Plan Review Details - Permit 16060502
Plan Review Stops For Permit 16060502
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-19 Cont ID  
Sent By jwitmer Date 2016-09-19 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2016-09-19 Time 08:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-24 Cont ID  
Sent By jwitmer Date 2016-06-24 Time 14:13 Rev Time 0.00
Received By jwitmer Date 2016-06-24 Time 13:25 Sent To  
Notes
2016-06-24 14:13:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060502
 ADD: 1150 45TH ST.
 CONT: JTL A/C
 TEL: 954-584-0070
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 24/ 2016
 ACTION: DENIED
  
 1) SHEET A2.4 & A3.0 BOTH SHOW ROOF CURB DETAILS. SHEET
 M4.1 DETAIL 2 SHOWS A CONNECTING DETAIL FROM THE CURB
 TO THE CURB CONNECTOR TO THE NEW MECHANICAL EQUIPMENT.
 THE PLANS INDICATE SECURE NEW EQUIPMENT TO CURBS WITH
 #10 TEK SCREWS @ 5 INCHES O. C. ALL AROUND THE UNIT.
  
 THERE IS NO WIND DESIGN CRITERIA GIVEN HOW THIS
 ATTACHMENT WAS FORMULATED. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO WIND
 LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS
 GOVERN THE DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM
 OF THE STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 LATERAL FORCE-RESISTING SYSTEM
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-30 Cont ID  
Sent By vperez Date 2016-08-30 Time 12:02 Rev Time 0.00
Received By vperez Date 2016-08-30 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-25 Cont ID  
Sent By vperez Date 2016-06-25 Time 14:34 Rev Time 0.00
Received By vperez Date 2016-06-25 Time 14:27 Sent To  
Notes
2016-06-25 14:34:36INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS FOR
 LIGHTNING PROTECTION SHOWN FOR ROOFTOP UNITS AND
 ASSOCIATED EQUIPMENT. A NOTE WILL SUFFICE.
 2. ADDRESS MECHANICAL COMMENTS FOR A COMPLETE REVIEW.
 3. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-31 Cont ID  
Sent By pleduc Date 2016-08-31 Time   Rev Time 0.00
Received By pleduc Date 2016-08-31 Time 15:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-27 Cont ID  
Sent By pleduc Date 2016-06-27 Time   Rev Time 0.00
Received By pleduc Date 2016-06-27 Time 15:30 Sent To PC
Notes
2016-06-27 15:35:09THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET M 5.2 - DOES THIS SHEET INDICATE DUCT
 DETECTORS FOR EACH UNIT OR JSUT THOSE REQUIRED BY CODE?
  
 DUCT DETECTORS
 PER NFPA 90 A , CHAPTER 6 CONTROLS
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
 2) SHEET M 5.2 & E 2.2 - THERE ARE REFERENCES TO
 CONNECTIONS TO THE FIRE ALARM PANELS. ALL WORK ON THE
 FIRE ALARM SYSTEM SHALL BE SUBMITTED, INSTALLED, AND
 TESTED BY CERTIFIED LIFE SAFETY CONTRACTORS UNDER
 SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE AN INDICATING NOTE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-20 Cont ID  
Sent By gjohnson Date 2016-09-20 Time 10:42 Rev Time 0.00
Received By gjohnson Date 2016-08-25 Time 12:40 Sent To  
Notes
2016-08-25 12:40:50C03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-05 Cont ID  
Sent By lmarchan Date 2016-07-05 Time 14:29 Rev Time 0.00
Received By lmarchan Date 2016-06-08 Time 13:23 Sent To  
Notes
2016-06-25 14:35:07SENT TO FIRE
2016-06-09 13:24:10C14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-31 Cont ID  
Sent By ccole Date 2016-08-31 Time 07:45 Rev Time 0.00
Received By ccole Date 2016-08-30 Time 17:21 Sent To  
Notes
2016-08-31 07:54:50MECHANICAL PROVISOS
 8/31/16
  
 1) A SEPARATE PERMIT IS REQUIRED FOR THE BOILER
 INSTALLATIONS.
  
 2) SIGNED AND SEALED ENGINEERING FOR ATTACHMENT OF THE
 RTU'S AND ROOF CURB ADAPTERS SHALL BE SUBMITTED AND
 APPROVED PRIOR TO FIRST MECHANICAL INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By ccole Date 2016-06-15 Time 10:24 Rev Time 0.00
Received By ccole Date 2016-06-15 Time 10:24 Sent To  
Notes
2016-06-15 10:56:441ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16060502
 6/15/16
  
 1) SHEET M1.1: PROVIDE THE EFFICIENCY RATINGS OF THE
 RTU'S IN THE SCHEDULE PER TABLE C403.2.3(1) FBC-14
 ENERGY CONSERVATION.
  
 2) M1.1: PROVIDE THE SCOP OF THE DATAAIRE AC SYSTEM IN
 THE IT ROOM- TABLE C403.2.3(10).
  
 3) M2.1: THE PLAN DOES NOT SHOW THE OPERATIONS
 MANAGER'S ROOM S-116A.
  
 4) M3.1: PROVIDE A COMBUSTION AIR CALCULATION FOR THE
 BOILER ROOMS AND MORE SPECIFIC INFORMATION ABOUT THE
 SIDEWALL VENTS INCLUDING- TYPE AND SIZE, AND EXACT
 LOCATIONS SHOWN WITH DIMENSIONS FROM FLOOR AND CEILING-
 SEE SECTION 304 FBC-14 FUEL GAS.
  
 5) M3.1: CLARIFY NOTE #8 AND SHOW THE VENT PIPE RUN AND
 TERMINATION LOCATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE BOILERS AND VENTING SYSTEMS.
  
 6) M4.1: PROVIDE THE WIND LOAD DESIGN CRITERIA ON THE
 PLAN INCLUDING WIND SPEED, IMPORTANCE FACTOR, RISK
 CATEGORY, AND EXPOSURE- SEE SECTION 301.15 FBC-14
 MECHANICAL, AND SECTION 1609 FBC-14 BUILDING.
  
 7) M4.1: PROVIDE A DETAIL FOR ANCHORING THE CU-1 TO THE
 EXISTING STAND.
  
 8) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF RTU'S 3-9 PER SECTION 606.2.1. PLEASE
 PROVIDE NOTES AND DETAILS ON TH PLAN VERIFYING
 COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-09-20 Cont ID  
Sent By gjohnson Date 2016-09-20 Time 10:41 Rev Time 0.00
Received By gjohnson Date 2016-09-20 Time 10:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-22 Cont ID  
Sent By gjohnson Date 2016-06-22 Time 15:32 Rev Time 0.00
Received By gjohnson Date 2016-06-22 Time 15:32 Sent To  
Notes
2016-06-22 15:32:191ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
  
 1. A SEPARATE PERMIT IS REQUIRED FOR BOILER
 INSTALLATION. PER WPB AMEND.TO FBC 105.1
  
 2. PROVIDE INSTILLATION GUIDE FOR VENTING ON BOILERS.
 PER WPB AMEND.TO FBC 107.2.1
  
 3. PROVIDE BTU LOAD OF EXISTING BOILERS . PER WPB
 AMEND.TO FBC 107.2.1
  
 4.IF NEW BOILER BTU LOAD IS LARGER THAN EXISTING
 PROVIDE EXISTING GAS PIPE SIZES, LENGTH AND PRESSURE.
 PER WPB AMEND.TO FBC 107.2.1

Review Stop Z ZONING
Rev No 2 Status P Date 2016-09-16 Cont ID  
Sent By njwira Date 2016-09-16 Time 16:01 Rev Time 0.00
Received By njwira Date 2016-09-16 Time 14:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-10 Cont ID  
Sent By nwier Date 2016-06-10 Time 16:19 Rev Time 0.00
Received By njwira Date 2016-06-10 Time 16:19 Sent To E
Notes
2016-06-10 16:20:296/10/16- FAILED
 1. NEED ELEVATION DRAWINGS. MECHANICAL EQUIPMENT CANNOT
 EXCEED 6FT. IN THE COMMUNITY SERVICES DISTRICT.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  