Plan Review Details - Permit 16060181
Plan Review Stops For Permit 16060181
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-12-15 Cont ID  
Sent By jwitmer Date 2016-12-15 Time 15:42 Rev Time 0.00
Received By jwitmer Date 2016-12-15 Time 07:02 Sent To  
Notes
2016-12-15 14:43:48BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060181
 ADD: 1301 MERCER AVE.
 CONT: STOR-ALL CONSTRUCTION
 TEL: 561-966-0056
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: THURS. DEC. 15/ 2016
  
 ACTION: BUILDING PROVISO:
  
 1) ROOFING SUBMITTAL CARLISLE SURE-WELD TPO SINGLE PLY
 ROOF SYSTEM WAS SUBMITTED, SUB-SYSTEM SC-168 WAS
 HIGHLIGHTED WITH A PRESSURE OF -67.5 PSF/ 10 FOOT WIDE
 MATERIAL. F.I.E. FLORIDA INTERNATIONAL ENGINEERING
 SUBMITTAL FOR HIS FLORIDA APPROVAL AND SUB-SYSTEM
 LISTED ABOVE WAS NOT SIGNED AND SEALED BY AN ENGINEER.
 THE FRONT PAGE LIST FOR ZONES 2 & 3 NO GOOD. 2ND PAGE
 OF DOCUMENT INDICATES FOR ROOF ZONE 2 USE ? OF THE
 SHEET 60 INCHES AND SPACING OF FASTENERS AT 6 INCHES ON
 CENTER AND A 1.5 INCH OUTSIDE SEAM WELD. FOR ZONE 3 USE
 A 30 INCH WIDE SHEET AND FASTENERS AT 6 INCHES ON
 CENTER AND A 1.5 INCH OUTSIDE SEAM WELD. NOTE THE
 ENGINEERING SHEET DOES NOT PROVIDE FOR ZONES 2 & 3 WHAT
 THE NARROWER WIDTHS WILL BE GOOD FOR. RESUBMIT WITH
 SIGNED AND SEALED DOCUMENTATION AND ASSUMED PRESSURES
 FOR ZONES 2 & 3.
 NOTE 14 OF THIS PRODUCT APPROVAL SHEET ALSO INDICATES
 FOR THE ROOF TOP INSULATION ENGINEERING FOR ANCHORING
 OF THE TAPERED WILL ALSO BE REQUIRED FOR THE VARIOUS
 ROOF ZONES.
  
 2) ROOF TOP A/C RACK/ STAND WILL NEED TO TAKE INTO
 ACCOUNT THE THICKNESS OF THE ROOF TOP INSULATION FROM
 THE FINISHED ROOF DECK VERTICALLY TO THE LOWEST
 HORIZONTAL SUPPORT FOR THE A/C STAND AND ADD THE
 THICKNESS OF THE ROOF INSULATION TO FIGURE CLEAR
 WORKING HEIGHT IN ACCORDANCE WITH 2014 FBC-B TABLE
 1009.6.5.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-11-04 Cont ID  
Sent By jwitmer Date 2016-11-04 Time 14:12 Rev Time 0.00
Received By jwitmer Date 2016-10-31 Time 10:31 Sent To  
Notes
2016-11-04 14:12:14BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060181
 ADD: 1301 MERCER AVE.
 CONT: STOR-ALL CONSTRUCTION
 TEL: 561-966-0056
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: FRI. NOV. 04/ 2016
 ACTION: DENIED
  
 1) SEMI-COMPLIED. DOCUMENTATION FOR THE VALUE OF THE
 COST ASSOCIATED WITH THE BUILDING HAS BEEN AGREED WITH
 THE BUILDING OFFICIAL ROBERT BROWN. THE VALUE OF
 $8,597,303.00 ($78.19 SQ. FT.) WILL BE THE ASSESSED
 VALUE FOR THE BUILDING. PLEASE NOTE THE MECHANICAL,
 ELECTRICAL, PLUMBING AND ROOFING PERMIT VALUES ARE
 INCORPORATED INTO THE MASTER/ PRIME PERMIT. THERE WILL
 BE A $80.00 ADMINISTRATIVE FEE FOR THESE SUB-PERMITS IF
 THEY WERE NOT GENERATED AT THE ORIGINAL PERMIT
 SUBMITTAL TIME.
 ALL OTHER SUB-PERMITS ASSOCIATED WITH THIS BUILDING,
 LOW VOLTAGE, FIRE ALARM, FIRE SPRINKLER, ETC? PLEASE
 PROVIDE AN ITEMIZED LIST OF TYPE OF PERMIT AND VALUE OF
 THE CONTRACTS. PLEASE DEDUCT THESE VALUES FROM THE
 VALUE OF $8,597,303.00 THIS ADJUSTED VALUE WILL BE THE
 VALUE WE WILL USE ONCE THE UNKNOWNS ARE PROVIDED. THE
 BUILDING DEPARTMENT DOES NOT WANT TO DOUBLE DIP IN THE
 PERMIT FEES.
  
 2) THIS BUILDING BEING A 5 STORY BUILDING IS CONSIDERED
 A THRESHOLD BUILDING. / FL S. S. 553.71(7) THRESHOLD
 BUILDING MEANING ANY BUILDING WHICH IS GREATER THAN (3)
 STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY CLASSIFICATION AS DENIED IN THE FLORIDA
 BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND
 AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A)2ND REQUEST FOR A WRITTEN THRESHOLD INSPECTION PLAN,
 IT WAS NOT INCLUDED IN THE SUBMITTED DOCUMENTS NOR PART
 OF THE STRUCTURAL NOTES ON SHEETS SS0.0 & S0.1.
 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B)SEMI-COMPLIED. THRESHOLD INSPECTION FORMS. SHEET 3OF
 6 THE SPECIAL INSPECTOR D. MARK LEBLANC P.E. HAS SIGNED
 ON AS THE JOBSITE INSPECTOR. WITHIN THE SUBMITTED
 THRESHOLD INSPECTION FORMS THERE ARE DOCUMENTS FOR
 BRETT S ROSE BN5798, DOUGLAS JOSEPH RICHARD BN6661 AND
 PEDRO LUIS BOURG BN4952. IF THESE (3) INSPECTORS ARE
 GOING TO DO JOBSITE INSPECTIONS UNDER YOUR DIRECTION,
 THEN EACH OF THESE INSPECTORS WILL NEED TO SIGN PAGE 3
 OF 6 FOR JOBSITE INSPECTORS.
 1ST ROUND COMMENTS. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
 2C) COMPLIED. THRESHOLD BLDG., STATEMENT/ 633 FLORIDA
 STATUTE.
 2D) NOT REQUIRED. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS..
 2E)SEMI-COMPLIED. THE ONLY INSPECTOR THAT HAS NOT
 WORKED IN THE THRESHOLD PROGRAM IN THE CITY OF WEST
 PALM BEACH IS PEDRO LUIS BOURG. REQUIRED RESUME? HAS
 NOT BEEN SUBMITTED.
 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'
  
 2F) COMPLIED. CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2G) SEMI- COMPLIED. THREE SETS OF PLANS SUBMITTED, IN
 AT LEAST ONE SET OF PLANS THERE ARE MISSING PLANS,
 SHEETS : A-2.1, A-2.2, A-2.3, A-3.1, A-3.2, A-3.3 &
 A-3.4.
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2H)NOTICE ONLY!!! NO ACTION IS REQUIRED. PLEASE CALL
 THE CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 2I) NOTICE ONLY!!! NO ACTION IS REQUIRED. 109.3.6
 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3-14) COMPLIED.
 15)2ND REQUEST. THIS REVIEW F. I. E. ENGINEERING &
 TESTING LABS ROOF CALCULATIONS WERE TAKEN FOR AN
 EXPOSURE C. THE JOBSITE LOCATION IS AN EXPOSURE D. BOTH
 THE STRUCTURAL SHEETS AND ENGINEERING SHEETS FROM
 ORIGINAL COMMENT. THE ROOFING PRODUCT APPROVAL
 SUBMITTED FL -16730 GAF SINGLE PLY SYSTEM. NO
 SUB-SYSTEM WAS CIRCLED W/ ASSOCIATED PREUSSRES, MAY
 REQUIRE ENHANCED FASTENING.
  
 16) 11/09/2016 I SPOKE WITH TOMMY HOBGOOD ABOUT THE
 POSSIBILITY OF A STRUCTURE ONLY PERMIT. THE COMPONENTS
 AND CLADDING WOULD BE ABLE TO BROUGHT IN UNDER THE
 BUILDING PERMIT. DURING THIS TIME WE WOULD BE GETTING
 SHOP DRAWINGS FOR THE SECONDARY FRAMING MEMBERS FOR THE
 WALLS AND ROOF FRAMING MEMBERS,
  
 11/04/2016.TO DATE THERE HAS BEEN NO SHOP DRAWINGS,
 ELEVATIONS OR VIEW OF THE ROOF SHOWING THE SPACING
 BETWEEN THE STRUCTURAL STEEL COLUMNS AND BEAMS OR THE
 PURLINS AND GIRTS FOR ZONES 1,2,3 4 & 5. THIS WILL NEED
 TO BE ENGINEERED DRAWINGS SINCE THE GIRTS AND PURLINS
 ARE SECONDARY FRAMING MEMBERS OF THE BUILDING. SPACING
 OF THE GIRTS AND PURLINS IS CRITICAL TO THE REVIEW OF
 THE PRODUCT APPROVALS FOR COMPONENTS AND CLADDING. BOLT
 LAYOUT FOR THE ANCHORAGE OF THE VERTICAL STEEL COLUMNS
 TO THE FOUNDATIONS, AND CENTER TO CENTER OF COLUMNS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 BUILDING ENVELOPE
 STRUCTURAL CALCULATIONS (IF REQUIRED)
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
  
 17A) ENGINEERING CALCULATIONS REVISION # 6 MBCI METAL
 ROOF AND WALL SYSTEMS ENGINEERING REPORT IS NOT SIGNED
 NOR SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS.
  
 17B) ENGINEERING CALCULATIONS REVISION # 6 MBCI METAL
 ROOF AND WALL SYSTEMS ENGINEERING REPORT CONSISTING OF
 (8) PAGES WILL ALSO NEED TO SHOW COMPLIANCE WITH
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET.
  
 18) PLEASE PROVIDE SPAN CHARTS FOR THE TYPE OF DECKING
 THAT WILL BE INSTALLED ON FLOORS 2-5 AND ALLOWABLE
 LOADS. PLEASE ALSO SEE SHEETS S2.1-S2.5 THERE IS AN
 ALTERNATE USE OF DECKING MATERIAL UNDER NOTE # 1.
 PLEASE SEE 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION. NO ALTERNATES. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 19) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 20) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-16 Cont ID  
Sent By jwitmer Date 2016-08-16 Time 07:27 Rev Time 0.00
Received By jwitmer Date 2016-08-15 Time 10:55 Sent To  
Notes
2016-08-16 07:24:30BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060181
 ADD: 1301 MERCER AVE.
 CONT: STOR-ALL CONSTRUCTION
 TEL: 561-966-0056
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. JUNE 11/ 2016
 ACTION: DENIED
  
 1) 2ND REQUEST. BUILDING VALUATION. THE RESPONSE LETTER
 FROM STOR ALL CONSTRUCTION INDICATES FOR THIS BUILDING
 TYPE OF CONSTRUCTION YOU ARE BUILDING AT A PRICE OF $
 70.53 PER GROSS SQUARE FOOT. DOES THIS SQUARE FOOT
 PRICE INCLUDE STRUCTURAL, ELECTRICAL, PLUMBING,
 MECHANICAL, INTERIOR FINISHES, NORMAL SITE WORK
 (EXCAVATION AND BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. IF SO YOU MAY SUBMIT A
 LETTER TO THE BUILDING OFFICIAL ROBERT BROWN ASKING FOR
 A REDUCTION IN PERMIT FEES. PLEASE INCLUDE A PRICE
 ANALYSIS OF SIMILAR PROJECTS IN COST, SQUARE FOOT AREA,
 HEIGHT AND BUILDING TYPE FOR RECENT BUDGET PRICING OF
 SIMILAR PROJECTS IN THE SOUTH FLORIDA REGION.
  
 1ST ROUND REVIEW COMMENT. THE BUILDING VALUATION IS LOW
 FOR THE BUILDING TYPE AND OCCUPANCY. THE JUNE 2016 IIC
 TABLES LIST THE VALUE OF THIS PROJECT AT $9,880,466.00
 DOLLARS. 109,954 SQ. FT. X $89.86= $9,880,466.00.
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THIS BUILDING BEING A 5 STORY BUILDING IS CONSIDERED
 A THRESHOLD BUILDING. / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.3.7.3 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. WE NEED EITHER THE GENERAL CONTRACTOR OR THE
 STRUCTURAL ENGINEERS E-MAIL ADDRESS TO FORWARD THE
 REQUIRED THRESHOLD FORMS TO BE FILED OUT AND RETURNED
 WITH THE NEXT REVIEW CYCLE.
  
 THRESHOLD INSPECTOR FORMS E-MAILED TO:
 [email protected] 8/24/2016 2:10 PM.
  
 2C) COMPLIED. W.P.B. AMENDMENT 110.3.7.4.4 SHEET A00.4
 & S0.0.
  
 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME? BEFORE PERMIT
 ISSUANCE.
  
 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
 110.3.7.5 NO ENFORCING AGENCY MAY ISSUE A BUILDING
 PERMIT FOR CONSTRUCTION OF ANY THRESHOLD BUILDING
 EXCEPT TO A LICENSED GENERAL CONTRACTOR, AS DEFINED IN
 SECTION 489.105(3)(A), FLORIDA STATUTES, OR TO A
 LICENSED BUILDING CONTRACTOR, AS DEFINED IN SECTION
 489.105(3)(B), FLORIDA STATUTES, WITHIN THE SCOPE OF
 HER OR HIS LICENSE.
  
 2F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) 2ND REQUEST. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) 2ND REQUEST. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 2ND REQUEST.109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3-13) COMPLIED.
  
 14) 2ND REQUEST. INDEX SHEET INDICATES THERE ARE FIRE
 PROTECTION PLANS IN THE SETS OF DRAWINGS, NO PLANS.
 SHEET A-0.3 INDICATES THIS BUILDING IS TO BE FIRE
 SPRINKLERED AND TO TAKE A ONE STORY INCREASE. NO FIRE
 SPRINKLER PLANS WERE SUBMITTED. 105.3.1.2 NO PERMIT MAY
 BE ISSUED FOR ANY BUILDING CONSTRUCTION,(2) FIRE
 SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR ADDITION
 WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS
 50 OR MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR
 II OR CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521,
 FLORIDA STATUTES, MAY DESIGN A FIRE SPRINKLER SYSTEM OF
 49 OR FEWER HEADS AND MAY DESIGN THE ALTERATION OF AN
 EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION
 CONSISTS OF THE RELOCATION, ADDITION OR DELETION OF NOT
 MORE THAN 49 HEADS, NOTWITHSTANDING THE SIZE OF THE
 EXISTING FIRE SPRINKLER
 SYSTEM. ALSO REVIEW FLORIDA ADMINISTRATIVE CODE
 61G15-32.004
  
 15A) THE ROOFING PRODUCT APPROVAL SUBMITTED FL
 -14083R11A CARLISLE SYNTEC SYSTEMS, CARLISLE SURE WELD
 TPO SINGLE PLY ROOF SYSTEMS NOTED ON THE FRONT PAGE FOR
 SUB-SYSTEM SEE PAGE 18 & 24. PLEASE NOTE PAGE 18 THE
 SUB-SYSTEM HIGHLIGHTED SC-111 IS GOOD FOR -157.5 @ 10
 SQ. FT./ THE STRUCTURAL SHEET S0.1 THE VASD WIND CHART
 FOR ZONE # 3 @ 10 SQ. FT. SHOWS PRESSURES OF -163. THE
 SECOND ISSUE PAGE 24 HAD BEEN REMOVED BY MISTAKE WILL
 NEED TO KNOW WHICH SUB-SYSTEM IS TO BE USED IN ZONES 1
 OR 2? PLEASE INDICATE WHICH SUB-SYSTEMS TO IN INSTALLED
 IN WHICH ZONES.
  
 15B) PLEASE CLARIFY HIGHLIGHT/ CIRCLE THE PANELS TO BE
 INSTALLED. WIDTH, LENGTH IN SPANS AND ASSOCIATED
 PRESSURES FOR BOTH THE FLORIDA APPROVAL AS WELL AS THE
 MIAMI-DADE NOA. ADDITIONAL INFORMATION REQUIRED.
 107.2.1.3.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By jwitmer Date 2016-07-11 Time 15:39 Rev Time 0.00
Received By jwitmer Date 2016-07-11 Time 08:03 Sent To  
Notes
2016-07-11 15:39:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060181
 ADD: 1301 MERCER AVE.
 CONT: STOR-ALL CONSTRUCTION
 TEL: 561-966-0056
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. JUNE 11/ 2016
 ACTION: DENIED
  
 1) THE BUILDING VALUATION IS LOW FOR THE BUILDING TYPE
 AND OCCUPANCY. THE JUNE 2016 IIC TABLES LIST THE VALUE
 OF THIS PROJECT AT $9,880,466.00 DOLLARS. 109,954 SQ.
 FT. X $89.86= $9,880,466.00.
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THIS BUILDING BEING A 5 STORY BUILDING IS CONSIDERED
 A THRESHOLD BUILDING. / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2E) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'
  
 2F) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2G) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 3) SHEET S0.0. PROVIDES THE WIND DESIGN CRITERIA. THE
 EXPOSURE IS LISTED AS A ?C? EXPOSURE. EXPOSURES FOR THE
 BUILDING ARE TAKEN FOR THE WORST CASE SCENARIO. THERE
 IS OVER 5000 FEET OF WATER TO THE NORTH AND NNW MEETING
 THE DEFINITION OF EXPOSURE D. 1609.4 EXPOSURE CATEGORY.
 1609.4.3 EXPOSURE CATEGORIES.
 AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE
 WITH THE FOLLOWING: EXPOSURE D. EXPOSURE D SHALL APPLY
 WHERE THE GROUND SURFACE ROUGHNESS, AS DEFINED BY
 SURFACE ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION
 FOR A DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20
 TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER.
 EXPOSURE D SHALL ALSO APPLY WHERE THE GROUND SURFACE
 ROUGHNESS IMMEDIATELY UPWIND OF THE SITE IS B OR C, AND
 THE SITE IS WITHIN A DISTANCE OF 600 FEET (183 M) OR 20
 TIMES THE BUILDING HEIGHT, WHICHEVER IS GREATER, FROM
 AN EXPOSURE D CONDITION AS DEFINED IN THE PREVIOUS
 SENTENCE.
  
 4) WITH THE PRESSURES GIVEN ON SHEET S0.1 THE PRESSURES
 WILL BE HIGHER SEE THE 2014 FBC-B TABLE 1609.7(2)
 ADJUSTMENT FACTOR FOR BUILDING HEIGHT AND EXPOSURE,
 (?). 55FT./ EXPOSURE D ADJUSTMENT FACTOR OF 1.84.
 PRESSURES WILL NEED TO BE RECALCULATED.
  
 5) SHEET S0.1 THE CHART FOR COMPONENTS & CLADDING
 PRESSURES THERE ARE ROOF ZONES 1 FOR THE INTERIOR ZONE
 AND WHAT APPEARS TO BE TWO ZONE 3 CATEGORIES, NO
 PERIMETER ZONE # 2? ASCE 7-10 FIGURE 30.5.1 .
  
 6) SHEET S0.1 PLEASE PROVIDE THE COMPONENT AND CLADDING
 IN VULT AND IN VASD. ALL OF THE PRODUCT APPROVALS ARE
 IN VASD, THE INSPECTORS IN THE FIELD NEED THE PLANS IN
 VASD TO MATCH THE PRODUCT APPROVAL. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 7) PLEASE NOTE THERE IS NO DOOR SCHEDULE LISTED IN THE
 DRAWING INDEX AND ON SHEET A5.3 IN THE HARDWARE
 SCHEDULE NEITHER EXIT STAIR TOWER 1 OR 2 DOOR HARDWARE
 SHOW A FIRE RATING . SEE 2014 FBC-B 1009.3.1.2.
 STAIRWELL 4 STORIES AND MORE REQUIRE A 2 HR. FIRE
 RATING AND TABLE 716.5 REQUIRES 1 ? HOUR PROTECTIVES.
  
 8) SHEET A-1.1 SHOWS THE ELEVATOR MACHINE ROOM AND THE
 ELECTRICAL ROOM AS 2 HOUR FIRE RATING, AGAIN NO DOOR
 SCHEDULE, REQUIRES 1 ? HOUR PROTECTIVE FOR A 2 HOUR
 RATED WALL. 2014 FBC-B TABLE 716.5.
  
 9A) SHEETS A-4.5 & A-4.6 BOTH SHOW A SIDE VIEW OF THE
 STAIRWELLS. THE 1ST FLOOR OF THE STAIR IN BOTH
 STAIRWELLS DOES NOT SHOW COMPLIANCE WITH: 2014
 FBC-ACCESSIBILITY CODE 307.4 AND FIGURE 307.4.
  
 9B) BOTH SHEETS A-4.5 & A-4.6 SHOW THE RISE AND RUN OF
 THE STAIRS, BUT PLANS DO NOT INDICATE IF THE STAIRS ARE
 TO HAVE SOLID RISERS. FBC-B 101009.7.5.3.
  
 9C) SHEETS A-4.5 & A-4.6 NEITHER SHOW COMPLIANCE WITH
 FBC-B 905.4. LOCATION OF CLASS I STANDPIPE(1) IN EVERY
 REQUIRED STAIRWAY.
  
 10) SHEET A-1.1 THE ELEVATOR CAB DOES NOT INDICATE WITH
 STRETCHER REQUIREMENTS, SEE FBC-B 3002.4 ELEVATOR CARS
 TO ACCOMMODATE AMBULANCE STRETCHERS.
  
 11) SHEET A-4.5 DETAIL 4 INDICATES WHAT APPEARS TO BE A
 HYDRAULIC ELEVATOR, PLEASE PROVIDE COMPLIANCE WITH
 FBC-B 3011.1 ELECTROLYSIS PROTECTION FOR UNDERGROUND
 HYDRAULIC ELEVATOR CYLINDERS.
 12) BOTH A-1.6 AND M6 SHOWS ROOF TOP COMPRESSORS ON TOP
 OF A/C STANDS. PLEASE SUBMIT THE PRODUCT APPROVAL FOR
 THE ROOF TOP STANDS. PROVIDE ANCHORING FOR THE STAND AS
 WELL AS THE UNIT TO THE STAND. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(G) PRE-ENGINEERED A/C STANDS.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 13) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN PROFESSIONAL
 IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE FOR
 REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS PREPARED
 BY OTHERS, INCLUDING PHASED AND DEFERRED SUBMITTAL
 ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF THE
 BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 14) SHEET A-0.3 INDICATES THIS BUILDING IS TO BE FIRE
 SPRINKLERED AND TO TAKE A ONE STORY INCREASE. NO FIRE
 SPRINKLER PLANS WERE SUBMITTED. 105.3.1.2 NO PERMIT MAY
 BE ISSUED FOR ANY BUILDING CONSTRUCTION,(2) FIRE
 SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR ADDITION
 WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS
 50 OR MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR
 II OR CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521,
 FLORIDA STATUTES, MAY DESIGN A FIRE SPRINKLER SYSTEM OF
 49 OR FEWER HEADS AND MAY DESIGN THE ALTERATION OF AN
 EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION
 CONSISTS OF THE RELOCATION, ADDITION OR DELETION OF NOT
 MORE THAN 49 HEADS, NOTWITHSTANDING THE SIZE OF THE
 EXISTING FIRE SPRINKLER
 SYSTEM. ALSO REVIEW FLORIDA ADMINISTRATIVE CODE
 61G15-32.004
  
 15) THE ROOFING PRODUCT APPROVAL SUBMITTED FL -16730
 GAF SINGLE PLY SYSTEM. NO SUB-SYSTEM WAS CIRCLED W/
 ASSOCIATED PREUSSRES, MAY REQUIRE ENHANCED FASTENING.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-10-17 Cont ID  
Sent By vperez Date 2016-10-17 Time 09:25 Rev Time 0.00
Received By vperez Date 2016-10-17 Time 09:40 Sent To  
Notes
2016-10-17 09:42:02PROVISO:
  
 ONE SET MISSING SHEET E6, PLEASE INSERT PREVIOUS
 APPROVED SHEET FOR APPPROVAL
  
 VAL PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-29 Cont ID  
Sent By vperez Date 2016-07-29 Time 12:21 Rev Time 0.00
Received By vperez Date 2016-07-29 Time 12:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-25 Cont ID  
Sent By vperez Date 2016-06-25 Time 13:37 Rev Time 0.00
Received By vperez Date 2016-06-25 Time 11:56 Sent To  
Notes
2016-06-25 13:37:51INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL
 SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE WILL
 SUFFICE.
 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR FIRE PUMP AND ALL LOW VOLTAGE SYSTEMS TO INCLUDE
 BUT NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS, CCTV,
 PHONE AND DATA, SIGNAGE, WIRELESS SYSTEMS, CAR CHARGING
 STATIONS, ETC. A NOTE WILL SUFFICE.
 3. PLEASE LABEL RECEPTACLE IN WORK ROOM TO BE GFCI
 PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF SINK ALL TO
 BE GFCI. SEE E1 OFFICE AREA
 4. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL
 AVAILABLE FAULT CURRENT AT THE TRANSFORMERS. FBC
 107.3.5
 5. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5
 6. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC
 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS.
 7. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS
 FOR FEEDERS AND BRANCH CIRCUITS.
 8. ADDRESS FIRE, MECH AND PLUMBING REVIEWS REGARDING
 ELECTRICAL REQUIREMENTS. FBC 107.3.5
 9. LABEL 1000AMP MAIN TO BE GFCI PROTECTED PER NEC
 240.13
 10. PROVIDE PHOTOMETRICS FOR ALL AREAS TO SHOW MINIMUM
 LIGHTING LEVELS. FBC 107.3.5
 11. PROVIDE A NOTE AT THE RISER DIAGRAM FIRE PUMP
 CONTROLLER TO RATED FOR SERVICE ENTRANCE.
 12. SHOW LOCATION OF PANEL AC, AT ELECTRICAL ROOM
 LOCATION. PROVIDE A NOTE TO COMPLY WITH TAP RULES PER
 NEC 240.21B
 13. AT TRANSFORMER RATED 112.5 SIZE GROUNDING ELECTRODE
 CONDUCTOR PER NEC 250.66 TABLE/ 1/0CU.
 14. SHOW A GFCI RECEPTACLE AT THE ELEVATOR MACHINE
 ROOM/ ELEVATOR EQUIPMENT PER NEC 620.23. ALSO A
 DEDICATED BRANCH TO BE PROVIDED EXCLUSIVELY TO ROOM.
 CIRCUIT H-9 SHOWN FEEDING OTHER AREAS, CORRECT AND
 ADDRESS AT PANEL SCHEDULE ALSO.
 15. PROVIDE A NOTE TO COMPLY WITH FBC ENERGY
 CONSERVATION 2014- 50% OF RECEPTACLES TO BE
 AUTOMATICALLY CONTROLLED PER CODE SECTION FBC C405.7.
 SHOW COMPLIANCE.
 16. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2017-01-06 Cont ID  
Sent By Mgonzale Date 2017-01-06 Time   Rev Time 1.00
Received By mgonzale Date 2017-01-06 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2016-10-03 Cont ID  
Sent By Mgonzale Date 2016-10-03 Time   Rev Time 1.00
Received By mgonzale Date 2016-10-03 Time   Sent To I
Notes
2016-10-03 17:17:11FINAL COMMENTS THRU ENGINEERING.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-07-25 Cont ID  
Sent By mgonzale Date 2016-07-25 Time   Rev Time 1.00
Received By mgonzale Date 2016-07-25 Time   Sent To Z
Notes
2016-07-25 15:02:42PLEASE ADDRESS FIRE DEPT COMMENTS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-10-28 Cont ID  
Sent By pleduc Date 2016-10-28 Time   Rev Time 0.00
Received By pleduc Date 2016-10-27 Time 17:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-08-04 Cont ID  
Sent By wjolin Date 2016-08-04 Time 13:59 Rev Time 0.00
Received By wjolin Date 2016-08-04 Time 13:30 Sent To  
Notes
2016-08-04 13:59:231301 MERCER AVENUE
 PERMIT #16060181
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SHEETS FP-61G NOT SUBMITTED.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. FOR ISSUANCE
 OF A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF
 THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE
 PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR
 ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-17 Cont ID  
Sent By wjolin Date 2016-06-17 Time 16:19 Rev Time 0.00
Received By wjolin Date 2016-06-09 Time 09:51 Sent To  
Notes
2016-06-09 09:52:361301 MERCER AVENUE
 PERMIT #16060181
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ARE CONSTRUCTION TRAILERS PLANNED FOR THIS SITE?
 NOTE:THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION
 TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO
 "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION
 REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION
 TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND
 COMPLIANCE WITH THE FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK
 SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH
 AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 CIVIL: NO NEW OR EXISTING FIRE HYDRANTS INDICATED.
 PROVIDE REQUIRED FIRE HYDRANTS AND FIRE FLOW
 CALCULATIONS IN ACCORDANCE WITH NFPA 1 SECTION 18.4.
  
 **PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER
 MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE
 INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO
 CONSTRUCTION WORK.**
  
 CIVIL: PROVIDE AUTOTURN DRAWING FOR 47-FOOT LONG FIRE
 LADDER APPARATUS.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. FOR ISSUANCE
 OF A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF
 THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE
 PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR
 ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PER NFPA 101 SECTION 7.2.2.5.4 - STAIRWAY
 IDENTIFICATION: NEW ENCLOSED STAIRS SERVING THREE OR
 MORE STORIES AND EXISTING ENCLOSED STAIRS SERVING FIVE
 OR MORE STORIES SHALL COMPLY WITH (A) THROUGH (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS ?NO ROOF ACCESS? AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER ?M? OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER ?B?
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 SHEET A2.3: 5 STORY ELEVATOR SHAFT WALL IS SHOWN WITH A
 1-HOUR FIRE RESISTANCE RATING.
  
 SHEET A5.3: NON OF THE STAIR DOORS HAVE A FIRE
 RESISTANCE RATING.
  
 SHEET E-7: COULD NOT LOCATE THE FIRE SPRINKLER JOCKEY
 PUMP CONTROL PANEL.
  
 PER NFPA 1 SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE
 AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-01-06 Cont ID  
Sent By lmarchan Date 2017-01-06 Time 15:54 Rev Time 0.00
Received By lmarchan Date 2016-12-06 Time 09:26 Sent To  
Notes
2016-12-07 09:26:59C37
 **OVERFLOW OF PLANS IN C38**

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-07 Cont ID  
Sent By lmarchan Date 2016-12-07 Time 09:17 Rev Time 0.00
Received By lmarchan Date 2016-10-11 Time 11:03 Sent To  
Notes
2016-10-12 11:03:17C37

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-03 Cont ID  
Sent By cpuell Date 2016-10-03 Time 15:47 Rev Time 0.00
Received By cpuell Date 2016-07-26 Time 08:18 Sent To  
Notes
2016-07-26 08:20:03C37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-26 Cont ID  
Sent By ccole Date 2016-07-26 Time 08:13 Rev Time 0.00
Received By ccole Date 2016-06-10 Time 10:26 Sent To  
Notes
2016-06-13 10:26:58C37

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status N Date 2016-12-15 Cont ID  
Sent By jwitmer Date 2016-12-15 Time 09:07 Rev Time 0.00
Received By jwitmer Date 2016-12-15 Time 09:04 Sent To  
Notes
2016-12-15 09:07:37PALM BEACH COUNTY IMPACT FEES
 DATE RECEIVED: 10/11/2016
 RECEIPT NUMBER 2016-1011-235
 TRACKING NUMBER MU-2016-024774-0000
 TOTAL FEES $62,279.87
  
 PLAN REVIEWER: J. WITMER

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2016-11-04 Cont ID  
Sent By jwitmer Date 2016-11-04 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2016-11-04 Time 14:14 Sent To  
Notes
2016-11-04 14:15:05BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-10-31 Cont ID  
Sent By jwitmer Date 2016-10-31 Time 12:26 Rev Time 0.00
Received By jwitmer Date 2016-10-31 Time 11:08 Sent To  
Notes
2016-10-31 12:26:49P. B. C. IMPACT FEE OFFICE:
 TRACKING NO. MU-2016-024774-0000
 RECEIPT NO. 2016-1011-235
 FEES: $62,279.87
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-08-16 Cont ID  
Sent By jwitmer Date 2016-08-16 Time 07:25 Rev Time 0.00
Received By jwitmer Date 2016-08-16 Time 07:25 Sent To  
Notes
2016-08-16 07:26:15BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By jwitmer Date 2016-07-11 Time 08:03 Rev Time 0.00
Received By jwitmer Date 2016-07-11 Time 08:03 Sent To  
Notes
2016-07-11 08:03:50BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-12-15 Cont ID  
Sent By ccole Date 2016-12-15 Time 15:19 Rev Time 0.00
Received By ccole Date 2016-12-15 Time 14:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-10-21 Cont ID  
Sent By ccole Date 2016-10-21 Time 16:02 Rev Time 0.00
Received By ccole Date 2016-10-21 Time 16:02 Sent To  
Notes
2016-10-21 16:05:273RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16060181
 10/21/16
  
 THE PLANS HAVE BEEN FAILED AGAIN DUE TO THE PREVIOUS
 COMMENTS LISTED BELOW THAT HAVE NOT BEEN ADDRESSED.
 THE ENGINEER OF RECORD MUST CORRECT THE PLANS AND
 PROVIDE A WRITTEN RESPONSE NARRATIVE.
  
 1) COMMISSIONING OF THE AC SYSTEMS IS REQUIRED IN
 ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY
 CONSERVATION. SUBMIT A COMMISSIONING PLAN IN COMPLIANCE
 WITH C408.2.1 FBC-14 ENERGY CONSERVATION- (SEE SECTION
 C408.2.1 FBC-14 ENERGY CONSERVATION PRINTED BELOW).
  
 2) THE COMPLIANCE DATA FOR THE AC SYSTEMS (AC
 IDENTIFICATIONS, AND CAPACITIES) LISTED ON PAGE 6 OF
 THE ENERGY GAUGE PERFORMANCE SUBMITTAL DO NOT MATCH THE
 SCHEDULES ON SHEET M8.
  
 3) REFER TO SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION: THE CAPACITIES OF THE DAIKIN AC SYSTEMS
 SPECIFIED FOR THE 1ST- 4TH FLOOR WAREHOUSE AREAS ARE
 EXCEEDING THE CALCULATED LOADS SHOWN IN THE SIZING
 SUMMARRIES.
  
 C408.2.1 COMMISSIONING PLAN.
 A COMMISSIONING PLAN SHALL BE DEVELOPED BY A REGISTERED
 DESIGN PROFESSIONAL OR APPROVED AGENCY AND SHALL
 INCLUDE THE FOLLOWING ITEMS:
  
 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL
 BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING,
 INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF
 THE ACTIVITIES.
  
 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR
 SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO
 BE PERFORMED.
  
 3. FUNCTIONS TO BE TESTED, INCLUDING, BUT NOT LIMITED
 TO CALIBRATIONS AND ECONOMIZER CONTROLS.
  
 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED.
 AT A MINIMUM, TESTING SHALL AFFIRM WINTER AND SUMMER
 DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS.
  
 5. MEASURABLE CRITERIA FOR PERFORMANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-03 Cont ID  
Sent By ccole Date 2016-08-03 Time 16:19 Rev Time 0.00
Received By ccole Date 2016-08-03 Time 15:35 Sent To  
Notes
2016-08-03 16:25:272ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16060181
 8/3/16
  
 COMMENTS #1-4 FROM THE 1ST REVIEW STILL EXIST. I HAVE
 REPRINTED THEM BELOW WITH SOME MODIFICATIONS BASED ON
 THIS 2ND REVIEW.
  
 1) COMMISSIONING OF THE AC SYSTEMS IS REQUIRED IN
 ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY
 CONSERVATION. SUBMIT A COMMISSIONING PLAN IN COMPLIANCE
 WITH C408.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) THE COMPLIANCE DATA FOR THE AC SYSTEMS (AC
 IDENTIFICATIONS, AND CAPACITIES) LISTED ON PAGE 6 OF
 THE ENERGY GAUGE PERFORMANCE SUBMITTAL DO NOT MATCH THE
 SCHEDULES ON SHEET M8.
  
 3) ENERGY GAUGE SUBMITTAL, PAGE 2 CERTIFICATIONS: THE
 ARCHITECT OF RECORD MUST PROVIDE HIS REGISTRATION
 NUMBER ON THE PAGE.
  
 4) REFER TO SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION: THE CAPACITIES OF THE DAIKIN AC SYSTEMS
 SPECIFIED FOR THE 1ST- 4TH FLOOR WAREHOUSE AREAS ARE
 EXCEEDING THE CALCULATED LOADS SHOWN IN THE SIZING
 SUMMARRIES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-16 Cont ID  
Sent By ccole Date 2016-06-16 Time 08:54 Rev Time 0.00
Received By ccole Date 2016-06-16 Time 07:15 Sent To  
Notes
2016-06-16 10:38:451ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16060181
 6/16/16
  
 1) COMMISSIONING OF THE AC SYSTEMS IS REQUIRED IN
 ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY
 CONSERVATION. SUBMIT A COMMISSIONING PLAN IN COMPLIANCE
 WITH C408.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) THE COMPLIANCE DATA FOR THE AC SYSTEMS (AC
 IDENTIFICATIONS, AND CAPACITIES) LISTED ON PAGE 6 OF
 THE ENERGY GAUGE PERFORMANCE SUBMITTAL DO NOT MATCH THE
 SCHEDULES ON SHEET M8.
  
 3) ENERGY GAUGE SUBMITTAL, PAGE 2 CERTIFICATIONS: THE
 ARCHITECT OF RECORD MUST PROVIDE HIS SIGNATURE, SEAL,
 AND REGISTRATION NUMBER ON THE PAGE. THE OWNER MUST
 SIGN AND DATE.
  
 4) REFER TO SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION: THE CAPACITIES OF THE DAIKIN AC SYSTEMS
 ARE EXCEEDING THE CALCULATED LOADS SHOWN IN THE SIZING
 SUMMARRIES.
  
 5) SHEETS A-6.1- A-6.5: PROVIDE CEILING FINISH SYMBOLS
 IN THE LEGENDS. PLEASE NOTE THAT ACCESS FOR MAINTENANCE
 AND REPLACEMENT OF ABOVE CEILING AIR HANDLERS MUST BE
 PROVIDED PER SECTION 306.1. INDICATE REQUIRED ACDCESS
 PANELS ON THE PLANS WITH DIMENSIONS.
  
 6) M1- M5: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 RETURN AIR SYSTEMS OF THE AHU'S- SEE SECTION 606.2.1.
 REVISE THE PLAN TO SHOW THE LOCATIONS AND PROVIDE
 INSTALLATION DETAILS.
  
 7) M1- M5: PROVIDE CLEARANCE DISTANCE MEASUREMENTS FOR
 THE OUTDOOR AIR INTAKES AS REQUIRED BY SECTION 401.4.
  
 8) M1- M5: PROVIDE EQUIPMENT SCHEDULES AND SUBMITTALS
 (FL. PRODUCT APPROVALS AND/OR NOA'S) FOR THE EXHAUST
 OUTLET AND O/A INTAKE WALL CAPS- REFER TO SECTIONS
 401.5 AND 501.3.2.
  
 9) M7: THE AC MOUNTING DETAIL NEEDS TO BE CLARIFIED
 (MUCH OF THE PRINT IS ILLEGIBLE). PROVIDE A FL. PRODUCT
 APPROVAL AND/OR MIAMI-DADE NOA FOR THE STAND, AND
 PROVIDE THE WIND LOAD DESIGN CRITERIA PER SECTION 1609
 FBC-14 BUILDING.
  
 10) P1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR AHU-1.F
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-01-06 Cont ID  
Sent By gjohnson Date 2017-01-06 Time 09:42 Rev Time 0.00
Received By gjohnson Date 2017-01-06 Time 09:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-10-26 Cont ID  
Sent By gjohnson Date 2016-10-26 Time 12:18 Rev Time 0.00
Received By gjohnson Date 2016-10-26 Time 12:18 Sent To  
Notes
2016-10-26 12:54:042ND REVIEW
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE OVERFLOW SCUPPER THAT IS PART OF THE PRIMARY
 DRAIN COLLECTOR BOX DOES NOT COMPLY WITH FBC PL SEC
 1108. A TOTALLY SEPARATE SECONDARY "OVERFLOW DRAIN"
 WITH A SEPARATE OPENING IN PARAPET WALL IS REQUIRED.
 PER FBC PL SEC 1108.2 AND SHALL COMPLY WITH FBC SEC
 1503.4.2.1 -1503.7
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-08-23 Cont ID  
Sent By gjohnson Date 2016-08-23 Time 11:28 Rev Time 0.00
Received By gjohnson Date 2016-08-23 Time 11:28 Sent To  
Notes
2016-08-23 11:29:35GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS: 2ND REVIEW
  
 2ND REQUEST
  
 5. NOT COMPLIED SHOW CLEAR FLOOR SPACE FOR WATER
 FOUNTAIN SHALL COMPLY WITH FBC ACC 602.2 CLEAR FLOOR
 SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 SHT A4.4 SHOWS A PARALLEL APPROACH IT SHALL BE A
 FORWARD APPROACH.
  
 10.NOT COMPLIED PROVIDE MANUFACTURE SPECIFICATIONS FOR
 TANKLESS HEATERS AND ELEVATOR SUMP PIT OIL SMART PUMP.
 PER PB AMEND. TO FBC SEC. 107.2.1
 SHOW NOTE ON PLAN TO PROVIDE MANUFACTURE SPECS AND
 INSTILLATION GUIDES ON JOBSITE FOR INSPECTIONS.
  
 12.NOT COMPLIED PROVIDE SLOPE OF HORIZONTAL STORM DRAIN
 SHALL COMPLY WITH FBC PL TABLE 1106.3
 SHT. P1 YOU PROVIDED A NOTE REFERENCING THE TABLE BUT
 YOU DID NOT LIST WHICH ONE OUT OF THE THREE SLOPES WAS
 BEING USED.
  
 NEW COMMENTS
 1. THE FLOOR SINK FOR ELEVATOR SUMP PIT DRAINS IS NOT
 VENTED. PER 901.2.1 VENTING REQUIRED.
 TRAPS AND TRAPPED FIXTURES SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN
 THIS CHAPTER.
  
 2. SHT P8 INCLUDE THE FLOOR SINK ON YOUR NOTE FOR THE
 TRAP PRIMERS. PER WPB AMEND TO FBC 107.2.1
  
 3. THE LAVATORY FAUCETS IN THE BATHROOMS SHA HAVE A
 TEMPERATURE LIMITING DEVICE TO COMPLY WITH FBC PL 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
 607.1.1 TEMPERATURE LIMITING MEANS.
 A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE
 AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF
 COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR
 MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY
 TEMPERATURE AT FIXTURES.
  
 4. SHT. P4 SHOWS 1IN CW FROM 3RD FLOOR TO BATHROOMS SHT
 P8 WATER RISER SHOWS 3/4 FROM 3RD FLOOR TO BATHROOMS
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. THE SPOUT FOR THE EMERGENCY ROOF DRAIN SHALL
 DISCHARGE A MIN. OF 12IN FROM BUILDING. PER FBC 1503.7
  
 SEPARATE PERMIT REQUIRED FOR BACKFLOWS
  
 DOCUMENTATION REQUIRED FOR BACKFLOW PREVENTION DEVICE
 PERMITS
  
 EFFECTIVE DATE: JANUARY 4TH, 2016
  
 THE PERMIT APPLICATION SHALL BE SUBMITTED WITH THE
 FOLLOWING DOCUMENTATION:
  
 1) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE
 DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
  
 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE.
  
 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES.
 4) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO
 CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE
 CITY?S REQUIREMENTS.
 5) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED
 IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH
 PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO
 ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE
 DEVICE.
 NOTE: THE PERMIT CARD AND MANUFACTURER?S SPECIFICATIONS
 SHALL BE ON THE JOBSITE FOR INSPECTION.
 PLEASE REFER TO THE ATTACHED DOCUMENT FOR INFORMATION
 REGARDING THE CITY OF WEST PALM BEACH APPROVED
 CONTRACTOR?S LIST FOR CERTIFYING / RECERTIFYING
 BACKFLOW DEVICES.
 THE ESTIMATED REVIEW TIME FOR THESE PERMITS IS
 APPROXIMATELY 72 HOURS.
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL CAN BE FOUND AT :
 HTTP://WPB.ORG/UTILITIES/BACKFLOW
 UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS:
 WWW.USC.EDU/DEPT/FCCCHR
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-23 Cont ID  
Sent By gjohnson Date 2016-06-23 Time 13:25 Rev Time 0.00
Received By gjohnson Date 2016-06-23 Time 13:25 Sent To  
Notes
2016-06-23 14:15:201ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALLL BE PROVIDED FOR EACH SEX.BATHROOM
 FACILITIES ARE NOT REQUIRED ON THE SECOND FLOOR YOU CAN
 PROVIDE SEPARATE FACILITIES ON FORTH FLOOR TO COMPLY
 WITH THIS CODE . PER BC PL SEC.403.2
  
 2. SHT. A-1 SHOWS A BATHROOM ON THIRD FLOOR SHT.-.03
 PLUMBING FIXTURE REQUIREMENTS SHOWS A BATHROOM ON THE
 THIRD FLOOR . THE REST OF THE PLAN SHOWS BATHROOMS ON
 THE SECOND AND FORTH FLOORS PLEASE CLARIFY. PER PB
 AMEND. TO FBC SEC. 107.2.1
  
 3. SHOW CLEAR FLOOR SPACE FOR WATER CLOSETS SHALL
 COMPLY WITH. FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 4. SHOW CLEAR FLOOR SPACE FOR WALL HUNG LAVATORIES
 SHALL COMPLY WITH FBC ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 5. SHOW CLEAR FLOOR SPACE FOR WATER FOUNTAIN SHALL
 COMPLY WITH FBC ACC 602.2 CLEAR FLOOR SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6. DOOR SWING IN BATHROOM S SHALL COMPLY WITH FBC ACC
 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 EXCEPTIONS:
 2. WHERE THE TOILET ROOM OR BATHING ROOM IS FOR
 INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE
 CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY
 FIXTURE.
  
 7. TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 8. GRAB BARS SHAL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE TO FINISHED FLOOR NOT FROM THE CENTER
 OF THE BAR. PER FBC ACC 609.4
  
 9. CIVIL PLAN SHOWS A 1IN WATER SERVICE SHT. P SHOWS AN
 11/4IN WATER SERVICE PLEASE CLARIFY. PER PB AMEND. TO
 FBC SEC. 107.2.1
  
 10. PROVIDE MANUFACTURE SPECIFICATIONS FOR TANKLESS
 HEATERS AND ELEVATOR SUMP PIT OIL SMART PUMP. PER PB
 AMEND. TO FBC SEC. 107.2.1
  
 11. SHOW ROOF TOP HOSE BIBS ON RISER DIAGRAM AND PLAN
 VIEW. PER PB AMEND. TO FBC SEC. 107.2.1
  
 12. PROVIDE SLOPE OF HORIZONTAL STORM DRAIN SHALL
 COMPLY WITH FBC PL TABLE 1106.3
  
  
  
  
  
  
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2016-12-15 Cont ID  
Sent By jwitmer Date 2016-12-15 Time 15:42 Rev Time 0.00
Received By jwitmer Date 2016-12-15 Time 15:42 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2016-11-04 Cont ID  
Sent By jwitmer Date 2016-11-04 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2016-10-31 Time 10:31 Sent To  
Notes
2016-11-04 14:14:11THRESHOLD BUILDING/ BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060181
 ADD: 1301 MERCER AVE.
 CONT: STOR-ALL CONSTRUCTION
 TEL: 561-966-0056
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: FRI. NOV. 04/ 2016
 ACTION: DENIED
  
 2) THIS BUILDING BEING A 5 STORY BUILDING IS CONSIDERED
 A THRESHOLD BUILDING. / FL S. S. 553.71(7) THRESHOLD
 BUILDING MEANING ANY BUILDING WHICH IS GREATER THAN (3)
 STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY CLASSIFICATION AS DENIED IN THE FLORIDA
 BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND
 AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A)2ND REQUEST FOR A WRITTEN THRESHOLD INSPECTION PLAN,
 IT WAS NOT INCLUDED IN THE SUBMITTED DOCUMENTS NOR PART
 OF THE STRUCTURAL NOTES ON SHEETS SS0.0 & S0.1.
 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B)SEMI-COMPLIED. THRESHOLD INSPECTION FORMS. SHEET 3OF
 6 THE SPECIAL INSPECTOR D. MARK LEBLANC P.E. HAS SIGNED
 ON AS THE JOBSITE INSPECTOR. WITHIN THE SUBMITTED
 THRESHOLD INSPECTION FORMS THERE ARE DOCUMENTS FOR
 BRETT S ROSE BN5798, DOUGLAS JOSEPH RICHARD BN6661 AND
 PEDRO LUIS BOURG BN4952. IF THESE (3) INSPECTORS ARE
 GOING TO DO JOBSITE INSPECTIONS UNDER YOUR DIRECTION,
 THEN EACH OF THESE INSPECTORS WILL NEED TO SIGN PAGE 3
 OF 6 FOR JOBSITE INSPECTORS.
 1ST ROUND COMMENTS. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
 2C) COMPLIED. THRESHOLD BLDG., STATEMENT/ 633 FLORIDA
 STATUTE.
 2D) NOT REQUIRED. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS..
 2E)SEMI-COMPLIED. THE ONLY INSPECTOR THAT HAS NOT
 WORKED IN THE THRESHOLD PROGRAM IN THE CITY OF WEST
 PALM BEACH IS PEDRO LUIS BOURG. REQUIRED RESUME? HAS
 NOT BEEN SUBMITTED.
 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'
  
 2F) COMPLIED. CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2G) SEMI- COMPLIED. THREE SETS OF PLANS SUBMITTED, IN
 AT LEAST ONE SET OF PLANS THERE ARE MISSING PLANS,
 SHEETS : A-2.1, A-2.2, A-2.3, A-3.1, A-3.2, A-3.3 &
 A-3.4.
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2H)NOTICE ONLY!!! NO ACTION IS REQUIRED. PLEASE CALL
 THE CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 2I) NOTICE ONLY!!! NO ACTION IS REQUIRED. 109.3.6
 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2016-08-16 Cont ID  
Sent By jwitmer Date 2016-08-16 Time 07:25 Rev Time 0.00
Received By jwitmer Date 2016-08-16 Time 07:25 Sent To  
Notes
2016-08-16 07:25:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060181
 ADD: 1301 MERCER AVE.
 CONT: STOR-ALL CONSTRUCTION
 TEL: 561-966-0056
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: MON. JUNE 11/ 2016
 ACTION: DENIED
  
  
 2) THIS BUILDING BEING A 5 STORY BUILDING IS CONSIDERED
 A THRESHOLD BUILDING. / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.3.7.3 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. WE NEED EITHER THE GENERAL CONTRACTOR OR THE
 STRUCTURAL ENGINEERS E-MAIL ADDRESS TO FORWARD THE
 REQUIRED THRESHOLD FORMS TO BE FILED OUT AND RETURNED
 WITH THE NEXT REVIEW CYCLE.
  
 2C) COMPLIED. W.P.B. AMENDMENT 110.3.7.4.4 SHEET A00.4
 & S0.0.
  
 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME? BEFORE PERMIT
 ISSUANCE.
  
 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
 110.3.7.5 NO ENFORCING AGENCY MAY ISSUE A BUILDING
 PERMIT FOR CONSTRUCTION OF ANY THRESHOLD BUILDING
 EXCEPT TO A LICENSED GENERAL CONTRACTOR, AS DEFINED IN
 SECTION 489.105(3)(A), FLORIDA STATUTES, OR TO A
 LICENSED BUILDING CONTRACTOR, AS DEFINED IN SECTION
 489.105(3)(B), FLORIDA STATUTES, WITHIN THE SCOPE OF
 HER OR HIS LICENSE.
  
 2F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) 2ND REQUEST. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) 2ND REQUEST. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 2ND REQUEST.109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By jwitmer Date 2016-07-11 Time 15:39 Rev Time 0.00
Received By jwitmer Date 2016-07-11 Time 08:03 Sent To  
Notes
2016-07-11 15:40:06SEE BUILDING COMMENT NUMBER 2.
2016-07-11 12:06:41SEE BUILDING COMMENTS.

Review Stop Z ZONING
Rev No 5 Status P Date 2017-01-04 Cont ID  
Sent By njwira Date 2017-01-04 Time 13:51 Rev Time 0.00
Received By njwira Date 2017-01-04 Time 13:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2016-10-20 Cont ID  
Sent By njwira Date 2016-10-20 Time 15:42 Rev Time 0.00
Received By njwira Date 2016-10-20 Time 15:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-08-01 Cont ID  
Sent By njwira Date 2016-08-01 Time 14:49 Rev Time 0.00
Received By njwira Date 2016-08-01 Time 14:49 Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2016-07-27 Cont ID  
Sent By njwira Date 2016-07-27 Time 16:09 Rev Time 0.00
Received By njwira Date 2016-07-27 Time 16:09 Sent To M
Notes
2016-07-27 16:12:347/27/16- FAILED
  
 FAILED
 1. LANDSCAPE PERMIT IS REQUIRED BEFORE PERMITS CAN BE
 ISSUED.
  
 PASSED
 1. BIKE RACK MEETS REQUIREMENT
 2. ACKNOWLEDGEMENT ACCEPTED
  
 NATHAN WIRA
 (561)822-1442
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2016-07-06 Cont ID  
Sent By avann Date 2016-07-06 Time 16:44 Rev Time 0.00
Received By njwira Date 2016-07-06 Time 16:44 Sent To E
Notes
2016-07-06 16:46:057/6/16- FAILED
  
 1. INCLUDE DETAIL FOR BICYCLE PARKING PAD MEETING
 MINIMUM SPACING REQUIREMENTS. (72" LENGTH, 30"
 SEPARATION BETWEEN RACKS, AND 24" FROM RACK TO EDGE OF
 PAD.) PLEASE CONTACT ME IF YOU NEED THE INFORMATION
 SHEETS FOR THE SPACING.
  
 2. IN ACCORDANCE WITH RESOLUTION NO. 365-15, A
 CROSS-ACCESS EASEMENT SHALL BE RECORDED ALLOWING FUTURE
 ACCESS TO THE PROPERTY TO THE SOUTH. THIS EASEMENT WILL
 NEED TO BE RECORDED, AND COPY PROVIDED TO THE PLANNING
 DIVISION, PRIOR TO ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY (C.O.) FOR THE BUILDING.
  
 3. SEPORATE LANDSCAPE PLAN REQUIRED.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  