Plan Review Details - Permit 16060042
Plan Review Stops For Permit 16060042
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-17 Cont ID  
Sent By jwitmer Date 2016-06-17 Time 06:55 Rev Time 0.00
Received By jwitmer Date 2016-06-17 Time 06:27 Sent To  
Notes
2016-06-17 06:44:00BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060042
 ADD: 701 S. OLIVE AVE.
 CONT: CSI
 TEL: 561-420-2725
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JUNE 17/16
 ACTION: DENIED
  
 1) 2ND REQUEST. THIS REVIEW SUBMITTED TEST REPORTS FOR
 ECO SILENCER ACOUSTICAL UNDERLAYMENT. REPORT SUBMITTED
 FOR ASTM E-90 AND ASTM E-84 MISSING TEST DOCUMENTATION
 FOR
  
 1A) SUBMITTED: FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) MISSING: FBC-B 2010 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) MISSING: FLAME SPREAD- FBC-B 2010 603.1. EXCEPTION
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-08 Cont ID  
Sent By jwitmer Date 2016-06-08 Time 07:02 Rev Time 0.00
Received By jwitmer Date 2016-06-08 Time 06:31 Sent To  
Notes
2016-06-08 07:02:06 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060042
 ADD: 701 S. OLIVE AVE.
 CONT: CSI
 TEL: 561-420-2725
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 08/16
 ACTION: DENIED
  
 1) PLEASE NOTE ONLY (1) SOUND REPORT WAS SUBMITTED,
 STRUCTURE BORNE SOUND ASTM E 492, MISSING (2) MORE
 REPORTS:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION FBC-B 2010)
  
 1A) SUBMITTED: FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) MISSING: FBC-B 2010 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) MISSING: FLAME SPREAD- FBC-B 2010 603.1. EXCEPTION
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-22 Cont ID  
Sent By mvaldes Date 2016-06-22 Time 10:56 Rev Time 0.00
Received By mvaldes Date 2016-06-22 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-06-06 Cont ID  
Sent By mvaldes Date 2016-06-06 Time 10:18 Rev Time 0.00
Received By mvaldes Date 2016-06-06 Time 10:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-06-17 Cont ID  
Sent By wjolin Date 2016-06-17 Time 12:35 Rev Time 0.00
Received By wjolin Date 2016-06-17 Time 12:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-06-08 Cont ID  
Sent By wjolin Date 2016-06-08 Time 13:21 Rev Time 0.00
Received By wjolin Date 2016-06-08 Time 13:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-22 Cont ID  
Sent By mvaldes Date 2016-06-22 Time 10:56 Rev Time 0.00
Received By mvaldes Date 2016-06-16 Time 12:49 Sent To  
Notes
2016-06-16 12:49:29B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-08 Cont ID  
Sent By wjolin Date 2016-06-08 Time 13:21 Rev Time 0.00
Received By wjolin Date 2016-06-01 Time 08:48 Sent To  
Notes
2016-06-02 08:49:14B04

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-21 Cont ID  
Sent By ccole Date 2016-06-21 Time 10:59 Rev Time 0.00
Received By ccole Date 2016-06-21 Time 10:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By ccole Date 2016-06-06 Time 12:01 Rev Time 0.00
Received By ccole Date 2016-06-06 Time 12:01 Sent To  
Notes
2016-06-06 12:15:151ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #160600042
 6/6/16
  
 1) PROVIDE A MECHANICAL PLAN: SHOW THE REQUIRED
 ALTERATIONS TO THE EXISTING AC SYSTEM IN ORDER TO
 PROVIDE AC SUPPLY AIR TO, AND RETURN AIR FROM THE NEW
 DEN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  