| Plan Review Stops For Permit 16060187 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-08-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-08-29 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-08-29 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2016-08-29 15:58:18 | APPROVED WITH EXCEPTION | | | 1) THE PRODUCT APPROVAL FOR THE METAL ROOFING IS FOR | | | NON-INSULATED DECKS AND THE PLANS SHOW 2" RIGID | | | INSULATION ON SHEET S-2. SUBMIT NEW PRODUCT APPROVALS | | | OR REVISED PLANS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-07-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-07-28 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-07-28 |
Time |
07:12 |
Sent To |
|
|
| Notes |
| 2016-07-28 14:58:53 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF | | | THE NEW METAL ROOFING, ALUMINUM SIDING AND ALUMINUM | | | PREFORATED V-GROOVE SOFFIT. | | | | | | 2) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED | | | IN THE GAF PRODUCT APPROVAL (NOA NO. 14-1030.02) FOR AN | | | INSULATED ROOF AS SPECIFIED ON THE PLANS WILL BE USED. | | | SUBMIT TWO SETS OF RAS 117 CALCULATIONS FOR ENHANCED | | | FASTENING AS REQUIRED BY LIMITATION NUMBER 7 OF THE | | | NOA. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-06-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-06-20 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-06-17 |
Time |
17:32 |
Sent To |
|
|
| Notes |
| 2016-06-20 14:45:23 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS ARE REQUIRED TO HAVE THE ORIGINAL | | | HANDWRITTEN SIGNATURE OF THE ENGINEER AND HIS SEAL | | | (COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE) PER FAC | | | 61G15-23.002. | | | | | | 2) THE SEAL IS REQUIRED TO BE A MINIMUM OF 1-7/8 INCHES | | | IN DIAMETER. FAC 61G15-23.001 | | | | | | 3) FOR CITY OF WEST PALM BEACH RECORD KEEPING PURPOSES | | | THE PLANS ARE REQUIRED TO BE A MINIMUM OF 1/8 INCH | | | SCALE. FBC107.2.1.3 AFTER THESE PLANS WERE REDUCED IN | | | SIZE THEY ARE NO LONGER 1/8 INCH SCALE. | | | | | | 4) SPECIFY THE WIND DESIGN DATA INCLUDING WIND SPEED | | | AND EXPOSURE CATEGORY ON THE PLANS. FBC-R301.2.1 | | | | | | 5)THE NOTES 1 AND 2 AT THE BOTTOM OF SHEET S-3 ARE NOT | | | LEGIBLE. FBC 107.2.1.4 | | | | | | 6) THE PRODUCT APPROVAL FOR THE ROOFING MATERIAL | | | SPECIFIED ON THE PLANS (NOA NO. 14-0611.01) IS EXPIRED. | | | PLEASE REVISE THE PLANS. | | | | | | 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF | | | THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES, | | | STORM PANELS, ALUMINUM SIDING, ALUMINUM SOFFIT AND | | | OVERHEAD GARAGE DOORS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-07-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-07-28 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-07-28 |
Time |
07:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2016-06-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-06-17 |
Time |
17:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-06-17 |
Time |
17:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-08-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-08-29 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-08-19 |
Time |
15:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-07-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-07-28 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-07-22 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2016-07-22 12:57:37 | RMCDOUGAL'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-06-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-06-20 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-06-03 |
Time |
11:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2016-07-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-07-28 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-07-28 |
Time |
07:46 |
Sent To |
|
|
| Notes |
| 2016-07-28 07:46:57 | EXHAUST FAN WAS REMOVED FROM THE SCOPE OF WORK. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-06-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-06-20 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-06-17 |
Time |
18:07 |
Sent To |
|
|
| Notes |
| 2016-06-20 14:19:11 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) EXISTING BUILDING | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE 20" X 20" EXHAUST FAN. FBC-M | | | TABLE 403.3 REQUIRES A MINIMUM OF 200 CFMS FOR A TWO | | | CAR GARAGE. |
|
|