2016-07-07 17:07:21RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION(2014)
  
 1- FLAT ROOF NOA 13-1217.01 SUBMITTED:
 A) ENGINEER'S CALCULATIONS AND APPROVED ASSEMBLY
 SUBMITTED DON'T MATCH. ENGINEER SPECIFIES APPROVED
 SYSTEM E(1) ON PAGE 26 OF 33, WHILE APPROVED ASSEMBLY
 SUBMITTED IS FOR SYSTEM E(2) ON PAGE 27 OF 33. REVISE
 AS REQUIRED TO MATCH. IT'S NOT CLEAR WHICH ASSEMBLY IS
 GOING TO BE INSTALLED. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) PROVIDE 2 SIGNED AND SEALED COPIES OF THE ENGINEER'S
 CALCULATIONS. ONLY ONE WAS SUBMITTED. SEC. 107.1 CITY
 AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-10 Cont ID  
Sent By jgomez Date 2016-06-10 Time 10:42 Rev Time 0.00
Received By jgomez Date 2016-06-10 Time 09:01 Sent To  
Notes
2016-06-10 11:09:42RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION(2014)
  
 1- FLAT ROOF:
 A) FLORIDA PRODUCT APPROVAL FL1654-R19 SUBMITTED IS NOT
 APPROVED YET. THE APPLICATION STATUS SAYS "PENDING FBC
 APPROVAL". NEED TO PROVIDE FLORIDA PRODUCT APPROVAL
 THAT IS APPROVED. FAC61G20-3.002(33).
  
 B) PROVIDE COMPLETE EVALUATION REPORT. SUBMIT THE FIRST
 9 PAGES OF THE EVALUATION REPORT AND PAGE SHOWING THE
 SELECTED ASSEMBLY. FAC 61G20-3.002(33).
  
  
 C) SELECTED ASSEMBLY W-138 SUBMITTED SHOWS MAXIMUM
 DESIGN PRESSURES OF -90 PSF.. THIS BUILDING IS LOCATED
 IN EXPOSURE "C". THE CORNER DESIGN PRESSURES ARE HIGHER
 THAN -90 PSF. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014). BONDED ASSEMBLIES DON'T ALLOW RATIONAL
 ANALYSIS. SEE NOTE: #9 ON PAGE 2 OF 45 OF EVALUATION
 REPORT.
  
 D) BONDED ASSEMBLIES REQUIRE UPLIFT TESTING TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. SEE LIMITATION 5.11 ON PAGE 5 OF 5 OF
 EVALUATION REPORT.
  
 2- METAL ROOFING:
 A) PROVIDE CURRENT FLORIDA PRODUCT APPROVAL. FLORIDA
 PRODUCT APPROVAL FL12744-R2 SUBMITTED WAS REVISED BY
 FL12744-R3. FAC 61G20-3.002(33).
  
 B) PROVIDE COMPLETE INSTALLATION INSTRUCTIONS AND
 EVALUATION REPORT FOR THE SPECIFIC METAL ROOF SELECTED
 FORM FLORIDA PRODUCT APPROVAL FL-12744-R3. FAC
 61G20-3.002(33).
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-11 Cont ID  
Sent By jgomez Date 2016-07-11 Time 15:43 Rev Time 0.00
Received By jgomez Date 2016-07-08 Time 10:01 Sent To  
Notes
2016-07-08 10:01:42RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-07 Cont ID  
Sent By jgomez Date 2016-07-07 Time 16:19 Rev Time 0.00
Received By jgomez Date 2016-07-07 Time 11:06 Sent To  
Notes
2016-07-07 11:06:24RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-10 Cont ID  
Sent By jgomez Date 2016-06-10 Time 09:10 Rev Time 0.00
Received By jgomez Date 2016-06-07 Time 15:49 Sent To  
Notes
2016-06-07 15:50:03CTHROOP'S DESK


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved