Plan Review Details - Permit 16060267
Plan Review Stops For Permit 16060267
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-08 Cont ID  
Sent By cthroop Date 2016-09-08 Time 10:15 Rev Time 0.00
Received By cthroop Date 2016-09-07 Time 14:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-21 Cont ID  
Sent By cthroop Date 2016-07-21 Time 09:48 Rev Time 0.00
Received By cthroop Date 2016-07-21 Time 08:19 Sent To  
Notes
2016-07-21 10:08:35BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/21/16
  
 1. PROVIDE INSTALLATION INSTRUCTIONS FOR PROPOSED DOORS
 ON NOTICE OF PRODUCT CERTIFICATION.
 2. PRODUCT APPROVAL REVIEW FORM ON PG A1 LIST'S THE
 CITY OF LAKE WORTH AS AHJ. CHANGE TO CITY OF WEST PALM
 BEACH.
 3. OPENING J (DR) LIST A PRODUCT APPROVAL FOR A WINDOW.
 4. ELEVATION KEY NOTES ON PG A1 MISSING ITEM #12.
 5. PROVIDE PRODUCT APPROVAL FOR DOOR (E), EXT. DOOR
 SUBJECT TO WIND LOADS.
 6. PROVIDE PRODUCT APPROVAL FOR WINDOW (B).
 7. PROVIDE PRODUCT APPROVAL FOR DOOR (Q). WINDOW AND
 DOOR SCHEDULE LIST A PRODUCT APPROVAL FOR A WINDOW.
 8. PROVIDE PRODUCT APPROVAL FOR WINDOW (L). WINDOW AND
 DOOR SCHEDULE LIST A PRODUCT APPROVAL FOR A SLIDING
 GLASS DOOR.
 9. PROVIDE BUILDING LOCATION W/SETBACKS ON SITE PLAN.
 10.ROOFING PERMIT IS REQUIRED.
 11. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 12. FOOTING SCHEDULE ON PG S-1 INCOMPLETE. PROVIDE
 FOOTING SCHEDULE FOR FOOTINGS TE-8 AND F3.0 SHOWN ON
 PLANS.
 13. IDENTIFY LOCATION OF RAFTER CONNECTORS AND TIE
 BEAMS FROM RAFTER CONNECTOR SCHEDULE ON PLANS.
 14. ROOF SHEATHING DETAIL ON PG S-1 REFERENCES A SLOPED
 GABLE ROOF. EXISTING & PROPOSED ROOF IS A FLAT ROOF.
 15. ARE ROOF DESIGN LOADS AND UPLIFT PRESSURES BASED ON
 EXISTING AND PROPOSED FLAT ROOF?
 16. IS THE ROOF SHEATHING ATTACHMENT SCHEDULE BASED ON
 THE EXISTING AND PROPOSED FLAT ROOF?
 17. IDENTIFY LOCATION OF ROOF FRAMING KEYS T1, T3 & T4
 ON PLANS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
 WINDOW AND DOOR SUBMITTALS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-26 Cont ID  
Sent By mvaldes Date 2016-09-26 Time 16:16 Rev Time 0.00
Received By mvaldes Date 2016-09-26 Time 15:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-08-29 Cont ID  
Sent By mvaldes Date 2016-08-29 Time 13:45 Rev Time 0.00
Received By mvaldes Date 2016-08-29 Time 12:32 Sent To  
Notes
2016-08-29 13:56:27REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PLEASE REVISE LOAD CALCS TO INCLUDE APPLIANCE LOADS
 AND CORRECT AC HEAT LOADS MATCHING THE PANEL SCHEDULE.
 NEC 220.82 OPTIONAL ( 2ND REQUEST )
  
 2] VERIFY RECEPTACLE OUTLET SPACING IN THE
 MASTER-BEDROOM. NEC 210.52(A) WALL SPACE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-16 Cont ID  
Sent By mvaldes Date 2016-06-16 Time 16:23 Rev Time 0.00
Received By mvaldes Date 2016-06-16 Time 13:50 Sent To  
Notes
2016-06-16 16:17:31JOB PERMIT NUMBER: 16060267
 JOB ADDRESS: 710 DUBBINS STREET
 WEST PALM BEACH FLORIDA
 DATE: JUNE 16 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - PANEL SCHEDULE REFLECTS THE FOLLOWING INCORRECT
 INFORMATION. THE A/C COMPRESSOR SHOWS 30 AMP BKR AND
 SPEC SHEET ON AC-1 NAMEPLATE INDICATES ?MAX FUSE SIZE
 60 AMP?. ALL BATHROOM AND SMALL APPLIANCE CIRCUITS MUST
 HAVE A MINIMUM AMPACITY OF 20 AMPS PER NEC
 210.11(C)(1)(3). WATER HEATER IS MISSING BKR SIZE.
 GENERAL RECEPTACLE LOAD ISN?T APPLICABLE FOR LOAD CLACS
 PLEASE SEE NEC 220.82(A)(B)(C) & NEC 220.83 OPTIONAL
 AND EXISTING CALCULATIONS. FBC 107.2.1 INSUFFICIENT
 DOCUMENTS.
 - UNDER THE IMPRESSION THE EXISTING CONDUITS EMT 1 ???
 SINCE NO EQUIPMENT GROUNDING CONDUCTOR IS SHOWN
 ACCORDING TO ANNEX C CONDUIT AND CONDUCTOR FILL TABLE
 2/0 AWG DOESN?T FIT IN THAT RACEWAY ? PLEASE CLARIFY ?
 - LABEL ?GFCI? TO ALL KITCHEN AND PENINSULAR
 COUNTERTOPS OUTLETS NEC 210.8(A). RECEPTACLES LOCATED
 OUTSIDE LABEL ?WR/WP? PER NEC 406.(B).
 - MASTER BATH MISSING RECEPTACLE OUTLET INSTALLED
 WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH BASIN. NEC
 210.52(D)
 - FBC-R 315.1 CARBON MONOXIDE PROTECTION. EVERY
 SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048
 MM) OF EACH ROOM USED FOR SLEEPING PURPOSES.
 - NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE
 DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910
 MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS.
 RELOCATE THE UNITS ACCORDINGLY. ( MASTER BEDROOM )
 - LOW VOLTAGE SHALL BE ON A SEPERATE PERMT. ( IF
 NECCESSARY )
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-11-08 Cont ID  
Sent By cthroop Date 2016-11-08 Time 11:47 Rev Time 0.00
Received By cthroop Date 2016-11-03 Time 09:25 Sent To  
Notes
2016-11-04 09:25:59RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-12 Cont ID  
Sent By cthroop Date 2016-10-12 Time 09:22 Rev Time 0.00
Received By cthroop Date 2016-09-23 Time 15:40 Sent To  
Notes
2016-10-11 18:03:22PLANS GIVEN TO CHRIS T. - 6:06 PM - 10/11/2016 - JORGE
 V. ----
2016-10-11 13:51:4010/11/16 - PLANS GIVEN TO JVALIDO
2016-09-23 15:40:36R19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-14 Cont ID  
Sent By lmarchan Date 2016-09-14 Time 09:16 Rev Time 0.00
Received By lmarchan Date 2016-08-18 Time 11:36 Sent To  
Notes
2016-08-19 11:36:55R09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-22 Cont ID  
Sent By cpuell Date 2016-07-22 Time 10:47 Rev Time 0.00
Received By cpuell Date 2016-06-07 Time 16:41 Sent To  
Notes
2016-06-07 16:41:41R02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2016-11-16 Cont ID  
Sent By cthroop Date 2016-11-16 Time 14:19 Rev Time 0.00
Received By cthroop Date 2016-11-16 Time 14:19 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-10-12 Cont ID  
Sent By cthroop Date 2016-10-12 Time 09:23 Rev Time 0.00
Received By cthroop Date 2016-10-12 Time 09:23 Sent To  
Notes
2016-10-12 09:23:41BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-09-08 Cont ID  
Sent By cthroop Date 2016-09-08 Time 10:14 Rev Time 0.00
Received By cthroop Date 2016-09-08 Time 10:14 Sent To  
Notes
2016-09-08 10:15:10BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-07-21 Cont ID  
Sent By cthroop Date 2016-07-21 Time 09:47 Rev Time 0.00
Received By cthroop Date 2016-07-21 Time 09:47 Sent To  
Notes
2016-07-21 09:48:32BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/21/16
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-11-07 Cont ID  
Sent By jvalido Date 2016-11-07 Time 15:33 Rev Time 0.00
Received By jvalido Date 2016-11-07 Time 14:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-10-11 Cont ID  
Sent By jvalido Date 2016-10-11 Time 17:58 Rev Time 0.00
Received By jvalido Date 2016-10-11 Time 16:40 Sent To  
Notes
2016-10-11 17:47:54CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) RETURN AIR TRANSFER FROM BEDROOM #3 IS IN THE
 KITCHEN CABINET.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (2) FORM R405-2014 MUST BE SIGNED BY "OWNER/AGENT"
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-09-13 Cont ID  
Sent By jvalido Date 2016-09-13 Time 17:41 Rev Time 0.00
Received By jvalido Date 2016-09-13 Time 16:53 Sent To  
Notes
2016-09-13 16:57:50CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) RETURN AIR IS REQUIRED FROM ALL BEDROOMS.
 (2) MASTER BEDROOM REQUIRES EXHAUST FAN.
 (3) KITCHEN EXHAUST (RECICULATING OR VENTED TO
 EXTERIOR) ??????
  
  
 FLORIDA ENERGY CODE FBC 2014
  
 (4) ALL FORMS 405 - 2014 MUST BE SIGNED BY OWNER/AGENT
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-21 Cont ID  
Sent By jvalido Date 2016-07-21 Time 17:12 Rev Time 0.00
Received By jvalido Date 2016-07-21 Time 16:39 Sent To  
Notes
2016-07-21 17:08:31CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) TOTAL CFM FOR AHU #1 EXCEEDS EQUIPMENT SCHEDULE AND
 DESIGNED UNIT AMOUNT.
 (2) BATH EXHAUST IN MASTER BEDROOM BATHROOM ??.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (3) HEAT LOADS CALCULATIONS AND ENERGY CALCULATIONS DO
 NOT MATCH SYSTEM DESIGN ON PLANS. REVIEW AND MAKE
 CORRECTIONS.
 (4) FORM R405-2014 MUST BE SIGNED BY PREPARER AND
 OWNER/AGENT.
  
 JORGE VALIDO
 CITY OF WEST PALM BEACH
 MECHANICAL INSPECTOR/PLANS EXAMINER
 561-805-673
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-09-13 Cont ID  
Sent By gjohnson Date 2016-09-13 Time 15:43 Rev Time 0.00
Received By gjohnson Date 2016-09-13 Time 15:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-21 Cont ID  
Sent By gjohnson Date 2016-06-21 Time 18:05 Rev Time 0.00
Received By gjohnson Date 2016-06-21 Time 17:19 Sent To  
Notes
2016-06-21 18:13:471ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
  
 1. SHT. A-1 SCOPE OF WORK INDICATES REPLACEMENT OF
 PLUMBING SYSTEMS PLEASE CLARIFY WHICH PART OR ALL OF TH
 SANITARY AND WATER SYSTEMS ARE BEING REPLACED. PER WPB
 AMEND. TO FBC SEC. 107.2.1
  
 2. PROVIDE PLUMBING RISER DIAGRAM FOR ALL NEW PIPING
 INCLUDING NEW PIPING FOR EXISTING BATHROOMS OR KITCHEN
 ,LAUNDRY. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 3.SHOW LOCATION OF WATER HEATER. IS IT BEING REPLACED
 OR REMAIN. PER WPB AMEND. TO FBC SEC. 107.2.1
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2016-11-08 Cont ID  
Sent By cthroop Date 2016-11-08 Time 11:47 Rev Time 0.00
Received By cthroop Date 2016-11-08 Time 11:47 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2016-10-12 Cont ID  
Sent By cthroop Date 2016-10-12 Time 09:23 Rev Time 0.00
Received By cthroop Date 2016-10-12 Time 09:23 Sent To  
Notes
2016-10-12 09:25:16BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW ROOF SYSTEM
 COMPONENTS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-09-08 Cont ID  
Sent By cthroop Date 2016-09-08 Time 10:15 Rev Time 0.00
Received By cthroop Date 2016-09-08 Time 10:15 Sent To  
Notes
2016-09-08 10:17:14BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 ACTION: DENIED
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW ROOF SYSTEM
 COMPONENETS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-07-21 Cont ID  
Sent By cthroop Date 2016-07-21 Time 10:08 Rev Time 0.00
Received By cthroop Date 2016-07-21 Time 10:08 Sent To  
Notes
2016-07-21 10:13:19BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/21/16
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW FLAT ROOF SYSTEM
 COMPONENTS.
 2. PROVIDE ROOF SHEATHING DETAIL FOR EXISTING AND
 PROPOSED FLAT ROOF.
 3. ARE ROOF DESIGN LOADS AND ROOF UPLIFT PRESSURES
 BASED ON EXISTING AND PROPOSED FLAT ROOF?
 4. IS THE ROOF SHEATHING ATTACHMENT SCHEDULE BASED ON
 THE EXISTING AND PROPOSED FLAT ROOF?
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  
  
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2016-11-02 Cont ID  
Sent By njwira Date 2016-11-02 Time 16:01 Rev Time 0.00
Received By njwira Date 2016-11-02 Time 16:01 Sent To R
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2016-10-03 Cont ID  
Sent By njwira Date 2016-10-03 Time 16:58 Rev Time 0.00
Received By njwira Date 2016-09-30 Time 15:13 Sent To  
Notes
2016-10-03 16:58:4910/3/16- FAILED
  
 ADDITION HAS A FRONT SETBACK OF 24.75FT. WHICH DOESN'T
 MEET THE 25FT. FRONT SETBACK REQUIREMENT.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-08-23 Cont ID  
Sent By njwira Date 2016-08-23 Time 11:41 Rev Time 0.00
Received By njwira Date 2016-08-22 Time 13:57 Sent To  
Notes
2016-09-02 11:52:01PASS FIRST PAGE
2016-08-23 11:41:556/10/16- FAILED
 1. 24.75FT. DOES NOT MEET MINIMUM FRONT SETBACK
 REQUIREMENTS. EXISITING IS A NON-CONFORMING USE AT
 22FT. CANNOT BUILD FURTHER INTO SETBACK.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-10 Cont ID  
Sent By nwier Date 2016-06-10 Time 16:43 Rev Time 0.00
Received By njwira Date 2016-06-10 Time 16:43 Sent To E
Notes
2016-06-10 16:46:106/10/16- FAILED
 1. 24.75FT. DOES NOT MEET MINIMUM FRONT SETBACK
 REQUIREMENTS. EXISITING IS A NON-CONFORMING USE AT
 22FT. CANNOT BUILD FURTHER INTO SETBACK.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  