Plan Review Details - Permit 16060187
Plan Review Stops For Permit 16060187
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-29 Cont ID  
Sent By rmcdouga Date 2016-08-29 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2016-08-29 Time 12:27 Sent To  
Notes
2016-08-29 15:58:18APPROVED WITH EXCEPTION
 1) THE PRODUCT APPROVAL FOR THE METAL ROOFING IS FOR
 NON-INSULATED DECKS AND THE PLANS SHOW 2" RIGID
 INSULATION ON SHEET S-2. SUBMIT NEW PRODUCT APPROVALS
 OR REVISED PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-28 Cont ID  
Sent By rmcdouga Date 2016-07-28 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2016-07-28 Time 07:12 Sent To  
Notes
2016-07-28 14:58:53PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE NEW METAL ROOFING, ALUMINUM SIDING AND ALUMINUM
 PREFORATED V-GROOVE SOFFIT.
  
 2) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE GAF PRODUCT APPROVAL (NOA NO. 14-1030.02) FOR AN
 INSULATED ROOF AS SPECIFIED ON THE PLANS WILL BE USED.
 SUBMIT TWO SETS OF RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING AS REQUIRED BY LIMITATION NUMBER 7 OF THE
 NOA.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-20 Cont ID  
Sent By rmcdouga Date 2016-06-20 Time 16:11 Rev Time 0.00
Received By rmcdouga Date 2016-06-17 Time 17:32 Sent To  
Notes
2016-06-20 14:45:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS ARE REQUIRED TO HAVE THE ORIGINAL
 HANDWRITTEN SIGNATURE OF THE ENGINEER AND HIS SEAL
 (COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE) PER FAC
 61G15-23.002.
  
 2) THE SEAL IS REQUIRED TO BE A MINIMUM OF 1-7/8 INCHES
 IN DIAMETER. FAC 61G15-23.001
  
 3) FOR CITY OF WEST PALM BEACH RECORD KEEPING PURPOSES
 THE PLANS ARE REQUIRED TO BE A MINIMUM OF 1/8 INCH
 SCALE. FBC107.2.1.3 AFTER THESE PLANS WERE REDUCED IN
 SIZE THEY ARE NO LONGER 1/8 INCH SCALE.
  
 4) SPECIFY THE WIND DESIGN DATA INCLUDING WIND SPEED
 AND EXPOSURE CATEGORY ON THE PLANS. FBC-R301.2.1
  
 5)THE NOTES 1 AND 2 AT THE BOTTOM OF SHEET S-3 ARE NOT
 LEGIBLE. FBC 107.2.1.4
  
 6) THE PRODUCT APPROVAL FOR THE ROOFING MATERIAL
 SPECIFIED ON THE PLANS (NOA NO. 14-0611.01) IS EXPIRED.
 PLEASE REVISE THE PLANS.
  
 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 STORM PANELS, ALUMINUM SIDING, ALUMINUM SOFFIT AND
 OVERHEAD GARAGE DOORS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-28 Cont ID  
Sent By rmcdouga Date 2016-07-28 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2016-07-28 Time 07:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-06-17 Cont ID  
Sent By rmcdouga Date 2016-06-17 Time 17:57 Rev Time 0.00
Received By rmcdouga Date 2016-06-17 Time 17:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-29 Cont ID  
Sent By rmcdouga Date 2016-08-29 Time 15:56 Rev Time 0.00
Received By rmcdouga Date 2016-08-19 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-28 Cont ID  
Sent By rmcdouga Date 2016-07-28 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2016-07-22 Time 12:57 Sent To  
Notes
2016-07-22 12:57:37RMCDOUGAL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-20 Cont ID  
Sent By rmcdouga Date 2016-06-20 Time 16:11 Rev Time 0.00
Received By rmcdouga Date 2016-06-03 Time 11:01 Sent To  
Notes
2016-06-06 11:01:11R05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-07-28 Cont ID  
Sent By rmcdouga Date 2016-07-28 Time 07:46 Rev Time 0.00
Received By rmcdouga Date 2016-07-28 Time 07:46 Sent To  
Notes
2016-07-28 07:46:57EXHAUST FAN WAS REMOVED FROM THE SCOPE OF WORK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-20 Cont ID  
Sent By rmcdouga Date 2016-06-20 Time 14:19 Rev Time 0.00
Received By rmcdouga Date 2016-06-17 Time 18:07 Sent To  
Notes
2016-06-20 14:19:11PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014) EXISTING BUILDING
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE 20" X 20" EXHAUST FAN. FBC-M
 TABLE 403.3 REQUIRES A MINIMUM OF 200 CFMS FOR A TWO
 CAR GARAGE.