Plan Review Details - Permit 16060181
| Plan Review Stops For Permit 16060181 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-12-15 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-12-15 |
Time |
07:02 |
Sent To |
|
|
| Notes |
| 2016-12-15 14:43:48 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16060181 | | | ADD: 1301 MERCER AVE. | | | CONT: STOR-ALL CONSTRUCTION | | | TEL: 561-966-0056 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 3RD REVIEW | | | DATE: THURS. DEC. 15/ 2016 | | | | | | ACTION: BUILDING PROVISO: | | | | | | 1) ROOFING SUBMITTAL CARLISLE SURE-WELD TPO SINGLE PLY | | | ROOF SYSTEM WAS SUBMITTED, SUB-SYSTEM SC-168 WAS | | | HIGHLIGHTED WITH A PRESSURE OF -67.5 PSF/ 10 FOOT WIDE | | | MATERIAL. F.I.E. FLORIDA INTERNATIONAL ENGINEERING | | | SUBMITTAL FOR HIS FLORIDA APPROVAL AND SUB-SYSTEM | | | LISTED ABOVE WAS NOT SIGNED AND SEALED BY AN ENGINEER. | | | THE FRONT PAGE LIST FOR ZONES 2 & 3 NO GOOD. 2ND PAGE | | | OF DOCUMENT INDICATES FOR ROOF ZONE 2 USE ? OF THE | | | SHEET 60 INCHES AND SPACING OF FASTENERS AT 6 INCHES ON | | | CENTER AND A 1.5 INCH OUTSIDE SEAM WELD. FOR ZONE 3 USE | | | A 30 INCH WIDE SHEET AND FASTENERS AT 6 INCHES ON | | | CENTER AND A 1.5 INCH OUTSIDE SEAM WELD. NOTE THE | | | ENGINEERING SHEET DOES NOT PROVIDE FOR ZONES 2 & 3 WHAT | | | THE NARROWER WIDTHS WILL BE GOOD FOR. RESUBMIT WITH | | | SIGNED AND SEALED DOCUMENTATION AND ASSUMED PRESSURES | | | FOR ZONES 2 & 3. | | | NOTE 14 OF THIS PRODUCT APPROVAL SHEET ALSO INDICATES | | | FOR THE ROOF TOP INSULATION ENGINEERING FOR ANCHORING | | | OF THE TAPERED WILL ALSO BE REQUIRED FOR THE VARIOUS | | | ROOF ZONES. | | | | | | 2) ROOF TOP A/C RACK/ STAND WILL NEED TO TAKE INTO | | | ACCOUNT THE THICKNESS OF THE ROOF TOP INSULATION FROM | | | THE FINISHED ROOF DECK VERTICALLY TO THE LOWEST | | | HORIZONTAL SUPPORT FOR THE A/C STAND AND ADD THE | | | THICKNESS OF THE ROOF INSULATION TO FIGURE CLEAR | | | WORKING HEIGHT IN ACCORDANCE WITH 2014 FBC-B TABLE | | | 1009.6.5. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | TEL: 561-805-6715 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2016-11-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-11-04 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-10-31 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2016-11-04 14:12:14 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16060181 | | | ADD: 1301 MERCER AVE. | | | CONT: STOR-ALL CONSTRUCTION | | | TEL: 561-966-0056 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2ND REVIEW | | | DATE: FRI. NOV. 04/ 2016 | | | ACTION: DENIED | | | | | | 1) SEMI-COMPLIED. DOCUMENTATION FOR THE VALUE OF THE | | | COST ASSOCIATED WITH THE BUILDING HAS BEEN AGREED WITH | | | THE BUILDING OFFICIAL ROBERT BROWN. THE VALUE OF | | | $8,597,303.00 ($78.19 SQ. FT.) WILL BE THE ASSESSED | | | VALUE FOR THE BUILDING. PLEASE NOTE THE MECHANICAL, | | | ELECTRICAL, PLUMBING AND ROOFING PERMIT VALUES ARE | | | INCORPORATED INTO THE MASTER/ PRIME PERMIT. THERE WILL | | | BE A $80.00 ADMINISTRATIVE FEE FOR THESE SUB-PERMITS IF | | | THEY WERE NOT GENERATED AT THE ORIGINAL PERMIT | | | SUBMITTAL TIME. | | | ALL OTHER SUB-PERMITS ASSOCIATED WITH THIS BUILDING, | | | LOW VOLTAGE, FIRE ALARM, FIRE SPRINKLER, ETC? PLEASE | | | PROVIDE AN ITEMIZED LIST OF TYPE OF PERMIT AND VALUE OF | | | THE CONTRACTS. PLEASE DEDUCT THESE VALUES FROM THE | | | VALUE OF $8,597,303.00 THIS ADJUSTED VALUE WILL BE THE | | | VALUE WE WILL USE ONCE THE UNKNOWNS ARE PROVIDED. THE | | | BUILDING DEPARTMENT DOES NOT WANT TO DOUBLE DIP IN THE | | | PERMIT FEES. | | | | | | 2) THIS BUILDING BEING A 5 STORY BUILDING IS CONSIDERED | | | A THRESHOLD BUILDING. / FL S. S. 553.71(7) THRESHOLD | | | BUILDING MEANING ANY BUILDING WHICH IS GREATER THAN (3) | | | STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY | | | OCCUPANCY CLASSIFICATION AS DENIED IN THE FLORIDA | | | BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND | | | AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. | | | | | | 2A)2ND REQUEST FOR A WRITTEN THRESHOLD INSPECTION PLAN, | | | IT WAS NOT INCLUDED IN THE SUBMITTED DOCUMENTS NOR PART | | | OF THE STRUCTURAL NOTES ON SHEETS SS0.0 & S0.1. | | | 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING | | | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | 2B)SEMI-COMPLIED. THRESHOLD INSPECTION FORMS. SHEET 3OF | | | 6 THE SPECIAL INSPECTOR D. MARK LEBLANC P.E. HAS SIGNED | | | ON AS THE JOBSITE INSPECTOR. WITHIN THE SUBMITTED | | | THRESHOLD INSPECTION FORMS THERE ARE DOCUMENTS FOR | | | BRETT S ROSE BN5798, DOUGLAS JOSEPH RICHARD BN6661 AND | | | PEDRO LUIS BOURG BN4952. IF THESE (3) INSPECTORS ARE | | | GOING TO DO JOBSITE INSPECTIONS UNDER YOUR DIRECTION, | | | THEN EACH OF THESE INSPECTORS WILL NEED TO SIGN PAGE 3 | | | OF 6 FOR JOBSITE INSPECTORS. | | | 1ST ROUND COMMENTS. THRESHOLD INSPECTOR: WPB AMENDMENT | | | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT | | | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS | | | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE | | | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE | | | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT | | | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO | | | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT | | | ISSUANCE WILL TAKE PLACE. | | | 2C) COMPLIED. THRESHOLD BLDG., STATEMENT/ 633 FLORIDA | | | STATUTE. | | | 2D) NOT REQUIRED. 110.3.7.4.3 ALL SHORING AND RESHORING | | | PROCEDURES, PLANS AND DETAILS.. | | | 2E)SEMI-COMPLIED. THE ONLY INSPECTOR THAT HAS NOT | | | WORKED IN THE THRESHOLD PROGRAM IN THE CITY OF WEST | | | PALM BEACH IS PEDRO LUIS BOURG. REQUIRED RESUME? HAS | | | NOT BEEN SUBMITTED. | | | 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL | | | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL | | | OR HIS DESIGNEE WILL REVIEW THE RESUME' | | | | | | 2F) COMPLIED. CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 2G) SEMI- COMPLIED. THREE SETS OF PLANS SUBMITTED, IN | | | AT LEAST ONE SET OF PLANS THERE ARE MISSING PLANS, | | | SHEETS : A-2.1, A-2.2, A-2.3, A-3.1, A-3.2, A-3.3 & | | | A-3.4. | | | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 2H)NOTICE ONLY!!! NO ACTION IS REQUIRED. PLEASE CALL | | | THE CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE | | | INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING | | | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT | | | THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF | | | JOB, NO INSPECTION ACTIVITY. | | | | | | 2I) NOTICE ONLY!!! NO ACTION IS REQUIRED. 109.3.6 | | | THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD | | | INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED | | | ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED | | | FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | 3-14) COMPLIED. | | | 15)2ND REQUEST. THIS REVIEW F. I. E. ENGINEERING & | | | TESTING LABS ROOF CALCULATIONS WERE TAKEN FOR AN | | | EXPOSURE C. THE JOBSITE LOCATION IS AN EXPOSURE D. BOTH | | | THE STRUCTURAL SHEETS AND ENGINEERING SHEETS FROM | | | ORIGINAL COMMENT. THE ROOFING PRODUCT APPROVAL | | | SUBMITTED FL -16730 GAF SINGLE PLY SYSTEM. NO | | | SUB-SYSTEM WAS CIRCLED W/ ASSOCIATED PREUSSRES, MAY | | | REQUIRE ENHANCED FASTENING. | | | | | | 16) 11/09/2016 I SPOKE WITH TOMMY HOBGOOD ABOUT THE | | | POSSIBILITY OF A STRUCTURE ONLY PERMIT. THE COMPONENTS | | | AND CLADDING WOULD BE ABLE TO BROUGHT IN UNDER THE | | | BUILDING PERMIT. DURING THIS TIME WE WOULD BE GETTING | | | SHOP DRAWINGS FOR THE SECONDARY FRAMING MEMBERS FOR THE | | | WALLS AND ROOF FRAMING MEMBERS, | | | | | | 11/04/2016.TO DATE THERE HAS BEEN NO SHOP DRAWINGS, | | | ELEVATIONS OR VIEW OF THE ROOF SHOWING THE SPACING | | | BETWEEN THE STRUCTURAL STEEL COLUMNS AND BEAMS OR THE | | | PURLINS AND GIRTS FOR ZONES 1,2,3 4 & 5. THIS WILL NEED | | | TO BE ENGINEERED DRAWINGS SINCE THE GIRTS AND PURLINS | | | ARE SECONDARY FRAMING MEMBERS OF THE BUILDING. SPACING | | | OF THE GIRTS AND PURLINS IS CRITICAL TO THE REVIEW OF | | | THE PRODUCT APPROVALS FOR COMPONENTS AND CLADDING. BOLT | | | LAYOUT FOR THE ANCHORAGE OF THE VERTICAL STEEL COLUMNS | | | TO THE FOUNDATIONS, AND CENTER TO CENTER OF COLUMNS. | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: | | | BUILDING ENVELOPE | | | STRUCTURAL CALCULATIONS (IF REQUIRED) | | | WALL SYSTEMS | | | FLOOR SYSTEMS | | | ROOF SYSTEMS | | | | | | 17A) ENGINEERING CALCULATIONS REVISION # 6 MBCI METAL | | | ROOF AND WALL SYSTEMS ENGINEERING REPORT IS NOT SIGNED | | | NOR SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING | | | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE | | | DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS. | | | | | | 17B) ENGINEERING CALCULATIONS REVISION # 6 MBCI METAL | | | ROOF AND WALL SYSTEMS ENGINEERING REPORT CONSISTING OF | | | (8) PAGES WILL ALSO NEED TO SHOW COMPLIANCE WITH | | | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX | | | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND | | | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE | | | PRODUCTION & PREPARATION OF EACH SECTION OF THE | | | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION | | | ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE | | | COVERED UNDER THE COVER SHEET OR INDEX SHEET. | | | | | | 18) PLEASE PROVIDE SPAN CHARTS FOR THE TYPE OF DECKING | | | THAT WILL BE INSTALLED ON FLOORS 2-5 AND ALLOWABLE | | | LOADS. PLEASE ALSO SEE SHEETS S2.1-S2.5 THERE IS AN | | | ALTERNATE USE OF DECKING MATERIAL UNDER NOTE # 1. | | | PLEASE SEE 2014 FLORIDA BUILDING CODE W 2014 WEST PALM | | | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER | | | 1, ADMINISTRATION 2014 FLORIDA BUILDING CODE W 2014 | | | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION. NO ALTERNATES. SUCH | | | DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION, | | | IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF | | | MATERIALS, WHERE | | | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL | | | CODES. SUCH INFORMATION SHALL BE SPECIFIC, AND THE | | | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN | | | PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE | | | USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. | | | | | | 19) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 20) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-08-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-08-16 |
Time |
07:27 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-08-15 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2016-08-16 07:24:30 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16060181 | | | ADD: 1301 MERCER AVE. | | | CONT: STOR-ALL CONSTRUCTION | | | TEL: 561-966-0056 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 1ST REVIEW | | | DATE: MON. JUNE 11/ 2016 | | | ACTION: DENIED | | | | | | 1) 2ND REQUEST. BUILDING VALUATION. THE RESPONSE LETTER | | | FROM STOR ALL CONSTRUCTION INDICATES FOR THIS BUILDING | | | TYPE OF CONSTRUCTION YOU ARE BUILDING AT A PRICE OF $ | | | 70.53 PER GROSS SQUARE FOOT. DOES THIS SQUARE FOOT | | | PRICE INCLUDE STRUCTURAL, ELECTRICAL, PLUMBING, | | | MECHANICAL, INTERIOR FINISHES, NORMAL SITE WORK | | | (EXCAVATION AND BACKFILL FOR BUILDINGS), ARCHITECTURAL | | | AND DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT; | | | EXCLUDING ONLY LAND VALUE. IF SO YOU MAY SUBMIT A | | | LETTER TO THE BUILDING OFFICIAL ROBERT BROWN ASKING FOR | | | A REDUCTION IN PERMIT FEES. PLEASE INCLUDE A PRICE | | | ANALYSIS OF SIMILAR PROJECTS IN COST, SQUARE FOOT AREA, | | | HEIGHT AND BUILDING TYPE FOR RECENT BUDGET PRICING OF | | | SIMILAR PROJECTS IN THE SOUTH FLORIDA REGION. | | | | | | 1ST ROUND REVIEW COMMENT. THE BUILDING VALUATION IS LOW | | | FOR THE BUILDING TYPE AND OCCUPANCY. THE JUNE 2016 IIC | | | TABLES LIST THE VALUE OF THIS PROJECT AT $9,880,466.00 | | | DOLLARS. 109,954 SQ. FT. X $89.86= $9,880,466.00. | | | 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER | | | ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL | | | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, | | | PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE | | | WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD | | | AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION | | | REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF | | | NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | 2) THIS BUILDING BEING A 5 STORY BUILDING IS CONSIDERED | | | A THRESHOLD BUILDING. / FL S. S. 553.71(7) ?THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 2A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. | | | | | | 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.3.7.3 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S | | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS | | | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH | | | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND | | | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE | | | PLACE. WE NEED EITHER THE GENERAL CONTRACTOR OR THE | | | STRUCTURAL ENGINEERS E-MAIL ADDRESS TO FORWARD THE | | | REQUIRED THRESHOLD FORMS TO BE FILED OUT AND RETURNED | | | WITH THE NEXT REVIEW CYCLE. | | | | | | THRESHOLD INSPECTOR FORMS E-MAILED TO: | | | [email protected] 8/24/2016 2:10 PM. | | | | | | 2C) COMPLIED. W.P.B. AMENDMENT 110.3.7.4.4 SHEET A00.4 | | | & S0.0. | | | | | | 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL | | | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL | | | OR HIS DESIGNEE WILL REVIEW THE RESUME? BEFORE PERMIT | | | ISSUANCE. | | | | | | 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB | | | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | 110.3.7.5 NO ENFORCING AGENCY MAY ISSUE A BUILDING | | | PERMIT FOR CONSTRUCTION OF ANY THRESHOLD BUILDING | | | EXCEPT TO A LICENSED GENERAL CONTRACTOR, AS DEFINED IN | | | SECTION 489.105(3)(A), FLORIDA STATUTES, OR TO A | | | LICENSED BUILDING CONTRACTOR, AS DEFINED IN SECTION | | | 489.105(3)(B), FLORIDA STATUTES, WITHIN THE SCOPE OF | | | HER OR HIS LICENSE. | | | | | | 2F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF | | | DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT | | | ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE | | | PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN | | | E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU | | | MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE | | | PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE | | | OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO | | | PRINT MAYBE IN BLACK & WHITE.. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 2G) 2ND REQUEST. 110.3.7.4.3 ALL SHORING AND RESHORING | | | PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE | | | ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND | | | RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED | | | AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | 2H) 2ND REQUEST. PLEASE CALL THE CITY OF WEST PALM | | | BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN | | | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 2I) 2ND REQUEST.109.3.6 THRESHOLD BUILDINGS, OPERATING | | | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT | | | THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING | | | PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | 3-13) COMPLIED. | | | | | | 14) 2ND REQUEST. INDEX SHEET INDICATES THERE ARE FIRE | | | PROTECTION PLANS IN THE SETS OF DRAWINGS, NO PLANS. | | | SHEET A-0.3 INDICATES THIS BUILDING IS TO BE FIRE | | | SPRINKLERED AND TO TAKE A ONE STORY INCREASE. NO FIRE | | | SPRINKLER PLANS WERE SUBMITTED. 105.3.1.2 NO PERMIT MAY | | | BE ISSUED FOR ANY BUILDING CONSTRUCTION,(2) FIRE | | | SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR ADDITION | | | WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS | | | 50 OR MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR | | | II OR CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521, | | | FLORIDA STATUTES, MAY DESIGN A FIRE SPRINKLER SYSTEM OF | | | 49 OR FEWER HEADS AND MAY DESIGN THE ALTERATION OF AN | | | EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION | | | CONSISTS OF THE RELOCATION, ADDITION OR DELETION OF NOT | | | MORE THAN 49 HEADS, NOTWITHSTANDING THE SIZE OF THE | | | EXISTING FIRE SPRINKLER | | | SYSTEM. ALSO REVIEW FLORIDA ADMINISTRATIVE CODE | | | 61G15-32.004 | | | | | | 15A) THE ROOFING PRODUCT APPROVAL SUBMITTED FL | | | -14083R11A CARLISLE SYNTEC SYSTEMS, CARLISLE SURE WELD | | | TPO SINGLE PLY ROOF SYSTEMS NOTED ON THE FRONT PAGE FOR | | | SUB-SYSTEM SEE PAGE 18 & 24. PLEASE NOTE PAGE 18 THE | | | SUB-SYSTEM HIGHLIGHTED SC-111 IS GOOD FOR -157.5 @ 10 | | | SQ. FT./ THE STRUCTURAL SHEET S0.1 THE VASD WIND CHART | | | FOR ZONE # 3 @ 10 SQ. FT. SHOWS PRESSURES OF -163. THE | | | SECOND ISSUE PAGE 24 HAD BEEN REMOVED BY MISTAKE WILL | | | NEED TO KNOW WHICH SUB-SYSTEM IS TO BE USED IN ZONES 1 | | | OR 2? PLEASE INDICATE WHICH SUB-SYSTEMS TO IN INSTALLED | | | IN WHICH ZONES. | | | | | | 15B) PLEASE CLARIFY HIGHLIGHT/ CIRCLE THE PANELS TO BE | | | INSTALLED. WIDTH, LENGTH IN SPANS AND ASSOCIATED | | | PRESSURES FOR BOTH THE FLORIDA APPROVAL AS WELL AS THE | | | MIAMI-DADE NOA. ADDITIONAL INFORMATION REQUIRED. | | | 107.2.1.3. | | | | | | 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-07-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-07-11 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-07-11 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2016-07-11 15:39:13 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16060181 | | | ADD: 1301 MERCER AVE. | | | CONT: STOR-ALL CONSTRUCTION | | | TEL: 561-966-0056 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 1ST REVIEW | | | DATE: MON. JUNE 11/ 2016 | | | ACTION: DENIED | | | | | | 1) THE BUILDING VALUATION IS LOW FOR THE BUILDING TYPE | | | AND OCCUPANCY. THE JUNE 2016 IIC TABLES LIST THE VALUE | | | OF THIS PROJECT AT $9,880,466.00 DOLLARS. 109,954 SQ. | | | FT. X $89.86= $9,880,466.00. | | | 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER | | | ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL | | | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, | | | PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE | | | WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD | | | AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION | | | REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF | | | NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | 2) THIS BUILDING BEING A 5 STORY BUILDING IS CONSIDERED | | | A THRESHOLD BUILDING. / FL S. S. 553.71(7) ?THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING | | | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S | | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS | | | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH | | | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND | | | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE | | | PLACE | | | | | | 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. | | | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH | | | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT | | | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE | | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | 2D) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, | | | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT | | | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING | | | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND | | | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | 2E) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME' | | | | | | 2F) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 2G) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE | | | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, | | | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING | | | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE | | | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR | | | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN | | | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR | | | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE | | | IN BLACK & WHITE.. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL | | | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 | | | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES | | | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER | | | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE | | | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR | | | WALLS AND CEILINGS. | | | | | | 3) SHEET S0.0. PROVIDES THE WIND DESIGN CRITERIA. THE | | | EXPOSURE IS LISTED AS A ?C? EXPOSURE. EXPOSURES FOR THE | | | BUILDING ARE TAKEN FOR THE WORST CASE SCENARIO. THERE | | | IS OVER 5000 FEET OF WATER TO THE NORTH AND NNW MEETING | | | THE DEFINITION OF EXPOSURE D. 1609.4 EXPOSURE CATEGORY. | | | 1609.4.3 EXPOSURE CATEGORIES. | | | AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE | | | WITH THE FOLLOWING: EXPOSURE D. EXPOSURE D SHALL APPLY | | | WHERE THE GROUND SURFACE ROUGHNESS, AS DEFINED BY | | | SURFACE ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION | | | FOR A DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20 | | | TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER. | | | EXPOSURE D SHALL ALSO APPLY WHERE THE GROUND SURFACE | | | ROUGHNESS IMMEDIATELY UPWIND OF THE SITE IS B OR C, AND | | | THE SITE IS WITHIN A DISTANCE OF 600 FEET (183 M) OR 20 | | | TIMES THE BUILDING HEIGHT, WHICHEVER IS GREATER, FROM | | | AN EXPOSURE D CONDITION AS DEFINED IN THE PREVIOUS | | | SENTENCE. | | | | | | 4) WITH THE PRESSURES GIVEN ON SHEET S0.1 THE PRESSURES | | | WILL BE HIGHER SEE THE 2014 FBC-B TABLE 1609.7(2) | | | ADJUSTMENT FACTOR FOR BUILDING HEIGHT AND EXPOSURE, | | | (?). 55FT./ EXPOSURE D ADJUSTMENT FACTOR OF 1.84. | | | PRESSURES WILL NEED TO BE RECALCULATED. | | | | | | 5) SHEET S0.1 THE CHART FOR COMPONENTS & CLADDING | | | PRESSURES THERE ARE ROOF ZONES 1 FOR THE INTERIOR ZONE | | | AND WHAT APPEARS TO BE TWO ZONE 3 CATEGORIES, NO | | | PERIMETER ZONE # 2? ASCE 7-10 FIGURE 30.5.1 . | | | | | | 6) SHEET S0.1 PLEASE PROVIDE THE COMPONENT AND CLADDING | | | IN VULT AND IN VASD. ALL OF THE PRODUCT APPROVALS ARE | | | IN VASD, THE INSPECTORS IN THE FIELD NEED THE PLANS IN | | | VASD TO MATCH THE PRODUCT APPROVAL. 1609.3.1 WIND SPEED | | | CONVERSION VULT TO VASD. | | | | | | 7) PLEASE NOTE THERE IS NO DOOR SCHEDULE LISTED IN THE | | | DRAWING INDEX AND ON SHEET A5.3 IN THE HARDWARE | | | SCHEDULE NEITHER EXIT STAIR TOWER 1 OR 2 DOOR HARDWARE | | | SHOW A FIRE RATING . SEE 2014 FBC-B 1009.3.1.2. | | | STAIRWELL 4 STORIES AND MORE REQUIRE A 2 HR. FIRE | | | RATING AND TABLE 716.5 REQUIRES 1 ? HOUR PROTECTIVES. | | | | | | 8) SHEET A-1.1 SHOWS THE ELEVATOR MACHINE ROOM AND THE | | | ELECTRICAL ROOM AS 2 HOUR FIRE RATING, AGAIN NO DOOR | | | SCHEDULE, REQUIRES 1 ? HOUR PROTECTIVE FOR A 2 HOUR | | | RATED WALL. 2014 FBC-B TABLE 716.5. | | | | | | 9A) SHEETS A-4.5 & A-4.6 BOTH SHOW A SIDE VIEW OF THE | | | STAIRWELLS. THE 1ST FLOOR OF THE STAIR IN BOTH | | | STAIRWELLS DOES NOT SHOW COMPLIANCE WITH: 2014 | | | FBC-ACCESSIBILITY CODE 307.4 AND FIGURE 307.4. | | | | | | 9B) BOTH SHEETS A-4.5 & A-4.6 SHOW THE RISE AND RUN OF | | | THE STAIRS, BUT PLANS DO NOT INDICATE IF THE STAIRS ARE | | | TO HAVE SOLID RISERS. FBC-B 101009.7.5.3. | | | | | | 9C) SHEETS A-4.5 & A-4.6 NEITHER SHOW COMPLIANCE WITH | | | FBC-B 905.4. LOCATION OF CLASS I STANDPIPE(1) IN EVERY | | | REQUIRED STAIRWAY. | | | | | | 10) SHEET A-1.1 THE ELEVATOR CAB DOES NOT INDICATE WITH | | | STRETCHER REQUIREMENTS, SEE FBC-B 3002.4 ELEVATOR CARS | | | TO ACCOMMODATE AMBULANCE STRETCHERS. | | | | | | 11) SHEET A-4.5 DETAIL 4 INDICATES WHAT APPEARS TO BE A | | | HYDRAULIC ELEVATOR, PLEASE PROVIDE COMPLIANCE WITH | | | FBC-B 3011.1 ELECTROLYSIS PROTECTION FOR UNDERGROUND | | | HYDRAULIC ELEVATOR CYLINDERS. | | | 12) BOTH A-1.6 AND M6 SHOWS ROOF TOP COMPRESSORS ON TOP | | | OF A/C STANDS. PLEASE SUBMIT THE PRODUCT APPROVAL FOR | | | THE ROOF TOP STANDS. PROVIDE ANCHORING FOR THE STAND AS | | | WELL AS THE UNIT TO THE STAND. 2014 FBC-B 1609.1.2 | | | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & | | | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE | | | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR | | | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: (31)(G) PRE-ENGINEERED A/C STANDS. | | | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL | | | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO | | | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND | | | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 13) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE. THE REGISTERED DESIGN PROFESSIONAL | | | IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE FOR | | | REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS PREPARED | | | BY OTHERS, INCLUDING PHASED AND DEFERRED SUBMITTAL | | | ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF THE | | | BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA | | | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY | | | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | 14) SHEET A-0.3 INDICATES THIS BUILDING IS TO BE FIRE | | | SPRINKLERED AND TO TAKE A ONE STORY INCREASE. NO FIRE | | | SPRINKLER PLANS WERE SUBMITTED. 105.3.1.2 NO PERMIT MAY | | | BE ISSUED FOR ANY BUILDING CONSTRUCTION,(2) FIRE | | | SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR ADDITION | | | WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS | | | 50 OR MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR | | | II OR CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521, | | | FLORIDA STATUTES, MAY DESIGN A FIRE SPRINKLER SYSTEM OF | | | 49 OR FEWER HEADS AND MAY DESIGN THE ALTERATION OF AN | | | EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION | | | CONSISTS OF THE RELOCATION, ADDITION OR DELETION OF NOT | | | MORE THAN 49 HEADS, NOTWITHSTANDING THE SIZE OF THE | | | EXISTING FIRE SPRINKLER | | | SYSTEM. ALSO REVIEW FLORIDA ADMINISTRATIVE CODE | | | 61G15-32.004 | | | | | | 15) THE ROOFING PRODUCT APPROVAL SUBMITTED FL -16730 | | | GAF SINGLE PLY SYSTEM. NO SUB-SYSTEM WAS CIRCLED W/ | | | ASSOCIATED PREUSSRES, MAY REQUIRE ENHANCED FASTENING. | | | | | | 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2016-10-17 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-10-17 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-10-17 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2016-10-17 09:42:02 | PROVISO: | | | | | | ONE SET MISSING SHEET E6, PLEASE INSERT PREVIOUS | | | APPROVED SHEET FOR APPPROVAL | | | | | | VAL PEREZ | | | *6717 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-07-29 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-07-29 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-07-29 |
Time |
12:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-06-25 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-06-25 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-06-25 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2016-06-25 13:37:51 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED | | | SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL | | | SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE WILL | | | SUFFICE. | | | 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE | | | REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS | | | FOR FIRE PUMP AND ALL LOW VOLTAGE SYSTEMS TO INCLUDE | | | BUT NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS, CCTV, | | | PHONE AND DATA, SIGNAGE, WIRELESS SYSTEMS, CAR CHARGING | | | STATIONS, ETC. A NOTE WILL SUFFICE. | | | 3. PLEASE LABEL RECEPTACLE IN WORK ROOM TO BE GFCI | | | PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF SINK ALL TO | | | BE GFCI. SEE E1 OFFICE AREA | | | 4. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL | | | AVAILABLE FAULT CURRENT AT THE TRANSFORMERS. FBC | | | 107.3.5 | | | 5. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5 | | | 6. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC | | | 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE | | | DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS. | | | 7. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS | | | FOR FEEDERS AND BRANCH CIRCUITS. | | | 8. ADDRESS FIRE, MECH AND PLUMBING REVIEWS REGARDING | | | ELECTRICAL REQUIREMENTS. FBC 107.3.5 | | | 9. LABEL 1000AMP MAIN TO BE GFCI PROTECTED PER NEC | | | 240.13 | | | 10. PROVIDE PHOTOMETRICS FOR ALL AREAS TO SHOW MINIMUM | | | LIGHTING LEVELS. FBC 107.3.5 | | | 11. PROVIDE A NOTE AT THE RISER DIAGRAM FIRE PUMP | | | CONTROLLER TO RATED FOR SERVICE ENTRANCE. | | | 12. SHOW LOCATION OF PANEL AC, AT ELECTRICAL ROOM | | | LOCATION. PROVIDE A NOTE TO COMPLY WITH TAP RULES PER | | | NEC 240.21B | | | 13. AT TRANSFORMER RATED 112.5 SIZE GROUNDING ELECTRODE | | | CONDUCTOR PER NEC 250.66 TABLE/ 1/0CU. | | | 14. SHOW A GFCI RECEPTACLE AT THE ELEVATOR MACHINE | | | ROOM/ ELEVATOR EQUIPMENT PER NEC 620.23. ALSO A | | | DEDICATED BRANCH TO BE PROVIDED EXCLUSIVELY TO ROOM. | | | CIRCUIT H-9 SHOWN FEEDING OTHER AREAS, CORRECT AND | | | ADDRESS AT PANEL SCHEDULE ALSO. | | | 15. PROVIDE A NOTE TO COMPLY WITH FBC ENERGY | | | CONSERVATION 2014- 50% OF RECEPTACLES TO BE | | | AUTOMATICALLY CONTROLLED PER CODE SECTION FBC C405.7. | | | SHOW COMPLIANCE. | | | 16. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL | | | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS | | | REGARDING THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2017-01-06 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2017-01-06 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2017-01-06 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2016-10-03 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2016-10-03 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2016-10-03 |
Time |
|
Sent To |
I |
|
| Notes |
| 2016-10-03 17:17:11 | FINAL COMMENTS THRU ENGINEERING. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2016-07-25 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2016-07-25 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2016-07-25 |
Time |
|
Sent To |
Z |
|
| Notes |
| 2016-07-25 15:02:42 | PLEASE ADDRESS FIRE DEPT COMMENTS. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF | | | WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." | | | FOR MORE INFORMATION REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2016-10-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-10-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-10-27 |
Time |
17:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2016-08-04 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-08-04 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-08-04 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2016-08-04 13:59:23 | 1301 MERCER AVENUE | | | PERMIT #16060181 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FIRE PROTECTION SHEETS FP-61G NOT SUBMITTED. | | | | | | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE | | | REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE | | | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN | | | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED | | | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. FOR ISSUANCE | | | OF A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF | | | THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE | | | PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR | | | ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER | | | FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE | | | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-06-17 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-06-17 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-06-09 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2016-06-09 09:52:36 | 1301 MERCER AVENUE | | | PERMIT #16060181 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ARE CONSTRUCTION TRAILERS PLANNED FOR THIS SITE? | | | NOTE:THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION | | | TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO | | | "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC | | | SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION | | | REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION | | | TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND | | | COMPLIANCE WITH THE FOLLOWING: | | | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: | | | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF | | | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE | | | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, | | | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. | | | PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK | | | SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH | | | AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED | | | EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION | | | AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE | | | SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING | | | MATERIALS SHALL BE PROVIDED. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | CIVIL: NO NEW OR EXISTING FIRE HYDRANTS INDICATED. | | | PROVIDE REQUIRED FIRE HYDRANTS AND FIRE FLOW | | | CALCULATIONS IN ACCORDANCE WITH NFPA 1 SECTION 18.4. | | | | | | **PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER | | | MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE | | | INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO | | | CONSTRUCTION WORK.** | | | | | | CIVIL: PROVIDE AUTOTURN DRAWING FOR 47-FOOT LONG FIRE | | | LADDER APPARATUS. | | | | | | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE | | | REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE | | | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN | | | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED | | | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. FOR ISSUANCE | | | OF A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF | | | THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE | | | PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR | | | ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER | | | FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE | | | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | PER NFPA 101 SECTION 7.2.2.5.4 - STAIRWAY | | | IDENTIFICATION: NEW ENCLOSED STAIRS SERVING THREE OR | | | MORE STORIES AND EXISTING ENCLOSED STAIRS SERVING FIVE | | | OR MORE STORIES SHALL COMPLY WITH (A) THROUGH (L). | | | (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE | | | WITHIN THE ENCLOSURE AT EACH FLOOR LANDING. | | | (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL. | | | (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP | | | AND BOTTOM OF THE STAIR ENCLOSURE. | | | (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF | | | THE STAIR ENCLOSURE. | | | (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND | | | THE DIRECTION TO, EXIT DISCHARGE. | | | (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE | | | APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A | | | POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN | | | OR CLOSED POSITION. | | | (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE. | | | (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE | | | WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE | | | WALL. | | | (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED | | | AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH | | | LETTERING. | | | (J) SIGNAGE THAT READS ?NO ROOF ACCESS? AND IS LOCATED | | | UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL | | | DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS. | | | LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH. | | | (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE | | | MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS. | | | MEZZANINE LEVELS SHALL HAVE THE LETTER ?M? OR OTHER | | | APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR | | | NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER ?B? | | | OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING | | | THE FLOOR LEVEL NUMBER. | | | (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF | | | THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN | | | IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS. | | | | | | SHEET A2.3: 5 STORY ELEVATOR SHAFT WALL IS SHOWN WITH A | | | 1-HOUR FIRE RESISTANCE RATING. | | | | | | SHEET A5.3: NON OF THE STAIR DOORS HAVE A FIRE | | | RESISTANCE RATING. | | | | | | SHEET E-7: COULD NOT LOCATE THE FIRE SPRINKLER JOCKEY | | | PUMP CONTROL PANEL. | | | | | | PER NFPA 1 SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE | | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | | FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE | | | AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. | | | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON | | | CENTER. | | | | | | DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT | | | RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE | | | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION | | | 1.14.4). | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-01-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-01-06 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-12-06 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2016-12-07 09:26:59 | C37 | | | **OVERFLOW OF PLANS IN C38** |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-12-07 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-12-07 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-10-11 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-10-03 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-10-03 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-07-26 |
Time |
08:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-07-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-07-26 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-06-10 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
5 |
Status |
N |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-12-15 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-12-15 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2016-12-15 09:07:37 | PALM BEACH COUNTY IMPACT FEES | | | DATE RECEIVED: 10/11/2016 | | | RECEIPT NUMBER 2016-1011-235 | | | TRACKING NUMBER MU-2016-024774-0000 | | | TOTAL FEES $62,279.87 | | | | | | PLAN REVIEWER: J. WITMER |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
4 |
Status |
F |
Date |
2016-11-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-11-04 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-11-04 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2016-11-04 14:15:05 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2016-10-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-10-31 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-10-31 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2016-10-31 12:26:49 | P. B. C. IMPACT FEE OFFICE: | | | TRACKING NO. MU-2016-024774-0000 | | | RECEIPT NO. 2016-1011-235 | | | FEES: $62,279.87 | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2016-08-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-08-16 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-08-16 |
Time |
07:25 |
Sent To |
|
|
| Notes |
| 2016-08-16 07:26:15 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-07-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-07-11 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-07-11 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2016-07-11 08:03:50 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-12-15 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-12-15 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2016-10-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-10-21 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-10-21 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2016-10-21 16:05:27 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #16060181 | | | 10/21/16 | | | | | | THE PLANS HAVE BEEN FAILED AGAIN DUE TO THE PREVIOUS | | | COMMENTS LISTED BELOW THAT HAVE NOT BEEN ADDRESSED. | | | THE ENGINEER OF RECORD MUST CORRECT THE PLANS AND | | | PROVIDE A WRITTEN RESPONSE NARRATIVE. | | | | | | 1) COMMISSIONING OF THE AC SYSTEMS IS REQUIRED IN | | | ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY | | | CONSERVATION. SUBMIT A COMMISSIONING PLAN IN COMPLIANCE | | | WITH C408.2.1 FBC-14 ENERGY CONSERVATION- (SEE SECTION | | | C408.2.1 FBC-14 ENERGY CONSERVATION PRINTED BELOW). | | | | | | 2) THE COMPLIANCE DATA FOR THE AC SYSTEMS (AC | | | IDENTIFICATIONS, AND CAPACITIES) LISTED ON PAGE 6 OF | | | THE ENERGY GAUGE PERFORMANCE SUBMITTAL DO NOT MATCH THE | | | SCHEDULES ON SHEET M8. | | | | | | 3) REFER TO SECTION C403.2.2 FBC-14 ENERGY | | | CONSERVATION: THE CAPACITIES OF THE DAIKIN AC SYSTEMS | | | SPECIFIED FOR THE 1ST- 4TH FLOOR WAREHOUSE AREAS ARE | | | EXCEEDING THE CALCULATED LOADS SHOWN IN THE SIZING | | | SUMMARRIES. | | | | | | C408.2.1 COMMISSIONING PLAN. | | | A COMMISSIONING PLAN SHALL BE DEVELOPED BY A REGISTERED | | | DESIGN PROFESSIONAL OR APPROVED AGENCY AND SHALL | | | INCLUDE THE FOLLOWING ITEMS: | | | | | | 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL | | | BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING, | | | INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF | | | THE ACTIVITIES. | | | | | | 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR | | | SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO | | | BE PERFORMED. | | | | | | 3. FUNCTIONS TO BE TESTED, INCLUDING, BUT NOT LIMITED | | | TO CALIBRATIONS AND ECONOMIZER CONTROLS. | | | | | | 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED. | | | AT A MINIMUM, TESTING SHALL AFFIRM WINTER AND SUMMER | | | DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS. | | | | | | 5. MEASURABLE CRITERIA FOR PERFORMANCE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-08-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-08-03 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-08-03 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2016-08-03 16:25:27 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16060181 | | | 8/3/16 | | | | | | COMMENTS #1-4 FROM THE 1ST REVIEW STILL EXIST. I HAVE | | | REPRINTED THEM BELOW WITH SOME MODIFICATIONS BASED ON | | | THIS 2ND REVIEW. | | | | | | 1) COMMISSIONING OF THE AC SYSTEMS IS REQUIRED IN | | | ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY | | | CONSERVATION. SUBMIT A COMMISSIONING PLAN IN COMPLIANCE | | | WITH C408.2.1 FBC-14 ENERGY CONSERVATION. | | | | | | 2) THE COMPLIANCE DATA FOR THE AC SYSTEMS (AC | | | IDENTIFICATIONS, AND CAPACITIES) LISTED ON PAGE 6 OF | | | THE ENERGY GAUGE PERFORMANCE SUBMITTAL DO NOT MATCH THE | | | SCHEDULES ON SHEET M8. | | | | | | 3) ENERGY GAUGE SUBMITTAL, PAGE 2 CERTIFICATIONS: THE | | | ARCHITECT OF RECORD MUST PROVIDE HIS REGISTRATION | | | NUMBER ON THE PAGE. | | | | | | 4) REFER TO SECTION C403.2.2 FBC-14 ENERGY | | | CONSERVATION: THE CAPACITIES OF THE DAIKIN AC SYSTEMS | | | SPECIFIED FOR THE 1ST- 4TH FLOOR WAREHOUSE AREAS ARE | | | EXCEEDING THE CALCULATED LOADS SHOWN IN THE SIZING | | | SUMMARRIES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-06-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-06-16 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-06-16 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2016-06-16 10:38:45 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16060181 | | | 6/16/16 | | | | | | 1) COMMISSIONING OF THE AC SYSTEMS IS REQUIRED IN | | | ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY | | | CONSERVATION. SUBMIT A COMMISSIONING PLAN IN COMPLIANCE | | | WITH C408.2.1 FBC-14 ENERGY CONSERVATION. | | | | | | 2) THE COMPLIANCE DATA FOR THE AC SYSTEMS (AC | | | IDENTIFICATIONS, AND CAPACITIES) LISTED ON PAGE 6 OF | | | THE ENERGY GAUGE PERFORMANCE SUBMITTAL DO NOT MATCH THE | | | SCHEDULES ON SHEET M8. | | | | | | 3) ENERGY GAUGE SUBMITTAL, PAGE 2 CERTIFICATIONS: THE | | | ARCHITECT OF RECORD MUST PROVIDE HIS SIGNATURE, SEAL, | | | AND REGISTRATION NUMBER ON THE PAGE. THE OWNER MUST | | | SIGN AND DATE. | | | | | | 4) REFER TO SECTION C403.2.2 FBC-14 ENERGY | | | CONSERVATION: THE CAPACITIES OF THE DAIKIN AC SYSTEMS | | | ARE EXCEEDING THE CALCULATED LOADS SHOWN IN THE SIZING | | | SUMMARRIES. | | | | | | 5) SHEETS A-6.1- A-6.5: PROVIDE CEILING FINISH SYMBOLS | | | IN THE LEGENDS. PLEASE NOTE THAT ACCESS FOR MAINTENANCE | | | AND REPLACEMENT OF ABOVE CEILING AIR HANDLERS MUST BE | | | PROVIDED PER SECTION 306.1. INDICATE REQUIRED ACDCESS | | | PANELS ON THE PLANS WITH DIMENSIONS. | | | | | | 6) M1- M5: DUCT SMOKE DETECTORS ARE REQUIRED IN THE | | | RETURN AIR SYSTEMS OF THE AHU'S- SEE SECTION 606.2.1. | | | REVISE THE PLAN TO SHOW THE LOCATIONS AND PROVIDE | | | INSTALLATION DETAILS. | | | | | | 7) M1- M5: PROVIDE CLEARANCE DISTANCE MEASUREMENTS FOR | | | THE OUTDOOR AIR INTAKES AS REQUIRED BY SECTION 401.4. | | | | | | 8) M1- M5: PROVIDE EQUIPMENT SCHEDULES AND SUBMITTALS | | | (FL. PRODUCT APPROVALS AND/OR NOA'S) FOR THE EXHAUST | | | OUTLET AND O/A INTAKE WALL CAPS- REFER TO SECTIONS | | | 401.5 AND 501.3.2. | | | | | | 9) M7: THE AC MOUNTING DETAIL NEEDS TO BE CLARIFIED | | | (MUCH OF THE PRINT IS ILLEGIBLE). PROVIDE A FL. PRODUCT | | | APPROVAL AND/OR MIAMI-DADE NOA FOR THE STAND, AND | | | PROVIDE THE WIND LOAD DESIGN CRITERIA PER SECTION 1609 | | | FBC-14 BUILDING. | | | | | | 10) P1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR AHU-1.F | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2017-01-06 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-01-06 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-06 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2016-10-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-10-26 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-10-26 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2016-10-26 12:54:04 | 2ND REVIEW | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE OVERFLOW SCUPPER THAT IS PART OF THE PRIMARY | | | DRAIN COLLECTOR BOX DOES NOT COMPLY WITH FBC PL SEC | | | 1108. A TOTALLY SEPARATE SECONDARY "OVERFLOW DRAIN" | | | WITH A SEPARATE OPENING IN PARAPET WALL IS REQUIRED. | | | PER FBC PL SEC 1108.2 AND SHALL COMPLY WITH FBC SEC | | | 1503.4.2.1 -1503.7 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2016-08-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-08-23 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-08-23 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2016-08-23 11:29:35 | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | | | | PLUMBING COMMENTS: 2ND REVIEW | | | | | | 2ND REQUEST | | | | | | 5. NOT COMPLIED SHOW CLEAR FLOOR SPACE FOR WATER | | | FOUNTAIN SHALL COMPLY WITH FBC ACC 602.2 CLEAR FLOOR | | | SPACE. | | | UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH | | | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | SHT A4.4 SHOWS A PARALLEL APPROACH IT SHALL BE A | | | FORWARD APPROACH. | | | | | | 10.NOT COMPLIED PROVIDE MANUFACTURE SPECIFICATIONS FOR | | | TANKLESS HEATERS AND ELEVATOR SUMP PIT OIL SMART PUMP. | | | PER PB AMEND. TO FBC SEC. 107.2.1 | | | SHOW NOTE ON PLAN TO PROVIDE MANUFACTURE SPECS AND | | | INSTILLATION GUIDES ON JOBSITE FOR INSPECTIONS. | | | | | | 12.NOT COMPLIED PROVIDE SLOPE OF HORIZONTAL STORM DRAIN | | | SHALL COMPLY WITH FBC PL TABLE 1106.3 | | | SHT. P1 YOU PROVIDED A NOTE REFERENCING THE TABLE BUT | | | YOU DID NOT LIST WHICH ONE OUT OF THE THREE SLOPES WAS | | | BEING USED. | | | | | | NEW COMMENTS | | | 1. THE FLOOR SINK FOR ELEVATOR SUMP PIT DRAINS IS NOT | | | VENTED. PER 901.2.1 VENTING REQUIRED. | | | TRAPS AND TRAPPED FIXTURES SHALL BE VENTED IN | | | ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN | | | THIS CHAPTER. | | | | | | 2. SHT P8 INCLUDE THE FLOOR SINK ON YOUR NOTE FOR THE | | | TRAP PRIMERS. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. THE LAVATORY FAUCETS IN THE BATHROOMS SHA HAVE A | | | TEMPERATURE LIMITING DEVICE TO COMPLY WITH FBC PL 416.5 | | | TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES. | | | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND | | | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES | | | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED | | | WATER SHALL BE DELIVERED THROUGH AN APPROVED | | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | | 1070 OR CSA B125.3. | | | 607.1.1 TEMPERATURE LIMITING MEANS. | | | A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE | | | AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF | | | COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR | | | MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY | | | TEMPERATURE AT FIXTURES. | | | | | | 4. SHT. P4 SHOWS 1IN CW FROM 3RD FLOOR TO BATHROOMS SHT | | | P8 WATER RISER SHOWS 3/4 FROM 3RD FLOOR TO BATHROOMS | | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 5. THE SPOUT FOR THE EMERGENCY ROOF DRAIN SHALL | | | DISCHARGE A MIN. OF 12IN FROM BUILDING. PER FBC 1503.7 | | | | | | SEPARATE PERMIT REQUIRED FOR BACKFLOWS | | | | | | DOCUMENTATION REQUIRED FOR BACKFLOW PREVENTION DEVICE | | | PERMITS | | | | | | EFFECTIVE DATE: JANUARY 4TH, 2016 | | | | | | THE PERMIT APPLICATION SHALL BE SUBMITTED WITH THE | | | FOLLOWING DOCUMENTATION: | | | | | | 1) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR | | | THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE | | | DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK | | | SECTION ON THE PERMIT APPLICATION. | | | | | | 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE. | | | | | | 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF | | | SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES. | | | 4) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO | | | CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE | | | CITY?S REQUIREMENTS. | | | 5) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED | | | IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND | | | CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES | | | DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH | | | PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO | | | ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE | | | DEVICE. | | | NOTE: THE PERMIT CARD AND MANUFACTURER?S SPECIFICATIONS | | | SHALL BE ON THE JOBSITE FOR INSPECTION. | | | PLEASE REFER TO THE ATTACHED DOCUMENT FOR INFORMATION | | | REGARDING THE CITY OF WEST PALM BEACH APPROVED | | | CONTRACTOR?S LIST FOR CERTIFYING / RECERTIFYING | | | BACKFLOW DEVICES. | | | THE ESTIMATED REVIEW TIME FOR THESE PERMITS IS | | | APPROXIMATELY 72 HOURS. | | | THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL | | | MANUAL CAN BE FOUND AT : | | | HTTP://WPB.ORG/UTILITIES/BACKFLOW | | | UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS: | | | WWW.USC.EDU/DEPT/FCCCHR | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-06-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-06-23 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-06-23 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2016-06-23 14:15:20 | 1ST REVIEW | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | | | | PLUMBING COMMENTS: | | | | | | 1. WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE | | | FACILITIES SHALLL BE PROVIDED FOR EACH SEX.BATHROOM | | | FACILITIES ARE NOT REQUIRED ON THE SECOND FLOOR YOU CAN | | | PROVIDE SEPARATE FACILITIES ON FORTH FLOOR TO COMPLY | | | WITH THIS CODE . PER BC PL SEC.403.2 | | | | | | 2. SHT. A-1 SHOWS A BATHROOM ON THIRD FLOOR SHT.-.03 | | | PLUMBING FIXTURE REQUIREMENTS SHOWS A BATHROOM ON THE | | | THIRD FLOOR . THE REST OF THE PLAN SHOWS BATHROOMS ON | | | THE SECOND AND FORTH FLOORS PLEASE CLARIFY. PER PB | | | AMEND. TO FBC SEC. 107.2.1 | | | | | | 3. SHOW CLEAR FLOOR SPACE FOR WATER CLOSETS SHALL | | | COMPLY WITH. FBC ACC 604.3.1 SIZE. | | | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE | | | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED | | | PERPENDICULAR FROM THE REAR WALL. | | | | | | 4. SHOW CLEAR FLOOR SPACE FOR WALL HUNG LAVATORIES | | | SHALL COMPLY WITH FBC ACC 606.2 CLEAR FLOOR SPACE. | | | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR | | | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 5. SHOW CLEAR FLOOR SPACE FOR WATER FOUNTAIN SHALL | | | COMPLY WITH FBC ACC 602.2 CLEAR FLOOR SPACE. | | | UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH | | | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 6. DOOR SWING IN BATHROOM S SHALL COMPLY WITH FBC ACC | | | 603.2.3 DOOR SWING. | | | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR | | | CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE | | | PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. | | | EXCEPTIONS: | | | 2. WHERE THE TOILET ROOM OR BATHING ROOM IS FOR | | | INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH | | | 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE | | | DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE | | | CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY | | | FIXTURE. | | | | | | 7. TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC | | | 604.7 DISPENSERS. | | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | | THE CENTERLINE OF THE DISPENSER. | | | | | | 8. GRAB BARS SHAL BE MEASURED TO THE TOP OF THE | | | GRIPPING SURFACE TO FINISHED FLOOR NOT FROM THE CENTER | | | OF THE BAR. PER FBC ACC 609.4 | | | | | | 9. CIVIL PLAN SHOWS A 1IN WATER SERVICE SHT. P SHOWS AN | | | 11/4IN WATER SERVICE PLEASE CLARIFY. PER PB AMEND. TO | | | FBC SEC. 107.2.1 | | | | | | 10. PROVIDE MANUFACTURE SPECIFICATIONS FOR TANKLESS | | | HEATERS AND ELEVATOR SUMP PIT OIL SMART PUMP. PER PB | | | AMEND. TO FBC SEC. 107.2.1 | | | | | | 11. SHOW ROOF TOP HOSE BIBS ON RISER DIAGRAM AND PLAN | | | VIEW. PER PB AMEND. TO FBC SEC. 107.2.1 | | | | | | 12. PROVIDE SLOPE OF HORIZONTAL STORM DRAIN SHALL | | | COMPLY WITH FBC PL TABLE 1106.3 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
4 |
Status |
P |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-12-15 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-12-15 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
F |
Date |
2016-11-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-11-04 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-10-31 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2016-11-04 14:14:11 | THRESHOLD BUILDING/ BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16060181 | | | ADD: 1301 MERCER AVE. | | | CONT: STOR-ALL CONSTRUCTION | | | TEL: 561-966-0056 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2ND REVIEW | | | DATE: FRI. NOV. 04/ 2016 | | | ACTION: DENIED | | | | | | 2) THIS BUILDING BEING A 5 STORY BUILDING IS CONSIDERED | | | A THRESHOLD BUILDING. / FL S. S. 553.71(7) THRESHOLD | | | BUILDING MEANING ANY BUILDING WHICH IS GREATER THAN (3) | | | STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY | | | OCCUPANCY CLASSIFICATION AS DENIED IN THE FLORIDA | | | BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND | | | AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. | | | | | | 2A)2ND REQUEST FOR A WRITTEN THRESHOLD INSPECTION PLAN, | | | IT WAS NOT INCLUDED IN THE SUBMITTED DOCUMENTS NOR PART | | | OF THE STRUCTURAL NOTES ON SHEETS SS0.0 & S0.1. | | | 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING | | | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | 2B)SEMI-COMPLIED. THRESHOLD INSPECTION FORMS. SHEET 3OF | | | 6 THE SPECIAL INSPECTOR D. MARK LEBLANC P.E. HAS SIGNED | | | ON AS THE JOBSITE INSPECTOR. WITHIN THE SUBMITTED | | | THRESHOLD INSPECTION FORMS THERE ARE DOCUMENTS FOR | | | BRETT S ROSE BN5798, DOUGLAS JOSEPH RICHARD BN6661 AND | | | PEDRO LUIS BOURG BN4952. IF THESE (3) INSPECTORS ARE | | | GOING TO DO JOBSITE INSPECTIONS UNDER YOUR DIRECTION, | | | THEN EACH OF THESE INSPECTORS WILL NEED TO SIGN PAGE 3 | | | OF 6 FOR JOBSITE INSPECTORS. | | | 1ST ROUND COMMENTS. THRESHOLD INSPECTOR: WPB AMENDMENT | | | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT | | | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS | | | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE | | | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE | | | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT | | | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO | | | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT | | | ISSUANCE WILL TAKE PLACE. | | | 2C) COMPLIED. THRESHOLD BLDG., STATEMENT/ 633 FLORIDA | | | STATUTE. | | | 2D) NOT REQUIRED. 110.3.7.4.3 ALL SHORING AND RESHORING | | | PROCEDURES, PLANS AND DETAILS.. | | | 2E)SEMI-COMPLIED. THE ONLY INSPECTOR THAT HAS NOT | | | WORKED IN THE THRESHOLD PROGRAM IN THE CITY OF WEST | | | PALM BEACH IS PEDRO LUIS BOURG. REQUIRED RESUME? HAS | | | NOT BEEN SUBMITTED. | | | 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL | | | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL | | | OR HIS DESIGNEE WILL REVIEW THE RESUME' | | | | | | 2F) COMPLIED. CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 2G) SEMI- COMPLIED. THREE SETS OF PLANS SUBMITTED, IN | | | AT LEAST ONE SET OF PLANS THERE ARE MISSING PLANS, | | | SHEETS : A-2.1, A-2.2, A-2.3, A-3.1, A-3.2, A-3.3 & | | | A-3.4. | | | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 2H)NOTICE ONLY!!! NO ACTION IS REQUIRED. PLEASE CALL | | | THE CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE | | | INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING | | | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT | | | THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF | | | JOB, NO INSPECTION ACTIVITY. | | | | | | 2I) NOTICE ONLY!!! NO ACTION IS REQUIRED. 109.3.6 | | | THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD | | | INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED | | | ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED | | | FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2016-08-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-08-16 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-08-16 |
Time |
07:25 |
Sent To |
|
|
| Notes |
| 2016-08-16 07:25:25 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16060181 | | | ADD: 1301 MERCER AVE. | | | CONT: STOR-ALL CONSTRUCTION | | | TEL: 561-966-0056 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2ND REVIEW | | | DATE: MON. JUNE 11/ 2016 | | | ACTION: DENIED | | | | | | | | | 2) THIS BUILDING BEING A 5 STORY BUILDING IS CONSIDERED | | | A THRESHOLD BUILDING. / FL S. S. 553.71(7) ?THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 2A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. | | | | | | 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.3.7.3 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S | | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS | | | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH | | | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND | | | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE | | | PLACE. WE NEED EITHER THE GENERAL CONTRACTOR OR THE | | | STRUCTURAL ENGINEERS E-MAIL ADDRESS TO FORWARD THE | | | REQUIRED THRESHOLD FORMS TO BE FILED OUT AND RETURNED | | | WITH THE NEXT REVIEW CYCLE. | | | | | | 2C) COMPLIED. W.P.B. AMENDMENT 110.3.7.4.4 SHEET A00.4 | | | & S0.0. | | | | | | 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL | | | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL | | | OR HIS DESIGNEE WILL REVIEW THE RESUME? BEFORE PERMIT | | | ISSUANCE. | | | | | | 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB | | | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | 110.3.7.5 NO ENFORCING AGENCY MAY ISSUE A BUILDING | | | PERMIT FOR CONSTRUCTION OF ANY THRESHOLD BUILDING | | | EXCEPT TO A LICENSED GENERAL CONTRACTOR, AS DEFINED IN | | | SECTION 489.105(3)(A), FLORIDA STATUTES, OR TO A | | | LICENSED BUILDING CONTRACTOR, AS DEFINED IN SECTION | | | 489.105(3)(B), FLORIDA STATUTES, WITHIN THE SCOPE OF | | | HER OR HIS LICENSE. | | | | | | 2F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF | | | DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT | | | ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE | | | PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN | | | E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU | | | MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE | | | PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE | | | OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO | | | PRINT MAYBE IN BLACK & WHITE.. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | 2G) 2ND REQUEST. 110.3.7.4.3 ALL SHORING AND RESHORING | | | PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE | | | ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND | | | RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED | | | AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | 2H) 2ND REQUEST. PLEASE CALL THE CITY OF WEST PALM | | | BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN | | | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 2I) 2ND REQUEST.109.3.6 THRESHOLD BUILDINGS, OPERATING | | | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT | | | THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING | | | PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2016-07-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-07-11 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-07-11 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2016-07-11 15:40:06 | SEE BUILDING COMMENT NUMBER 2. | | 2016-07-11 12:06:41 | SEE BUILDING COMMENTS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2017-01-04 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2017-01-04 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2017-01-04 |
Time |
13:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2016-10-20 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2016-10-20 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-10-20 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2016-08-01 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2016-08-01 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-08-01 |
Time |
14:49 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2016-07-27 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2016-07-27 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-07-27 |
Time |
16:09 |
Sent To |
M |
|
| Notes |
| 2016-07-27 16:12:34 | 7/27/16- FAILED | | | | | | FAILED | | | 1. LANDSCAPE PERMIT IS REQUIRED BEFORE PERMITS CAN BE | | | ISSUED. | | | | | | PASSED | | | 1. BIKE RACK MEETS REQUIREMENT | | | 2. ACKNOWLEDGEMENT ACCEPTED | | | | | | NATHAN WIRA | | | (561)822-1442 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-07-06 |
|
|
Cont ID |
|
| Sent By |
avann |
Date |
2016-07-06 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-07-06 |
Time |
16:44 |
Sent To |
E |
|
| Notes |
| 2016-07-06 16:46:05 | 7/6/16- FAILED | | | | | | 1. INCLUDE DETAIL FOR BICYCLE PARKING PAD MEETING | | | MINIMUM SPACING REQUIREMENTS. (72" LENGTH, 30" | | | SEPARATION BETWEEN RACKS, AND 24" FROM RACK TO EDGE OF | | | PAD.) PLEASE CONTACT ME IF YOU NEED THE INFORMATION | | | SHEETS FOR THE SPACING. | | | | | | 2. IN ACCORDANCE WITH RESOLUTION NO. 365-15, A | | | CROSS-ACCESS EASEMENT SHALL BE RECORDED ALLOWING FUTURE | | | ACCESS TO THE PROPERTY TO THE SOUTH. THIS EASEMENT WILL | | | NEED TO BE RECORDED, AND COPY PROVIDED TO THE PLANNING | | | DIVISION, PRIOR TO ISSUANCE OF A CERTIFICATE OF | | | OCCUPANCY (C.O.) FOR THE BUILDING. | | | | | | 3. SEPORATE LANDSCAPE PLAN REQUIRED. | | | | | | PLEASE CONTACT: | | | NATHAN WIRA | | | (561)822-1442 | | | [email protected] | | | |
|
|
|