Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-08 Cont ID  
Sent By tklarge Date 2016-06-08 Time 03:28 Rev Time 0.00
Received By tklarge Date 2016-06-08 Time 03:00 Sent To  
Notes
2016-06-08 03:04:45PLBG. APPROVED. SENT TO UTILITIES FOR REVIEW, TKL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-03 Cont ID  
Sent By tklarge Date 2016-06-03 Time 06:43 Rev Time 0.00
Received By tklarge Date 2016-06-03 Time 06:37 Sent To  
Notes
2016-06-03 06:43:51THE SPECIFICATION SHEETS THAT HAVE BEEN SUBMITTED DO
 NOT SHOW COMPLIANCE WITH THE FOLLOWING ITEMS:
  
 1) ALL BACKFLOW DEVICES MUST BE LEAD FREE.
  
 2) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR