Plan Review Details - Permit 16060097
Plan Review Stops For Permit 16060097
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-30 Cont ID  
Sent By rmcdouga Date 2016-06-30 Time 19:03 Rev Time 0.00
Received By rmcdouga Date 2016-06-30 Time 18:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By rmcdouga Date 2016-06-15 Time 10:21 Rev Time 0.00
Received By rmcdouga Date 2016-06-15 Time 10:09 Sent To E
Notes
2016-06-15 11:04:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC.
 THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE
 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC
 FIFTH EDITION.
  
 2) THE PLANS REFERENCE CHAPTER 4 OF THE FBC IN SEVERAL
 PLACES. THIS IS A PRIVATE SWIMMING POOL LOCATED AT A
 SINGLE FAMILY RESIDENCE, THEREFORE, THE FBC RESIDENTIAL
 APPLIES. SEE CHAPTER 42 FOR POOL ELECTRICAL
 REQUIREMENTS AND CHAPTER 45 FOR OTHER REQUIREMENTS.
  
 3) SUBMIT TWO COPIES OF THE REMOVEABLE CHILD BARRIER
 MANUFACTURER'S SPECIFICATIONS AND LISTING INFORMATION.
 FBC 107.2.1.3
  
 4) AN APPLICATION FOR THE POOL PLUMBING SUB IS REQUIRED
 BEFORE THE PERMIT WILL BE ISSUED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-30 Cont ID  
Sent By njwira Date 2016-06-30 Time 14:57 Rev Time 0.00
Received By mvaldes Date 2016-06-30 Time 16:04 Sent To  
Notes
2016-06-30 16:19:53ROUTED TO ROBBIE MCDOUGDAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-15 Time 17:23 Rev Time 0.00
Received By mvaldes Date 2016-06-15 Time 17:00 Sent To  
Notes
2016-06-15 17:30:10REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PLEASE COMPLY WITH BUILDING COMMENTS FOR FINAL
 APPROVAL
  
 - NEC 680.21(C) GFCI PROTECTION REQUIRED FOR OUTLETS
 SUPPLYING POOL PUMP MOTORS CONNECTED TO SINGLE PHASE
 120 V THROUGH 240 V BRANCH CIRCUITS, RATED 15 OR 20
 AMPS WHETHER BY RECEPTACLE OR BY DIRECT CONNECTION,
 SHALL BE PROVIDED WITH GROUND FAULT CIRCUIT INTERRUPTER
 PROTECTION FOR PERSONNEL.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-06-10 Cont ID  
Sent By tklarge Date 2016-06-10 Time 06:37 Rev Time 0.00
Received By tklarge Date 2016-06-10 Time 06:37 Sent To  
Notes
2016-06-10 06:39:00THERE IS NO GAS ASSOCIATED WITH THIS PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-30 Cont ID  
Sent By rmcdouga Date 2016-06-30 Time 19:03 Rev Time 0.00
Received By rmcdouga Date 2016-06-28 Time 11:47 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-15 Time 17:30 Rev Time 0.00
Received By mvaldes Date 2016-06-02 Time 13:55 Sent To  
Notes
2016-06-02 13:55:54ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-30 Cont ID  
Sent By rmcdouga Date 2016-06-30 Time 19:11 Rev Time 0.00
Received By rmcdouga Date 2016-06-30 Time 19:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-10 Cont ID  
Sent By tklarge Date 2016-06-10 Time 06:37 Rev Time 0.00
Received By tklarge Date 2016-06-10 Time 05:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-06-30 Cont ID  
Sent By rmcdouga Date 2016-06-30 Time 19:03 Rev Time 0.00
Received By njwira Date 2016-06-30 Time 14:57 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-03 Cont ID  
Sent By njwira Date 2016-06-03 Time 12:20 Rev Time 0.00
Received By njwira Date 2016-06-03 Time 12:20 Sent To B
Notes
2016-06-03 12:21:286/3/16- FAILED
 1. NEED TWO(2)COPIES OF A CERTIFIED SURVEY SHOWING
 WHERE THE POOL WILL BE LOCATED.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  