| 2016-06-17 15:33:21 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16060591 |
| | ADD: 524 DATURA ST. |
| | CONT: MOSS & ASSOCIATES, LLC |
| | TEL: 561-228-6420 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JUNE 17/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1.01 SHOWS THE USE OF 2 FT. 8 IN. DOORS IN |
| | 3'-0" OPENINGS. PERMIT # 14120850 INDICATED ALL DOOR |
| | OPENINGS (WRAPPED OPENINGS AT 36 INCHES FINISH |
| | DIMENSION) THE 2014 FBC-B SECTION 1008.1.1. SIZE OF |
| | DOORS, REQUIRES A MINIMUM CLEAR OPENING OF 32 INCHES. |
| | THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE |
| | SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL |
| | PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR |
| | OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| | WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 2) A-1.01 NOR THE ELECTRICAL SHEET SHOW HOW COMPLIANCE |
| | WITH 2014 FBC-B SECTION 1006.3(2) WILL BE ACHIEVED. |
| | 1006.3 EMERGENCY POWER FOR ILLUMINATION. |
| | THE POWER SUPPLY FOR MEANS OF EGRESS ILLUMINATION SHALL |
| | NORMALLY BE PROVIDED BY THE PREMISES? ELECTRICAL |
| | SUPPLY. |
| | IN THE EVENT OF POWER SUPPLY FAILURE, AN EMERGENCY |
| | ELECTRICAL SYSTEM SHALL AUTOMATICALLY ILLUMINATE ALL OF |
| | THE FOLLOWING AREAS: |
| | 1. AISLES AND UNENCLOSED EGRESS STAIRWAYS IN ROOMS AND |
| | SPACES THAT REQUIRE TWO OR MORE MEANS OF EGRESS. |
| | |
| | 2. CORRIDORS, INTERIOR EXIT STAIRWAYS AND RAMPS AND |
| | EXIT PASSAGEWAYS IN BUILDINGS REQUIRED TO HAVE TWO OR |
| | MORE EXITS. |
| | |
| | 3. EXTERIOR EGRESS COMPONENTS AT OTHER THAN THEIR |
| | LEVELS OF EXIT DISCHARGE UNTIL EXIT DISCHARGE IS |
| | ACCOMPLISHED FOR BUILDINGS REQUIRED TO HAVE TWO OR MORE |
| | EXITS. |
| | |
| | 3) SHEET A-1.01 DOES NOT SHOW THE LOCATION WHERE FIRE |
| | EXTINGUISHERS ARE TO BE LOCATED. FBC-B 906.1(5) WHERE |
| | REQUIRED BY THE FIRE PREVENTION CODE. |
| | |
| | 4) PLEASE NOTE THE COVER SHEET INDICATES THIS IS A |
| | FULLY FIRE SPRINKLERED BUILDING. PART OF THE SCOPE OF |
| | WORK UNDER THIS PERMIT IS THE INSTALATION OF ACOUSTICAL |
| | CEILINGS. THERE WAS NO FIRE SPRINKLER PLANS SUBMITTED |
| | FOR THE DROPPING OF THE FIRE SPRINKLERS TO THE NEW |
| | ACOUSTICAL CEILING HEIGHT. 2014 FBC-B 903.3.1.1 NFPA 13 |
| | SPRINKLER SYSTEMS. WHERE THE PROVISIONS OF THIS CODE |
| | REQUIRE THAT A BUILDING OR PORTION THEREOF BE EQUIPPED |
| | THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH THIS SECTION, SPRINKLERS SHALL BE |
| | INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13 EXCEPT |
| | AS PROVIDED IN SECTION 903.3.1.1.1. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |