Plan Review Details - Permit 16060273
Plan Review Stops For Permit 16060273
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2016-08-31 Cont ID  
Sent By jgomez Date 2016-08-31 Time 14:09 Rev Time 0.00
Received By jgomez Date 2016-08-31 Time 14:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2016-08-19 Cont ID  
Sent By jgomez Date 2016-08-19 Time 14:46 Rev Time 0.00
Received By jgomez Date 2016-08-19 Time 14:46 Sent To  
Notes
2016-08-19 15:24:12RESIDENTIAL (R3) REVISION, FIFTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT
 THE STAIR HALL. PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL COVER PAGES AND THE CORRESPONDING DRAWINGS.
  
 RESPONSE:
 FLORIDA PRODUCT APPROVAL FL16708-R4 SUBMITTED WAS
 MARKED WITH SELECTED DOOR FL16708.1. THE DESIGN
 PRESSURES FOR THIS DOOR ARE +/-50PSF FOR A 3'-0" X
 8'-0" DOOR. THE DESIGN PRESSURES DON'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT ON SHEET A4. NEED
 TO PROVIDE PRODUCT APPROVAL FOR SPECIFIED INSWING ENTRY
 DOOR SIZE THAT MEETS THE CALCULATED DESIGN PRESSURES.
  
 2- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT APPROVAL
 PRIOR TO SUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-08-08 Cont ID  
Sent By jgomez Date 2016-08-08 Time 09:37 Rev Time 0.00
Received By jgomez Date 2016-08-08 Time 08:44 Sent To  
Notes
2016-08-08 09:37:23RESIDENTIAL (R3) REVISION ADDRESSING BUILDING PROVISO,
 FOURTH BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 08/08/16 MET WITH DON STARR TO GO OVER RE- SUBMITTAL.
  
  
 ORIGINAL COMMENT:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) FLAT ROOF . AND, IDENTIFY APPROVED ASSEMBLY TO BE
 INSTALLED. NOTE: SIGNED & SEALED RAS 117 CALCULATIONS
 WILL BE REQUIRED IF THE ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES OF SEC. R301.
  
 NOTE: KEEP IN MIND THAT THERE ARE TWO DIFFERENT
 APPLICATIONS. THERE IS A FLAT ROOF ASSEMBLY OVER THE
 ENTRY TOWER AND THERE IS ANOTHER FLAT ROOF FOR THE
 SECOND FLOOR DECK. THE SECOND FLOOR DECK ASSEMBLY
 REQUIRES A SYSTEM THAT IS DESIGNED TO RECEIVE TILE.
  
 RESPONSE:
 ENGINEERED RAS 117 CALCULATIONS SUBMITTED REFERENCE
 FLORIDA PRODUCT APPROVAL FL2144-R5 SYSTEM W-1. FLORIDA
 PRODUCT APPROVAL FL 2144-R5 WAS REVISED WITH REVISION
 #6. THE CURRENT FLORIDA PRODUCT APPROVAL IS FL2144-R6.
 THE CURRENT FLORIDA PRODUCT APPROVAL DOESN'T HAVE
 ASSEMBLY W-1. REVISE CALCULATIONS AS REQUIRED TO MATCH
 CURRENT PRODUCT APPROVAL.
 THERE IS ANOTHER PRODUCT APPROVAL SUBMITTED. THIS ONE
 IS A MIAMI-DADE NOA. THIS MIAMI-DADE NOA IS FOR
 INSULATED ASSEMBLIES ONLY. SELECT INSULATED ASSEMBLY TO
 BE INSTALLED AND PROVIDE RAS 117 CALCULATIONS
 ACCORDINGLY.
  
  
 ORIGINAL COMMENT:
 B) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED
 TILE AS SPECIFIED ON PLANS. AND, IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. NOTE: SIGNED & SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED IF THE ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES OF SEC. R301.
 SEAL-O-FLEX NOA 15-0406.03 SUBMITTED IS FOR INSULATED
 ASSEMBLIES. ARCHITECTURAL PLANS DON'T SPECIFY INSULATED
 ASSEMBLIES.
  
 RESPONSE:
 SELECT INSULATED ASSEMBLY TO BE INSTALLED AND PROVIDE
 RAS 117 CALCULATIONS ACCORDINGLY.
  
  
  
 ORIGINAL COMMENT:
 C) INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT
 THE STAIR HALL. PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL COVER PAGES AND THE CORRESPONDING DRAWINGS.
  
 RESPONSE: MIAMI-DADE NOA SUBMITTED EXPIRED IN 2012 AND
 IS NOT PART OF THE FLORIDA PRODUCT APPROVAL SUBMITTED.
 IF THERE IS NO CURRENT FLORIDA PRODUCT APPROVAL, THEN
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
 ADVICE IF LOCAL PRODUCT APPROVAL IS REQUESTED FOR
 FURTHER INFORMATION REGARDING SUBMITTAL PROCESS.
  
 2- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-07-25 Cont ID  
Sent By jgomez Date 2016-07-25 Time 17:03 Rev Time 0.00
Received By jgomez Date 2016-07-25 Time 17:00 Sent To  
Notes
2016-07-25 17:04:12RESIDENTIAL (R3) REVISION ADDRESSING BUILDING PROVISO,
 THIRD BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) FLAT ROOF. AND, IDENTIFY APPROVED ASSEMBLY TO BE
 INSTALLED. NOTE: SIGNED & SEALED RAS 117 CALCULATIONS
 WILL BE REQUIRED IF THE ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES OF SEC. R301.
  
 RESPONSE:
 (1) THE DESIGN PRESSURES SHOWN ON SHEET A-4 ARE TOO LOW
 FOR THE FLAT ROOF . SEE TABLE R301.2(2) OF
 FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE DESIGN
 PRESSURES ACCORDING TO HEIGHT AND BUILDING EXPOSURE.
  
 (2) SELECTED ASSEMBLY FROM FLORIDA PRODUCT APPROVAL
 FL2144-R6 CAN NOT BE USED BECAUSE IT DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES, INCLUDING CORNER
 ZONES (ROOF ZONE #3). THE MAXIMUM DESIGN PRESSURES OF
 THE ASSEMBLIES WITH ADHERED MEMBRANES CAN NOT BE
 EXTRAPOLATED. SEE LIMITATION #9. THE MAXIMUM DESIGN
 PRESSURES FOR ASSEMBLY W-A-2 ARE -85PSF. THE DESIGN
 PRESSURES FOR ROOF ZONE #3 ARE HIGHER. THEREFORE, IT
 CAN NOT BE USED. NOTE: COORDINATE DESIGN PRESSURES WITH
 ITEM #(1) ABOVE.
  
  
  
 ORIGINAL COMMENT:
 B) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED
 TILE AS SPECIFIED ON PLANS. AND, IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. NOTE: SIGNED & SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED IF THE ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES OF SEC. R301.
 SEAL-O-FLEX NOA 15-0406.03 SUBMITTED IS FOR INSULATED
 ASSEMBLIES. ARCHITECTURAL PLANS DON'T SPECIFY INSULATED
 ASSEMBLIES.
  
 RESPONSE: REPEAT COMMENT. (1) FLORIDA PRODUCT APPROVAL
 FL2144-R6 SUBMITTED CAN NOT BE USED. IT'S NOT DESIGNED
 TO RECEIVE TILE AS SPECIFIED ON PLANS. NOTE: REVISE
 DESIGN PRESSURES SHOWN ON THE FLAT ROOF UPLIFT DIAGRAM
 AND DETAIL #2 ON SHEET A-4 SUBMITTED.
  
  
 ORIGINAL COMMENT:
 C) INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT
 THE STAIR HALL. PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL COVER PAGES AND THE CORRESPONDING DRAWINGS.
  
 RESPONSE: NEED THE FLORIDA PRODUCT APPROVAL COVER PAGE
 THAT CORRESPONDS TO DRAWINGS SUBMITTED. IF THERE IS NO
 CURRENT FLORIDA PRODUCT APPROVAL, THEN MANUFACTURER MAY
 APPLY FOR LOCAL PRODUCT APPROVAL. ADVICE IF LOCAL
 PRODUCT APPROVAL IS REQUESTED FOR FURTHER INFORMATION
 REGARDING SUBMITTAL PROCESS.
  
 2- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-14 Cont ID  
Sent By jgomez Date 2016-06-14 Time 14:02 Rev Time 0.00
Received By jgomez Date 2016-06-14 Time 14:01 Sent To  
Notes
2016-06-14 14:18:1406/14/16: PER MEETING WITH STEVE MALLEK (ROOFING
 CONTRACTOR), THE ROOFING SUB-PERMIT WAS ISSUED TO ALLOW
 FOR CONCRETE ROOF TILE DRY-IN INSPECTION . FOLLOWING
 COMMENTS NEED TO BE ADDRESSED BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS. THIS CHECKLIST WAS E-MAILED TO
 GENERAL CONTRACTOR AND ROOFING CONTRACTOR. JG.
  
  
 RESIDENTIAL (R3) REVISION ADDRESSING BUILDING PROVISO,
 SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) FLAT ROOF. AND, IDENTIFY APPROVED ASSEMBLY TO BE
 INSTALLED. NOTE: SIGNED & SEALED RAS 117 CALCULATIONS
 WILL BE REQUIRED IF THE ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES OF SEC. R301.
  
 RESPONSE: NOT ADDRESSED YET. NEED TO PROVIDE. THIS IS
 FOR THE FLAT DECK ABOVE THE NEW TWO STORY STAIRWAY
 TOWER. SEE PLANS.
  
 ORIGINAL COMMENT:
 B) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED
 TILE AS SPECIFIED ON PLANS. AND, IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. NOTE: SIGNED & SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED IF THE ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES OF SEC. R301.
 SEAL-O-FLEX NOA 15-0406.03 SUBMITTED IS FOR INSULATED
 ASSEMBLIES. ARCHITECTURAL PLANS DON'T SPECIFY INSULATED
 ASSEMBLIES.
  
 RESPONSE: FLORIDA PRODUCT APPROVAL FL2144-R6 SUBMITTED
 CAN NOT BE USED BECAUSE OF THE FOLLOWING: (1)IT'S NOT
 DESIGNED TO RECEIVED TILE AS SHOWN ON ARCHITECTURAL
 PLANS. SEE PRODUCT DESCRIPTION TABLE ON PAGE 1 OF 3 OF
 FL2144-R6 SUBMITTED FOR THE ROOF COATINGS ALLOWED FOR
 THIS TYPE OF LIQUID APPLIED MEMBRANE. NONE OF THEM
 DESCRIBE TILE AS THE ROOF COATING. (2) SELECTED
 ASSEMBLIES W-A-1 AND W-A-2 ON PAGE 13 OF 14 OF
 FL2144-R6 ARE FOR FULLY ADHERED MEMBRANES WITH MAXIMUM
 DESIGN PRESSURES OF -60PSF AND -85PSF RESPECTIVELY.
 LIMITATION #9 ON PAGE 3 OF 3 DOESN'T ALLOW DESIGN
 PRESSURES AUGMENTATION. ACCORDING TO SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014) THE DESIGN
 PRESSURES FOR THE PERIMETER AND CORNER AREAS ARE
 HIGHER. THEREFORE THEY CAN NOT BE USED. NEED TO PROVIDE
 PRODUCT APPROVAL THAT IS DESIGNED TO RECEIVE TILE AS
 SPECIFIED ON PLANS. AND, NEED RAS 117 CALCULATIONS IF
 THE SELECTED ASSEMBLY ALLOWS IT.
  
 ORIGINAL COMMENT:
 C) INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT
 THE STAIR HALL. PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL COVER PAGES AND THE CORRESPONDING DRAWINGS.
 RESPONSE: NOT ADDRESSED.
  
 2- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS.
  
  
 THE FOLLOWING ARE COMMENTS ARE FOR THE SUBMITTED
 INFORMATION:
 ORIGINAL COMMENT:
 (1) CONCRETE ROOF TILE NOA 12-0222.03 SUBMITTED NOW WAS
 ALREADY SUBMITTED AND APPROVED WITH THE ORIGINAL PERMIT
 SET. CLARIFY WHY SUBMITTING PRODUCT APPROVAL AGAIN.
 SEC. 107.2.1 CITY AMENDMENTS.
 RESPONSE: OK. APPROVED PRODUCT APPROVAL SHOULD BE ON
 SITE ALONG WITH THE REST OF THE APPROVED PRODUCT
 APPROVALS.
  
  
 ORIGINAL COMMENT:
 (2) ARCHITECTURAL PLANS SPECIFY "CEMENT TILE ON 90#
 FELT HOT MOPPED ON 30# FELT TIN TAGGED AT 6" EDGES AND
 12" FIELD O.C." THIS SUBMITTAL INCLUDES BORAL TILESEAL
 SELF-ADHERING UNDERLAYMENT AND TILE BOND ROOF TILE
 ADHESIVE. IF THERE IS A CHANGE IN THE ROOF TILE
 FASTENING AND UNDERLAYMENT METHOD, THEN REVISE
 ARCHITECTURAL PLANS ACCORDINGLY. SEC. 107.2.1.2 CITY
 AMENDMENTS.
 RESPONSE: THIS ITEM STILL NEEDS TO BE ADDRESSED.
  
 (3) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 NOTE: THERE WAS A ROOFING APPLICATION INSERTED IN THE
 PACKAGE SUBMITTED. ROOFING SUB-PERMIT WILL BE PROCESSED
 WHEN PENDING ROOFING ITEMS ARE ADDRESSED.
 RESPONSE: PER MEETING WITH STEVE MALLEK (CJM ROOFING),
 THE ROOFING SUB-PERMIT WAS ISSUED TO ALLOW FOR CONCRETE
 TILE DRY-IN INSPECTIONS. ALL THE PENDING ITEMS NEED TO
 BE ADDRESSED BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. PLEASE USE THIS REVISION NUMBER
 (16060273) FOR SUBMITTAL TO KEEP TRACK OF ALL THE
 PENDING ITEMS.
  
 ***NOTE:
 NUMBER OF PAGES WILL BE COORDINATED WHEN ADDRESSING
 COMMENTS. NEW PRODUCT APPROVALS (NOT PART OF THE
 ORIGINAL PACKAGE) WILL BE ADDED TO THE REVISION FEES.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-10 Cont ID  
Sent By jgomez Date 2016-06-10 Time 12:49 Rev Time 0.00
Received By jgomez Date 2016-06-10 Time 12:48 Sent To  
Notes
2016-06-10 12:50:40RESIDENTIAL (R3) REVISION ADDRESSING BUILDING PROVISO,
 BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) FLAT ROOF. AND, IDENTIFY APPROVED ASSEMBLY TO BE
 INSTALLED. NOTE: SIGNED & SEALED RAS 117 CALCULATIONS
 WILL BE REQUIRED IF THE ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES OF SEC. R301.
 RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED
 TILE AS SPECIFIED ON PLANS. AND, IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. NOTE: SIGNED & SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED IF THE ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES OF SEC. R301.
 SEAL-O-FLEX NOA 15-0406.03 SUBMITTED IS FOR INSULATED
 ASSEMBLIES. ARCHITECTURAL PLANS DON'T SPECIFY INSULATED
 ASSEMBLIES.
 RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 C) INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT
 THE STAIR HALL. PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL COVER PAGES AND THE CORRESPONDING DRAWINGS.
 RESPONSE: NOT ADDRESSED.
  
 2- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS.
  
  
 THE FOLLOWING ARE COMMENTS ARE FOR THE SUBMITTED
 INFORMATION:
 (1) CONCRETE ROOF TILE NOA 12-0222.03 SUBMITTED NOW WAS
 ALREADY SUBMITTED AND APPROVED WITH THE ORIGINAL PERMIT
 SET. CLARIFY WHY SUBMITTING PRODUCT APPROVAL AGAIN.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 (2) ARCHITECTURAL PLANS SPECIFY "CEMENT TILE ON 90#
 FELT HOT MOPPED ON 30# FELT TIN TAGGED AT 6" EDGES AND
 12" FIELD O.C." THIS SUBMITTAL INCLUDES BORAL TILESEAL
 SELF-ADHERING UNDERLAYMENT AND TILE BOND ROOF TILE
 ADHESIVE. IF THERE IS A CHANGE IN THE ROOF TILE
 FASTENING AND UNDERLAYMENT METHOD, THEN REVISE
 ARCHITECTURAL PLANS ACCORDINGLY. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 (3) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 NOTE: THERE WAS A ROOFING APPLICATION INSERTED IN THE
 PACKAGE SUBMITTED. ROOFING SUB-PERMIT WILL BE PROCESSED
 WHEN PENDING ROOFING ITEMS ARE ADDRESSED.
  
 ***NOTE:
 NUMBER OF PAGES WILL BE COORDINATED WHEN ADDRESSING
 COMMENTS. NEW PRODUCT APPROVALS (NOT PART OF THE
 ORIGINAL PACKAGE) WILL BE ADDED TO THE REVISION FEES.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-18 Cont ID  
Sent By mvaldes Date 2016-07-18 Time 11:59 Rev Time 0.00
Received By mvaldes Date 2016-07-18 Time 11:09 Sent To B
Notes
2016-07-18 12:00:53REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO'S
  
 - E3405.2 WORKING CLEARANCES FOR ENERGIZED EQUIPMENT
 AND PANELBOARDS.
 EXCEPT AS OTHERWISE SPECIFIED IN CHAPTERS 34 THROUGH
 43, THE DIMENSION OF THE WORKING SPACE IN THE DIRECTION
 OF ACCESS TO PANELBOARDS AND LIVE PARTS LIKELY TO
 REQUIRE EXAMINATION, ADJUSTMENT, SERVICING OR
 MAINTENANCE WHILE ENERGIZED SHALL BE NOT LESS THAN 36
 INCHES (914 MM) IN DEPTH. DISTANCES SHALL BE MEASURED
 FROM THE ENERGIZED PARTS WHERE SUCH PARTS ARE EXPOSED
 OR FROM THE ENCLOSURE FRONT OR OPENING WHERE SUCH PARTS
 ARE ENCLOSED. IN ADDITION TO THE 36-INCH DIMENSION (914
 MM), THE WORK SPACE SHALL NOT BE LESS THAN 30 INCHES
 (762 MM) WIDE IN FRONT OF THE ELECTRICAL EQUIPMENT AND
 NOT LESS THAN THE WIDTH OF SUCH EQUIPMENT. THE WORK
 SPACE SHALL BE CLEAR AND SHALL EXTEND FROM THE FLOOR OR
 PLATFORM TO A HEIGHT OF 6.5 FEET (1981 MM) OR THE
 HEIGHT OF THE EQUIPMENT, WHICHEVER IS GREATER. IN ALL
 CASES, THE WORK SPACE SHALL ALLOW AT LEAST A 90-DEGREE
 (1.57 RAD) OPENING OF EQUIPMENT DOORS OR HINGED PANELS.
 EQUIPMENT ASSOCIATED WITH THE ELECTRICAL INSTALLATION
 LOCATED ABOVE OR BELOW THE ELECTRICAL EQUIPMENT SHALL
 BE PERMITTED TO EXTEND NOT MORE THAN 6 INCHES (152 MM)
 BEYOND THE FRONT OF THE ELECTRICAL EQUIPMENT.
  
 - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-08-19 Cont ID  
Sent By jgomez Date 2016-08-19 Time 15:52 Rev Time 0.00
Received By jgomez Date 2016-08-18 Time 14:46 Sent To  
Notes
2016-08-19 14:46:20SENT TO JULIO'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-25 Cont ID  
Sent By jgomez Date 2016-07-25 Time 17:02 Rev Time 0.00
Received By jgomez Date 2016-07-15 Time 12:24 Sent To  
Notes
2016-07-15 12:24:46RESUB OF REVISION ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-14 Cont ID  
Sent By jgomez Date 2016-06-14 Time 14:18 Rev Time 0.00
Received By jgomez Date 2016-06-14 Time 14:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-10 Cont ID  
Sent By jgomez Date 2016-06-10 Time 12:48 Rev Time 0.00
Received By jgomez Date 2016-06-06 Time 15:51 Sent To  
Notes
2016-06-07 15:52:12JGOMEZ'S DESK