Plan Review Details - Permit 16060194
Plan Review Stops For Permit 16060194
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-02 Cont ID  
Sent By skennedy Date 2016-08-02 Time 11:36 Rev Time 0.00
Received By skennedy Date 2016-08-02 Time 11:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-27 Cont ID  
Sent By cthroop Date 2016-07-27 Time 08:59 Rev Time 0.00
Received By cthroop Date 2016-07-27 Time 08:59 Sent To  
Notes
2016-07-27 09:08:20BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/27/16
  
 1. ENERGY SUBMITTAL REQUIRED.
 2. IMPACT FEES REQUIRED.
 3. PROVIDE 2ND SET OF PLANS. TWO SETS OF PLANS IN
 SUBMITTAL HAVE BEEN MARKED VOID.
 4. COLUMN AT FRONT ENTRANCE TO BE REMOVED. CERTIFY THE
 TIE BEAM ABOVE IS INDEPENDANT OF THE COLUMN TO BE
 REMOVED AND HAS SUFFICIENT BEARING ON ADJACENT COLUMNS.
 5. CLOUDED NOTE AT FRONT DOOR ON PLAN PG. 2 REFERENCES
 A TABLE 4. TABLE 4 MISSING. PLEASE CLARIFY.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
  
  
  
  
  
2016-06-06 11:48:54NOTE, THIS IS A RENOVATION, ENERGY CODE APPLIES.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-27 Cont ID  
Sent By vperez Date 2016-07-27 Time 07:08 Rev Time 0.00
Received By vperez Date 2016-07-27 Time 07:08 Sent To  
Notes
2016-07-27 07:18:13NEED REVISED SHEET ELECTRICAL SIGNED AND NOTARIZED BY
 EOR BEFORE PERMIT PICKUP

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-06 Cont ID  
Sent By vperez Date 2016-07-05 Time 10:04 Rev Time 0.00
Received By vperez Date 2016-07-05 Time 10:04 Sent To  
Notes
2016-07-06 09:07:07INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADDRESS SMOKE DETECTORS IN ALL BEDROOMS AND
 EXTERIOR OF BEDROOMS, SHOW ON PLANS. FBC RES 314
 2. CALCULATIONS NOT ACCURATE PER SCOPE OF WORK SHOWN.
 ADD NEW THANKLESS HEATERS TO LOADS AS SHOWN ON PLANS.
 PROVIDE SPECS FOR NEW HEATERS. FBC 107.3.5
 3. ADDRESS RISER DIAGRAM, SHOW AN INTERSYSTEM BONDING
 CONNECTION, METER CAN AMP RATING, SIZE OF GUTTER BEING
 INSTALLED, AND SHOW EQUIPMENT GROUNDING CONDUCTOR
 FEEDING MLO PANELS. FBC 107.3.5
 4. FURTHER COMMENTS MAY FOLLOW. PLEASE FEEL FREE TO
 CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING THIS
 PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-07-27 Cont ID  
Sent By gjohnson Date 2016-07-27 Time 14:01 Rev Time 0.00
Received By gjohnson Date 2016-07-27 Time 14:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-06-21 Cont ID  
Sent By gjohnson Date 2016-06-21 Time 16:34 Rev Time 0.00
Received By gjohnson Date 2016-06-21 Time 16:34 Sent To  
Notes
2016-06-21 16:37:12GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
  
  
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-28 Cont ID  
Sent By cpuell Date 2016-07-28 Time 08:01 Rev Time 0.00
Received By cpuell Date 2016-06-03 Time 10:41 Sent To  
Notes
2016-06-06 10:41:35R17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-08-02 Cont ID  
Sent By skennedy Date 2016-08-02 Time 11:37 Rev Time 0.00
Received By skennedy Date 2016-08-02 Time 11:37 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-07-27 Cont ID  
Sent By cthroop Date 2016-07-27 Time 09:51 Rev Time 0.00
Received By cthroop Date 2016-07-27 Time 09:51 Sent To  
Notes
2016-07-27 09:52:33BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/27/16
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-02 Cont ID  
Sent By skennedy Date 2016-08-02 Time 11:37 Rev Time 0.00
Received By skennedy Date 2016-08-02 Time 11:37 Sent To  
Notes
2016-08-02 11:40:581ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL & EXISTING
 BUILDING
  
 APPROVED WITH EXCEPTION. THE EQUIPMENT SCHEDULE
 PROVIDED BY THE CONTRACTOR IS MESSY. FOLLOW THE
 SCHEDULE OF EQUIPMENT LISTED ON THE ENERGY SUBMITTAL.
 THE WORK IS SUBJECT TO INSPECTION AND MAY REQUIRE A
 REVISION.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-27 Cont ID  
Sent By jvalido Date 2016-07-27 Time 16:19 Rev Time 0.00
Received By jvalido Date 2016-07-27 Time 15:02 Sent To  
Notes
2016-07-27 16:10:07CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE (2) SETS OF PLANS.
 (2) PROVIDE SUPPLY AIR TO NEW FLORIDA ROOM ???.
 (3) PROVIDE EQUIPMENT SCHEDULE INCLUDE (BRAND, MODEL#
 SENSIBLE/LATEND BTU, SEER, TOTAL CFM OF AHU)
 (4) PROVIDE SPECIFICATIONS OF EXHAUST FOR NEW BATHROOM.
  
  
 FLORIDA ENERGY CODE FBC 2014
  
 (5) PROVIDE (2) SETS OF HEAT LOAD CALCULATIONS ( AS PER
 MANUAL D - J).
 (6) PROVIDE (2) SETS OF ENERGY CALCULATIONS FORM
 R405-2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
 THE RESPONSE FOR 16060294 SHOULD BE INCORPORATED INTO
 16060194 SO THE PROJECT CAN BE EVALUATED AS A
 RENOVATION PER THE ENERGY CODE DEFINITION. NOTE THAT
 THE APPLICATION FOR 16060294 SHOULD BE CHANGED TO A
 SUB-PERMIT APPLICATION.
  
2016-07-26 16:40:37SEE SEPARATE MECH APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-07-27 Cont ID  
Sent By gjohnson Date 2016-07-27 Time 13:55 Rev Time 0.00
Received By gjohnson Date 2016-07-27 Time 13:55 Sent To  
Notes
2016-08-02 12:23:22MADE A COPY.
2016-07-27 13:58:45REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
  
  
 1. PROVIDE TWO SETS OF PLANS THAT MATCH THE PLANS IN
 THE SUBMITTAL PACKAGE HAVE DIFFERENT SHEETS IN THEM AND
 ONE IS MARKED VOID. PLUMBING WOULD BE APPROVED IF THERE
 WAS TWO MATCHING SETS OF PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-21 Cont ID  
Sent By gjohnson Date 2016-06-21 Time 16:37 Rev Time 0.00
Received By gjohnson Date 2016-06-21 Time 16:37 Sent To  
Notes
2016-06-21 16:44:271ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE PLUMBING RISER DIAGRAM OF NEW
 BATHROOM. PER WPB AMEND TO FBC SEC. 107.3.5.3(11)
  
 2.SHOW LOCATION OF NEW WATER HEATERS. PER WPB AMEND TO
 FBC SEC. 107.2.1

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-26 Cont ID  
Sent By awooten Date 2016-07-26 Time 09:44 Rev Time 0.00
Received By awooten Date 2016-07-26 Time 09:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-06-16 Cont ID  
Sent By awooten Date 2016-06-16 Time 15:57 Rev Time 0.00
Received By awooten Date 2016-06-16 Time 15:56 Sent To  
Notes
***NONE***