Plan Review Details - Permit 16060011
Plan Review Stops For Permit 16060011
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2017-07-21 Cont ID  
Sent By jgomez Date 2017-07-21 Time 14:44 Rev Time 0.00
Received By jgomez Date 2017-07-21 Time 14:29 Sent To  
Notes
2017-07-21 14:33:1907/21/17 TALKED TO NEYITA (10:44AM). SHE SAID TO GO
 AHEAD WITH THE PROVISO. IT'S GOING TO BE OWNER-BUILDER.
 SHE WILL COME ON MONDAY WITH THE OWNER TO COMPLETE
 PERMIT APPLICATION.
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE ENERGY CALCULATIONS PRESCRIPTIVE FORM
 R402-2014 SUBMITTED:
 A) SPECIFY INSULATION FOR INTERIOR AND EXTERIOR SIDE OF
 MASONRY WALL AS REQUIRED BY SEE TABLE R402A.
 B) INFORMATION ON ITEM #9A2 NEEDS TO SPECIFY THE
 INTERIOR AND EXTERIOR MASONRY WALL INSULATION.
  
 2- ENGINEER TO PROVIDE DETAIL SHOWING INSULATION ON
 INTERIOR AND EXTERIOR OF MASONRY WALL.
 3- LABEL FOR WINDOWS AND DOORS WITH GLAZING SHOWING THE
 U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED.
  
  
  
  
  
  
 *******************************************************
 *******************************************************
 *******************************************************
 ********************************************
  
 NEYITA, REMEMBER THAT REVISION FEES WILL APPLY WITH THE
 PROVISO. ALSO, THE CONTRACTOR ON THE PERMIT APPLICATION
 IS "TBD". THE CONTRACTOR NEEDS TO APPLY IN ORDER TO
 PROCESS THE PERMIT.
 THANK YOU
  
 JULIO C. GOMEZ
 CITY OF WEST PALM BEACH
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
  
 FROM: NEYITA LEIVA
 TO: [email protected]
 DATE: 07/20/2017 05:17 PM
 SUBJECT: RE: 6205 WASHINGTON RD. PERMIT #16060011
  
 GRACIAS JULIO PORFAVOR DAME UN PROVISO QUE CREES???
  
 SENT FROM MY IPHONE
  
 ON JUL 20, 2017, AT 4:14 PM, [email protected] WROTE:
  
 YOUR WELCOME NEYITA,
 I TALKED TO EDGAR DUENAS REGARDING THESE COMMENTS AND
 LEFT A MESSAGE TO JORGE CABA SO WE CAN FINISH
 PROCESSING THIS PERMIT.
  
 JULIO C. GOMEZ
 CITY OF WEST PALM BEACH
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2017-07-20 Cont ID  
Sent By jgomez Date 2017-07-20 Time 08:39 Rev Time 0.00
Received By jgomez Date 2017-07-20 Time 08:15 Sent To  
Notes
2017-07-20 08:17:30RESIDENTIAL (R3) ADDITION/ALTERATION FIFTH BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT ITEMS REQUIRED BELOW MAY BE SUBMITTED LATER
 AFTER THE PERMIT IS ISSUED, BUT BEFORE INSPECTIONS TO
 AVOID DELAYS/CONFLICTS. REVISION FEES WILL APPLY.
 CONTRACTOR OR OWNER TO RESPOND IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME (IT MAY BE DONE BY
 RESPONDING TO THIS E-MAIL).
  
  
 1- ENERGY CALCULATIONS SUBMITTED:
 NOTE: NEW ENERGY CALCULATIONS WERE SUBMITTED. NEW
 ENERGY CALCULATIONS WERE DONE BY ANOTHER PREPARER AND
 THE FORM USED IS THE PRESCRIPTIVE FORM R402-2014. THE
 FOLLOWING COMMENTS APPLY TO THE NEW FORM SUBMITTED:
 A) IF USING THE PRESCRIPTIVE METHOD TO SHOW COMPLIANCE
 WITH THE ENERGY CODE, THEN ALL THE PRESCRIPTIVE
 REQUIREMENTS OF TABLE R402A MUST BE MET. THE PROPOSED
 ADDITION IS CONCRETE BLOCK. TABLE R402A REQUIRES A
 MINIMUM OF R-4 INSULATION ON THE INTERIOR OF THE WALL
 AND A MINIMUM OF R3 INSULATION ON THE EXTERIOR OF THE
 WALL. PLANS SUBMITTED DON'T COMPLY WITH THIS
 REQUIREMENTS. PERSON PREPARING THE ENERGY CALCULATIONS
 TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THIS REQUIREMENTS. ENGINEER OF RECORD TO
 REVISE PLANS AS WELL. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. REVISED FORM
 ONLY SHOWS INSULATION FOR THE EXTERIOR SIDE OF WALL.
 NEED INSULATION FOR BOTH INTERIOR AND EXTERIOR SIDE.
 AND NEED TO PROVIDE DETAIL SHOWING HOW INSTALLING THE
 INSULATION ON THE EXTERIOR SIDE OF THE MASONRY WALL.
  
 B) INFORMATION ON ITEM #9A2 NEEDS TO SPECIFY THE
 INSULATION FOR THE INTERIOR AND EXTERIOR SIDE OF THE
 MASONRY WALL. TABLE R402A. SEC. R101.5.1.1.1 FBC-ENERGY
 CONSERVATION.
  
 NOTE: LABEL FOR WINDOWS AND DOORS WITH GLAZING SHOWING
 THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED.
  
  
 ****PLEASE DO NOT STAPLE PRODUCT APPROVALS TO PLANS.
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REPLACE ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS WITH NEW DRAWINGS.
 SUBMIT OLD PLANS FOR REFERENCE TO EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTION, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-07-11 Cont ID  
Sent By jgomez Date 2017-07-11 Time 10:52 Rev Time 0.00
Received By jgomez Date 2017-07-11 Time 09:22 Sent To  
Notes
2017-07-11 09:41:07RESIDENTIAL (R3) ADDITION/ALTERATION FOURTH BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT ITEMS REQUIRED BELOW MAY BE SUBMITTED LATER
 AFTER THE PERMIT IS ISSUED, BUT BEFORE INSPECTIONS TO
 AVOID DELAYS/CONFLICTS. REVISION FEES WILL APPLY.
 CONTRACTOR OR OWNER TO RESPOND IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME (IT MAY BE DONE BY
 RESPONDING TO THIS E-MAIL).
  
 1- ENERGY CALCULATIONS SUBMITTED:
 NOTE: NEW ENERGY CALCULATIONS WERE SUBMITTED. NEW
 ENERGY CALCULATIONS WERE DONE BY ANOTHER PREPARER AND
 THE FORM USED IS THE PRESCRIPTIVE FORM R402-2014. THE
 FOLLOWING COMMENTS APPLY TO THE NEW FORM SUBMITTED:
 A) IF USING THE PRESCRIPTIVE METHOD TO SHOW COMPLIANCE
 WITH THE ENERGY CODE, THEN ALL THE PRESCRIPTIVE
 REQUIREMENTS OF TABLE R402A MUST BE MET. THE PROPOSED
 ADDITION IS CONCRETE BLOCK. TABLE R402A REQUIRES A
 MINIMUM OF R-4 INSULATION ON THE INTERIOR OF THE WALL
 AND A MINIMUM OF R3 INSULATION ON THE EXTERIOR OF THE
 WALL. PLANS SUBMITTED DON'T COMPLY WITH THIS
 REQUIREMENTS. PERSON PREPARING THE ENERGY CALCULATIONS
 TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THIS REQUIREMENTS. ENGINEER OF RECORD TO
 REVISE PLANS AS WELL. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) INFORMATION SHOWN ON ITEM #9A1 IS INCORRECT. WALL
 TYPE IS MASONRY NOT WOOD FRAME. REVISE AS REQUIRED TO
 MATCH PLANS AND TABLE R402A. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION.
  
 C) PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 A/C MANUFACTURER'S INFORMATION SHOWING THE SEER 20
 EQUIPMENT EFFICIENCY SPECIFIED ON ITEM #12 B. SEC.
 R103.2 FBC-ENERGY CONSERVATION.
  
 D) ITEM #14 SPECIFIED THAT HVAC CALCULATIONS ARE NOT
 ATTACHED. EQUIPMENT SIZING CALCULATIONS ARE REQUIRED.
 PROVIDE THE CALCULATIONS AND REVISE ITEM #14 AS
 REQUIRED. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 NOTE: LABEL FOR WINDOWS AND DOORS WITH GLAZING SHOWING
 THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED.
  
  
 ****PLEASE DO NOT STAPLE PRODUCT APPROVALS TO PLANS.
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REPLACE ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS WITH NEW DRAWINGS.
 SUBMIT OLD PLANS FOR REFERENCE TO EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTION, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-05-26 Cont ID  
Sent By jgomez Date 2017-05-26 Time 09:18 Rev Time 0.00
Received By jgomez Date 2017-05-26 Time 08:13 Sent To E
Notes
2017-05-26 08:20:18RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT ITEMS REQUIRED BELOW MAY BE SUBMITTED LATER
 AFTER THE PERMIT IS ISSUED, BUT BEFORE INSPECTIONS TO
 AVOID DELAYS/CONFLICTS. REVISION FEES WILL APPLY.
 CONTRACTOR OR OWNER TO RESPOND IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME (IT MAY BE DONE BY
 RESPONDING TO THIS E-MAIL). PERMIT WILL BE PROCESSED
 ONCE WE RECEIVE THE PLANS WITH THE COUNTY IMPACT FEES
 STAMP AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 1- THE NORTH ARROW ORIENTATION SHOWN IN ALL PLANS IS
 INCORRECT. SEE SURVEY AND REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT. THREE TIMES. RESPONSE LETTER
 STATES " COMMENT WAS ADDRESSED IN PREVIOUS REVISION.
 WHEN HOUSE IS ROTATED ABOUT 22 DEGREES CLOCKWISE THE
 NORTH ARROW ALSO ROTATES AN EQUIDISTANT AMOUNT. ". THIS
 IS THE TRUE, BUT THE PROBLEM IS THAT THE NORTH ARROW
 ORIENTATION WAS WRONG SINCE THE BEGINNING. SEE SURVEY
 AND REVISE AS REQUIRED.
  
 2- ENERGY CALCULATIONS SUBMITTED;
 A) REVISE WINDOWS INFORMATION ON PAGE 3 OF 4. WINDOWS
 AND DOORS WITH GLAZING ARE NOT VINYL FRAME. SEE PRODUCT
 APPROVALS AND REVISE AS REQUIRED. R101.5.1.1.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. RESPONSE LETTER STATES "THIS
 COMMENT WAS ADDRESSED IN THE PREVIOUS REVISION.
 MECHANICAL PLAN REVIEWER APPROVED IT AND PASSED ITS
 REVISION." MECHANICAL PLAN REVIEWER APPROVED THE
 MECHANICAL PLAN AND EQUIPMENT LOAD CALCULATIONS. THE
 ENERGY CALCULATIONS WERE APPROVED BY ME WITH THE
 CONDITION THAT WINDOW MATERIAL IS REVISED.
  
 NOTE: LABEL FOR WINDOWS AND DOORS WITH GLAZING SHOWING
 THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED WHEN THE ENERGY
 CALCULATIONS ARE NOT USING THE SOFTWARE DEFAULT FACTOR
 FOR GLAZING.
  
  
 ****PLEASE DO NOT STAPLE PRODUCT APPROVALS TO PLANS.
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REPLACE ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS WITH NEW DRAWINGS.
 SUBMIT OLD PLANS FOR REFERENCE TO EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTION, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-11-30 Cont ID  
Sent By jgomez Date 2016-11-29 Time 18:42 Rev Time 0.00
Received By jgomez Date 2016-11-29 Time 18:36 Sent To  
Notes
2016-11-29 18:45:52RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTES:
 (A) COORDINATE WITH ZONING COMMENTS.
  
 (B) BUILDING REVIEW MAY BE APPROVED WITH PROVISO.
 PROVISO MEANS THAT ITEMS REQUIRED BELOW MAY BE
 SUBMITTED LATER AFTER THE PERMIT IS ISSUED, BUT BEFORE
 INSPECTIONS TO AVOID DELAYS/CONFLICTS. REVISION FEES
 WILL APPLY. CONTRACTOR OR OWNER TO RESPOND IN WRITING
 IF PROVISO OPTION IS PREFERRED AT THIS TIME.
  
  
 1- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOMS,
 INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC. R315
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE:
 ELECTRICAL PLANS ONLY SHOW CARBON MONOXIDE ALARM FOR
 THE ADJACENT BEDROOM. THERE ARE MORE BEDROOMS IN THIS
 HOUSE. NEED TO PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH BEDROOM.
  
 2- THE NORTH ARROW ORIENTATION SHOWN IN ALL PLANS IS
 INCORRECT. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 3- ENERGY CALCULATIONS SUBMITTED;
 A) REVISE WINDOWS INFORMATION ON PAGE 3 OF 4. WINDOWS
 AND DOORS WITH GLAZING ARE NOT VINYL FRAME. SEE PRODUCT
 APPROVALS SUBMITTED AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS WITH GLAZING SHOWING
 THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED WHEN THE ENERGY
 CALCULATIONS ARE NOT USING THE SOFTWARE DEFAULT FACTOR
 FOR GLAZING.
  
  
 ****PLEASE DO NOT STAPLE PRODUCT APPROVALS TO PLANS.
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REPLACE ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS WITH NEW DRAWINGS.
 SUBMIT OLD PLANS FOR REFERENCE TO EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTION, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-03 Cont ID  
Sent By jgomez Date 2016-08-01 Time 18:36 Rev Time 0.00
Received By jgomez Date 2016-08-01 Time 18:15 Sent To M
Notes
2016-07-29 18:39:50RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. THE VALUATION WAS UPDATED TO $60,605. THE
 PERMIT FEE BALANCE IS $1569.47.
  
 3- SHEET S.P 1:
 A) THE COMPONENTS AND CLADDING DESIGN PRESSURES SHOWN
 ON THE DESIGN CRITERIA ARE TOO LOW. THEY DO NOT
 CORRESPOND TO EXPOSURE "C". REVISE AS REQUIRED. SEC.
 R301.2.1.4 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) ALTERATION LEVEL SPECIFIED ON THE DESIGN CRITERIA IS
 NOT ALTERATION LEVEL LL. THIS IS AN ADDITION. REVISE AS
 REQUIRED. SEC. 507 FBC-EXISTING BUILDING, 5TH EDITION
 (2014).
  
 4- REVISE COLUMN & BEAM SCHEDULE ON SHEET A-1. SIZE OF
 COLUMN C-1 IS NOT CLEAR. WHERE IS THE DIMENSION OF 16"
 TAKEN FOR THE 8" X 8" COLUMN?. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 5- SHEET A-2: IDENTIFY THE ROOMS THAT ARE ADJACENT TO
 THE ADDITION. IF THERE ARE ANY BEDROOMS ADJACENT TO THE
 ADDITION, THEN NEED TO SHOW COMPLIANCE WITH THE EGRESS
 REQUIREMENTS. SPECIFY WINDOWS TYPE AND SIZE TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS. SEC. 701.2
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 6- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOMS,
 INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC. R315
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 7- SHEET A-4: REVISE THE BOTTOM CORD LIVE LOAD
 SPECIFIED ON THE ROOF TRUSS DESIGN LOAD SHOWING
 COMPLIANCE WITH THE NOTES "A" AND "B" OF TABLE R301.5
 FBC-RESIDENTIAL. NOTE: COORDINATE WITH TRUSS DRAWINGS
 SUBMITTED.
  
 8- THE NORTH ARROW ORIENTATION SHOWN IN ALL PLANS IS
 INCORRECT. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 9- ENERGY CALCULATIONS SUBMITTED;
 A) OWNER/AGENT TO CERTIFY AND DATE AT BOTTOM OF FORM
 SUBMITTED AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) COMPLETE ALL THE INFORMATION ON TOP OF FORM
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 C) REVISE THE ATTIC VENT RATIO SHOWN ON PAGE 2 OF 4.
 CODE REQUIRES 1/150 RATIO. SEE SEC. R806.2
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 D) THERE ARE NO INSULATED DOORS IN THE ADDITION. SEE
 PLANS AND REVISE AS REQUIRED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 E) THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T
 MATCH INFORMATION SHOWN ON THE PLANS FOR THE ADDITION.
 SEE WINDOW ORIENTATION AND NUMBER OF WINDOWS SHOWN ON
 PLANS FOR THE ADDITION AND REVISE. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 F) THE WINDOWS OVERHANG SEPARATION SHOWN ON PAGE 3 OF 4
 DOESN'T MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 G) PROVIDE THE INSPECTION CHECKLIST AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 H) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS WITH GLAZING SHOWING
 THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED WHEN THE ENERGY
 CALCULATIONS ARE NOT USING THE SOFTWARE DEFAULT FACTOR
 FOR GLAZING.
  
 10- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING
 AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 MECHANICALLY FASTENED, THEN SPECIFY SCREW OR NAIL
 TYPE/SIZE AND NUMBER OF SCREWS/NAILS PER TILE. IF
 SPECIFYING ADHESIVE, THEN PROVIDE PRODUCT APPROVAL. SEE
 ROOF TILE PRODUCT APPROVAL FOR REFERENCE.
  
 11-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED FOR
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE ROOF TILE NOA FOR LISTED ADHESIVES.
  
 B) ROOF TILE: THERE ARE TWO DIFFERENT NOA'S SUBMITTED
 FOR TWO DIFFERENT MANUFACTURER'S . NOA 15-1102.04 AND
 NOA 12-0207.02. SUBMIT ONLY THE ROOF TILE NOA THAT IS
 GOING TO BE INSTALLED.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR LIST
 THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE
 SPECIFIED CONNECTOR.
  
 12- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 13- SHEET A-4: THE UPLIFT LOADS SHOWN ON THE ROOF
 FRAMING PLAN FOR THE TRUSS GIRDER A11G DON'T MATCH
 UPLIFT LOADS SHOWN ON THE TRUSS PACKAGE SUBMITTED. AND,
 THE CONNECTORS SPECIFIED ON THE CONNECTOR SCHEDULE
 DON'T MEET THE UPLIFT LOADS SPECIFIED FOR TRUSS GIRDER
 A11G ON TRUSS PACKAGE. REVISE AS REQUIRED. SEC. R301
 FBC-RESIDENTIAL.
  
 14- TRUSS PACKAGE SUBMITTED (NOTE: SUBMIT ONLY 2 COPIES
 OF TRUSS PACKAGE):
 A) TRUSS ENGINEER NEEDS TO PROVIDE ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 B) THE COVER PAGE IS MISSING THE INFORMATION OF THE
 STRUCTURAL ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-31.003
  
 C) STRUCTURAL ENGINEER OF RECORD TO REVIEW AND APPROVE
 COMPLETE TRUSS PACKAGE (LAYOUT AND INDIVIDUAL TRUSSES)
 PRIOR TO TO SUBMITTAL TO THIS OFFICE. SEC. 107.3.4.2
 CITY AMENDMENTS.
  
 ****PLEASE DO NOT STAPLE PRODUCT APPROVALS TO PLANS.
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REPLACE ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS WITH NEW DRAWINGS.
 SUBMIT OLD PLANS FOR REFERENCE TO EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTION, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-05-26 Cont ID  
Sent By jleahy Date 2017-05-26 Time 12:12 Rev Time 0.00
Received By jleahy Date 2017-05-26 Time 12:05 Sent To  
Notes
2017-05-26 10:10:16NEW REVISED DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-09 Cont ID  
Sent By vperez Date 2016-11-09 Time 11:56 Rev Time 0.00
Received By vperez Date 2016-11-09 Time 11:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-30 Cont ID  
Sent By albarran Date 2016-06-30 Time 11:11 Rev Time 0.00
Received By albarran Date 2016-06-30 Time 08:40 Sent To  
Notes
2016-06-30 11:11:571ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. PLEASE VERIFY THE INDICATED SCALE TO MATCH THE
 ACTUAL INTENDED. THIS MAY ALTER THE OUTLET PLACEMENT
 REQUIREMENTS AS PER NEC 210.52.
 2. CORRECT ELECTRICAL NOTE 2 TO SHOW THE CORRECT CODES.
 ALL WORK SHALL BE AS PER THE 5TH EDITION OF THE FBC
 2014 RATHER THAN THE SOUTH FLORIDA BLDG. CODE AS WELL
 AS THE 2011 EDITION OF THE NEC.
 3. CORRECT ELECTRICAL NOTE 7 AS ARTICLE 370 OF THE 2011
 NEC ADDRESSES CABLE BUS. THE ARTICLE ADDRESSING
 JUNCTION BOXES IS 314.
 4. PER NEC 406.12 ALL NEWLY INSTALLED RECEPTACLES IN
 DWELLING UNITS SHALL BE LISTED AS ?TAMPER-RESISTANT?.
 ADD THIS NOTE TO THE ELECTRICAL NOTES.
 5. PER NEC 250.94 THE INTER-SYSTEM BONDING TERMINAL
 SHALL BE AT THE SERVICE OR METER. CORRECT YOUR RISER
 DIAGRAM AS NOTED.
 6. PER NEC 210.70(A)(3) THE ATTIC LIGHT SWITCH SHALL BE
 ON A WALL ADJACENT TO THE POINT OF ENTRY. MAY I SUGGEST
 A SWITCH WITH A PILOT LIGHT TO INDICATE STATUS LOCATED
 IN A VISIBLE LOCATION.
 7. PER NEC 210.52(A) THE WALL BETWEEN THE CLOSET AND
 BATHROOM DOOR IS MISSING AN OUTLET.
 8. PER NEC 210.52(A) THE ROOM JUST OUTSIDE THE BEDROOM
 DOOR IS MISSING OUTLETS. MAY I SUGGEST A 3 WAY SWITCH
 FOR THE LIGHT AS WELL.
 9. PER NEC 680.73 THE POWER SOURCE OUTLET SHALL BE
 READILY ACCESSIBLE AND FACING THE OPENING IF
 APPLICABLE. THIS DEVICE SHALL BE NO MORE THAN 1 FOOT
 AWAY FROM THE OPENING.
 10. PER NEC 680.74 ALL METAL PARTS ASSOCIATED WITH OR
 IN CONTACT WITH THE CIRCULATING WATER SHALL BE BONDED
 WITH A #8 COPPER CONDUCTOR WHICH SHALL BE CONNECTED TO
 THE PUMP MOTOR AND FOR EQUIPOTENTIAL BONDING.
 11. PER NEC 440 PART II A DISCONNECT FOR THE MINI-SPLIT
 CONDENSING UNIT IS REQUIRED.
 12. PER FBC 314.3 YOU SHALL HAVE A SMOKE DETECTOR
 ?INSIDE? THE SLEEPING AREA AND ALSO IN THE IMMEDIATE
 AREA OUTSIDE. CORRECT THE DEVICE PLACEMENT AS INDICATED
 ON THE PLANS.
 13. PER FBC 314.3.1 YOU SHALL INSTALL SMOKE DETECTORS
 THROUGHOUT THE RESIDENCE AS REQUIRED FOR NEW
 CONSTRUCTION. IF ALREADY DONE SO, DISREGARD THIS
 COMMENT.
 14. PER FBC 315 IF THE RESIDENCE HAS AN ATTACHED GARAGE
 OR ANY FOSSIL FUEL BURNING APPLIANCE YOU SHALL INSTALL
 CARBON MONOXIDE DETECTORS AS INDICATED BY THIS SECTION.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-07-21 Cont ID  
Sent By jgomez Date 2017-07-21 Time 14:46 Rev Time 0.00
Received By jgomez Date 2017-07-21 Time 14:30 Sent To  
Notes
2017-07-21 14:31:05NEYITA, REMEMBER THAT REVISION FEES WILL APPLY WITH THE
 PROVISO. ALSO, THE CONTRACTOR ON THE PERMIT APPLICATION
 IS "TBD". THE CONTRACTOR NEEDS TO APPLY IN ORDER TO
 PROCESS THE PERMIT.
 THANK YOU
  
 JULIO C. GOMEZ
 CITY OF WEST PALM BEACH
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
  
 FROM: NEYITA LEIVA
 TO: [email protected]
 DATE: 07/20/2017 05:17 PM
 SUBJECT: RE: 6205 WASHINGTON RD. PERMIT #16060011
  
  
  
 GRACIAS JULIO PORFAVOR DAME UN PROVISO QUE CREES???
  
 SENT FROM MY IPHONE
  
 ON JUL 20, 2017, AT 4:14 PM, [email protected] WROTE:
  
 YOUR WELCOME NEYITA,
 I TALKED TO EDGAR DUENAS REGARDING THESE COMMENTS AND
 LEFT A MESSAGE TO JORGE CABA SO WE CAN FINISH
 PROCESSING THIS PERMIT.
  
  
  
  
 JULIO C. GOMEZ
 CITY OF WEST PALM BEACH
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
  
 HOW ARE WE DOING? PLEASE LET US KNOW BY TAKING AN
 ANONYMOUS SURVEY AT:
 HTTP://WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSE
 RVICES
  
  
  
 FROM: NEYITA LEIVA
 TO: [email protected]
 CC: EDGAR DUENAS ,
 [email protected]
 DATE: 07/20/2017 03:10 PM
 SUBJECT: RE: 6205 WASHINGTON RD. PERMIT #16060011
  
  
  
 THANK YOU JULIO
  
 SENT FROM MY IPHONE
  
 ON JUL 20, 2017, AT 2:31 PM, [email protected] WROTE:
  
 RESIDENTIAL (R3) ADDITION/ALTERATION FIFTH BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT ITEMS REQUIRED BELOW MAY BE SUBMITTED LATER
 AFTER THE PERMIT IS ISSUED, BUT BEFORE INSPECTIONS TO
 AVOID DELAYS/CONFLICTS. REVISION FEES WILL APPLY.
 CONTRACTOR OR OWNER TO RESPOND IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME (IT MAY BE DONE BY
 RESPONDING TO THIS E-MAIL).
  
  
 1- ENERGY CALCULATIONS SUBMITTED:
 NOTE: NEW ENERGY CALCULATIONS WERE SUBMITTED. NEW
 ENERGY CALCULATIONS WERE DONE BY ANOTHER PREPARER AND
 THE FORM USED IS THE PRESCRIPTIVE FORM R402-2014. THE
 FOLLOWING COMMENTS APPLY TO THE NEW FORM SUBMITTED:
 A) IF USING THE PRESCRIPTIVE METHOD TO SHOW COMPLIANCE
 WITH THE ENERGY CODE, THEN ALL THE PRESCRIPTIVE
 REQUIREMENTS OF TABLE R402A MUST BE MET. THE PROPOSED
 ADDITION IS CONCRETE BLOCK. TABLE R402A REQUIRES A
 MINIMUM OF R-4 INSULATION ON THE INTERIOR OF THE WALL
 AND A MINIMUM OF R3 INSULATION ON THE EXTERIOR OF THE
 WALL. PLANS SUBMITTED DON'T COMPLY WITH THIS
 REQUIREMENTS. PERSON PREPARING THE ENERGY CALCULATIONS
 TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THIS REQUIREMENTS. ENGINEER OF RECORD TO
 REVISE PLANS AS WELL. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. REVISED FORM
 ONLY SHOWS INSULATION FOR THE EXTERIOR SIDE OF WALL.
 NEED INSULATION FOR BOTH INTERIOR AND EXTERIOR SIDE.
 AND NEED TO PROVIDE DETAIL SHOWING HOW INSTALLING THE
 INSULATION ON THE EXTERIOR SIDE OF THE MASONRY WALL.
  
 B) INFORMATION ON ITEM #9A2 NEEDS TO SPECIFY THE
 INSULATION FOR THE INTERIOR AND EXTERIOR SIDE OF THE
 MASONRY WALL. TABLE R402A. SEC. R101.5.1.1.1 FBC-ENERGY
 CONSERVATION.
  
 NOTE: LABEL FOR WINDOWS AND DOORS WITH GLAZING SHOWING
 THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED.
  
  
 ****PLEASE DO NOT STAPLE PRODUCT APPROVALS TO PLANS.
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REPLACE ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS WITH NEW DRAWINGS.
 SUBMIT OLD PLANS FOR REFERENCE TO EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTION, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
 JULIO C. GOMEZ
 CITY OF WEST PALM BEACH
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
  
 HOW ARE WE DOING? PLEASE LET US KNOW BY TAKING AN
 ANONYMOUS SURVEY AT:
 HTTP://WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSE
 RVICES
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-07-20 Cont ID  
Sent By jgomez Date 2017-07-20 Time 09:00 Rev Time 0.00
Received By jgomez Date 2017-07-13 Time 14:28 Sent To  
Notes
2017-07-14 14:28:35JGOMEZ'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-07-11 Cont ID  
Sent By jgomez Date 2017-07-11 Time 10:59 Rev Time 0.00
Received By jgomez Date 2017-06-21 Time 13:30 Sent To  
Notes
2017-06-22 13:30:51RESUB ROUTED TO AWOOTEN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-26 Cont ID  
Sent By jleahy Date 2017-05-26 Time 12:13 Rev Time 0.00
Received By jleahy Date 2017-05-12 Time 13:18 Sent To  
Notes
2017-05-15 13:18:22R31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-30 Cont ID  
Sent By jgomez Date 2016-11-30 Time 18:49 Rev Time 0.00
Received By jgomez Date 2016-11-03 Time 09:29 Sent To  
Notes
2016-11-04 09:29:15R21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-05 Cont ID  
Sent By cpuell Date 2016-08-05 Time 09:57 Rev Time 0.00
Received By cpuell Date 2016-06-01 Time 16:05 Sent To  
Notes
2016-06-01 16:05:24R16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2017-07-11 Cont ID  
Sent By jgomez Date 2017-07-11 Time 10:57 Rev Time 0.00
Received By jgomez Date 2017-07-11 Time 10:57 Sent To  
Notes
2017-07-11 10:58:55$236.59 PAID. MU-2017-015224.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-05-26 Cont ID  
Sent By jgomez Date 2017-05-26 Time 10:11 Rev Time 0.00
Received By jgomez Date 2017-05-26 Time 10:10 Sent To  
Notes
2017-05-26 10:12:031- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-11-29 Cont ID  
Sent By jgomez Date 2016-11-29 Time 18:47 Rev Time 0.00
Received By jgomez Date 2016-11-29 Time 18:46 Sent To  
Notes
2016-11-29 18:47:421- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By jgomez Date 2016-08-02 Time 08:20 Rev Time 0.00
Received By jgomez Date 2016-08-02 Time 08:20 Sent To  
Notes
2016-08-02 08:20:321- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-11-29 Cont ID  
Sent By jvalido Date 2016-11-29 Time 17:00 Rev Time 0.00
Received By jvalido Date 2016-11-29 Time 16:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-04 Cont ID  
Sent By jvalido Date 2016-08-04 Time 16:44 Rev Time 0.00
Received By jvalido Date 2016-08-04 Time 16:06 Sent To  
Notes
2016-08-04 16:44:33CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 FLORIDA ENERGY CODE FBC 2014
  
 (1) FORM 405-2014 MUST BE COMPLETLY FILL ED OUT WITH
 ALL THE NECESSARY INFORMATION.
 (2) PROVIDE SIGNATURE OF "OWNER/AGENT" ON BOTH COPIES
 OF FORM 405-2014.
 (3) HEAT LOAD CALCULATIONS MUST BE COMPLETLY FILLED
 OUT. PROVIDE "JOB", "DATE", "PREPARED BY"
  
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-28 Cont ID  
Sent By tklarge Date 2016-11-28 Time 10:14 Rev Time 0.00
Received By tklarge Date 2016-11-28 Time 10:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-16 Cont ID  
Sent By gjohnson Date 2016-06-16 Time 15:07 Rev Time 0.00
Received By gjohnson Date 2016-06-16 Time 15:07 Sent To  
Notes
2016-06-16 15:18:15PLUMBING COMMENTS:
  
 1. VALUE OF JOB APPEARS LOW. PER WPB AMEND. TO FBC SEC.
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2.SANITARY PIPING ON FLAT PLAN DOES NOT MATCH RISER
 DIAGRAM PLEAS CLARIFY. PER WPB AMEND. TO FBC SEC.
 107.2.1
  
 3. HORIZONTAL DRY VENT ON SHOWER NOT ALLOWED. PER FBC
 PL SEC. P3104.3- P3104.4
  
 4. SHT. E-1 SHOWS HORIZONTAL DRY VENT NOT ALLOWED. PER
 FBC PL SEC. P3104.3- P3104.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-11-30 Cont ID  
Sent By jgomez Date 2016-11-30 Time 18:47 Rev Time 0.00
Received By jgomez Date 2016-11-30 Time 17:21 Sent To  
Notes
2016-11-30 18:49:48APPROVED PRODUCT APPROVALS:
  
 1- ROOF TILE UNDERLAYMENT NOA 14-0717.08.
  
 2- ROOF TILE NOA 15-1102.04.
  
 3- ROOF TILE ADHESIVE NOA 14-0805.01.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-08-03 Cont ID  
Sent By jgomez Date 2016-08-03 Time 18:58 Rev Time 0.00
Received By jgomez Date 2016-08-03 Time 18:58 Sent To  
Notes
2016-08-03 18:59:321-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED FOR
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE ROOF TILE NOA FOR LISTED ADHESIVES.
  
 B) ROOF TILE: THERE ARE TWO DIFFERENT NOA'S SUBMITTED
 FOR TWO DIFFERENT MANUFACTURER'S . NOA 15-1102.04 AND
 NOA 12-0207.02. SUBMIT ONLY THE ROOF TILE NOA THAT IS
 GOING TO BE INSTALLED.
  
 2- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2017-06-23 Time   Rev Time 0.00
Received By   Date 2017-06-23 Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2017-05-11 Cont ID  
Sent By   Date 2017-05-11 Time   Rev Time 0.00
Received By   Date 2017-05-11 Time   Sent To  
Notes
2017-05-11 10:37:07*******ZONING REVIEW**********
  
 PER THE ZONING ADMINISTRATOR, ANGELLA VANN, THE FRONT
 YARD OF THIS PROPERTY IS ON WASHINGTON ROAD. THEREFORE,
 THE ADDITION WILL BE PERMITTED WITH A 7.5 FOOT SETBACK.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-828-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2016-11-28 Cont ID  
Sent By Alana Date 2016-11-28 Time 15:21 Rev Time 0.00
Received By awooten Date 2016-11-28 Time 15:12 Sent To  
Notes
2016-11-28 15:19:49******ZONING FAILED********
  
 ACCORDING TO TODAY'S CODE, THE FRONT OF THE LOT IS THE
 PUBLIC STREET RIGHT-OF-WAY WHICH POSSESSES THE
 NARROWEST LENGTH. SO SANTA LUCIA AVENUE IS THE FRONT OF
 THIS PROPERTY, WHICH MAKES THE SOUTHERN SETBACK THE
 REAR SETBACK. THE REAR SETBACK BASED ON THE CODE FOR
 THIS DISTRICT IS 15 FEET OR 10% OF LOT DEPTH, WHICHEVER
 IS LESS. THE NEW ADDITION WOULD HAVE TO MEET A 9.6 FOOT
 REAR SETBACK.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 DEVELOPMENT SERVICES
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By awooten Date 2016-06-15 Time 13:41 Rev Time 0.00
Received By awooten Date 2016-06-15 Time 13:41 Sent To  
Notes
2016-06-15 13:55:45ACCORDING TO TODAY'S CODE, THE FRONT OF THE LOT IS THE
 PUBLIC STREET RIGHT-OF-WAY WHICH POSSESSES THE
 NARROWEST LENGTH. SO SANTA LUCIA AVENUE IS THE FRONT OF
 THIS PROPERTY, WHICH MAKES THE SOUTHERN SETBACK THE
 REAR SETBACK. THE REAR SETBACK BASED ON THE CODE FOR
 THIS DISTRICT IS 15 FEET OR 10% OF LOT DEPTH, WHICHEVER
 IS LESS. THE NEW ADDITION WOULD HAVE TO MEET THIS REAR
 SETBACK.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved