Plan Review Details - Permit 16060495
Plan Review Stops For Permit 16060495
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-20 Cont ID  
Sent By mvaldes Date 2016-07-20 Time 12:07 Rev Time 0.00
Received By mvaldes Date 2016-07-20 Time 11:53 Sent To  
Notes
2016-07-20 12:07:27REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO'S
  
 - GFCI PROTECTION REQUIRED FOR POOL HEATERS NEC 680.22
  
 - HEATER GROUNDING SHALL BE BONDED TO POOL
 EQUALPOTENTIAL NEC 680.26(6)(B)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-09 Cont ID  
Sent By mvaldes Date 2016-06-09 Time 09:35 Rev Time 0.00
Received By mvaldes Date 2016-06-09 Time 09:34 Sent To  
Notes
2016-06-09 09:37:35REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
  
 - 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
  
 - PROVIDE A SITE SPECIFIC PLAN SHOWING THE LOCATION OF
 EQUIPMENT ALONG WITH SOME SORT OF DIAGRAM OR PANEL
 SCHEDULE SHOWING WIRE AND BREAKER SIZES.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-20 Cont ID  
Sent By mvaldes Date 2016-07-20 Time 12:07 Rev Time 0.00
Received By mvaldes Date 2016-07-19 Time 14:00 Sent To  
Notes
2016-07-19 14:00:50RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-09 Cont ID  
Sent By mvaldes Date 2016-06-09 Time 09:37 Rev Time 0.00
Received By mvaldes Date 2016-06-08 Time 13:36 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-09 Cont ID  
Sent By mvaldes Date 2016-06-09 Time 09:37 Rev Time 0.00
Received By tklarge Date 2016-06-09 Time 06:08 Sent To  
Notes
***NONE***