12,000 SF GENERAL RETAIL. RESOLUTION NO.
 288-11 INCLUDES DEVELOPMENT REGULATION 15.B)V) REQUIRES
 THAT A CHANGE IN THE MIX OF USES APPROVED IN THE PALM
 BEACH COUNTY TRAFFIC PERFORMANCE STANDARDS REVIEW
 LETTER SHALL REQUIRE A NEW PALM BEACH COUNTY TRAFFIC
 PERFORMANCE STANDARDS REVIEW LETTER. PRIOR TO ZONING
 APPROVAL OF THE BUILDING PERMIT, PROVIDE AN UPDATED
 PALM BEACH COUNTY TRAFFIC PERFORMANCE STANDARDS REVIEW
 LETTER APPROVING THE CONVERSION OF 13,340 SF OF MEDICAL
 OFFICE TO A 150 STUDENT HIGH SCHOOL.
  
 2) PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY FOR THIS BUILDING, AN AS-BUILT MINOR
 AMENDMENT SHALL BE SUBMITTED TO THE PLANNING DIVISION
 AND AN APPROVAL LETTER ISSUED THAT REFLECTS THE SITE,
 LANDSCAPE AND ELEVATION CHANGES BASED ON THIS BUILDING
 PERMIT.
  
 3) REPEAT COMMENT: THE NEW DOORWAY OPENINGS ON THE WEST
 AND NORTH SIDES OF THE BUILDING APPEAR TO CONFLICT WITH
 THE APPROVED LANDSCAPE PLANS. ZONING WILL NOT APPROVE
 THIS PERMIT UNTIL A LANDSCAPE PERMIT IS SUBMITTED THAT
 SHOWS THE EXISTING LANDSCAPE ADJUSTED TO REFLECT THE
 PROPOSED DOORWAY OPENINGS. THE UPDATED PLANS SHALL
 VERIFY THAT THERE WILL BE NO LANDSCAPE DEFICIENCIES
 BASED ON THE NEW OPENINGS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By eschneid Date 2016-06-15 Time 14:40 Rev Time 2.00
Received By eschneid Date 2016-06-14 Time 16:13 Sent To  
Notes
2016-06-15 15:03:18FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE LATEST PALM BEACH COUNTY TRAFFIC PERFORMANCE
 STANDARDS REVIEW LETTER ISSUED ON APRIL 21, 2014,
 APPROVED 29,012 SF OF MEDICAL OFFICE (OR ANY
 COMBINATION OF GENERAL AND MEDICAL OFFICES), 3,820 SF
 BANK WDT, AND 12,000 SF GENERAL RETAIL. RESOLUTION NO.
 288-11 INCLUDES DEVELOPMENT REGULATION 15.B)V) REQUIRES
 THAT A CHANGE IN THE MIX OF USES APPROVED IN THE PALM
 BEACH COUNTY TRAFFIC PERFORMANCE STANDARDS REVIEW
 LETTER SHALL REQUIRE A NEW PALM BEACH COUNTY TRAFFIC
 PERFORMANCE STANDARDS REVIEW LETTER. PRIOR TO ZONING
 APPROVAL OF THE BUILDING PERMIT, PROVIDE AN UPDATED
 PALM BEACH COUNTY TRAFFIC PERFORMANCE STANDARDS REVIEW
 LETTER APPROVING THE CONVERSION OF 13,340 SF OF MEDICAL
 OFFICE TO A 150 STUDENT HIGH SCHOOL.
  
 2) THE SITE PLAN PROVIDED ON SHEET SP-1 SHOWS A 13,200
 SQUARE FOOT BUILDING. THE SHELL BUILDING PERMIT WAS FOR
 A 13,340 SQUARE FOOT BUILDING. THE SITE PLAN AND SITE
 PLAN FOOTNOTES SHALL BE CORRECTED TO REFLECT THE ACTUAL
 BUILDING CONDITION.
  
 3) THE FLOOR PLANS SHOW NEW OPENINGS ON MULTIPLE
 FACADES. PROVIDE UPDATED ELEVATION DRAWINGS SHOWING THE
 FACADE THAT MATCHES THE PROPOSED BUILDING REVISIONS.
  
 4) THE NEW DOORWAY OPENINGS ON THE WEST AND NORTH SIDES
 OF THE BUILDING APPEAR TO CONFLICT WITH THE APPROVED
 LANDSCAPE PLANS. ZONING WILL NOT APPROVE THIS PERMIT
 UNTIL A LANDSCAPE PERMIT IS SUBMITTED THAT SHOWS THE
 EXISTING LANDSCAPE ADJUSTED TO REFLECT THE PROPOSED
 DOORWAY OPENINGS. THE UPDATED PLANS SHALL VERIFY THAT
 THERE WILL BE NO LANDSCAPE DEFICIENCIES BASED ON THE
 NEW OPENINGS.
  
 5) RESOLUTION NO. 288-11 REQUIRES THAT ROOF MOUNTED AIR
 CONDITIONING, MECHANICAL EQUIPMENT, SATELLITE DISHES,
 GENERATORS, ETC., SHALL BE SCREENED FROM VIEW ON ALL
 SIDES BY A VISUALLY OPAQUE BARRIER CONSISTENT WITH THE
 COLOR, CHARACTER AND ARCHITECTURAL STYLE OF THE
 STRUCTURES. THE HEIGHT OF THE OPAQUE BARRIER SHALL BE
 AS REQUIRED TO PROVIDE AMPLE SCREENING. PROVIDE PLANS
 TO VERIFY THAT THE PROPOSED NEW ROOFTOP UNITS, TO
 INCLUDE THEIR PLACEMENT ON THE EXISTING CURBS, ARE
 SCREENED FROM VIEW. DIMENSIONS SHALL BE INCLUDED.
  
 6) THE PLANS SHOW WALL MOUNTED EXTERIOR LIGHTS. PROVIDE
 PHOTOMETRIC PLANS TO SHOW THE FOOT CANDLE LEVEL AT THE
 WESTERN PROPERTY LINE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
  
  