| 2016-06-16 12:57:38 | BUILDING PLAN REVIEW |
| | W.P.B. PERMIT NO.: 16051255 |
| | ADD: 1200 S. FLAGLER DR. |
| | CONTR: CONCRETE RESTORATION SERVICES |
| | TEL: 561-833-3573 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 6/16/16 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES THE WORK UNDER THE |
| | SCOPE OF THIS PERMIT LIST THE SITE ADDRESS AS 1200 S. |
| | FLAGLER DR. WHEREAS THE SPECIAL INSPECTOR AGREEMENT |
| | LIST THE ADDRESS AS 120 S. FLAGLER DR. PLEASE CORRECT |
| | THE DISCREPANCY IN THE ADDRESS. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE |
| | PROJECT. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) THIS BUILDING MEETS THE DEFINITION OF: THRESHOLD |
| | BUILDING F.S. 553.71 (7) |
| | ?THRESHOLD BUILDING? ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND HAS AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) UPDATE THE SPECIAL INSPECTOR AGREEMENT TO THE |
| | CORRECT ADDRESS. |
| | |
| | 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| | BUILDINGS, A SPECIAL INSPECTOR IS REQUIRED BY F.S. |
| | 553.79 (5) TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE |
| | FILLED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND |
| | RETURNED TO THIS OFFICE AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. CONTACT KEN |
| | CONRAD, MANAGER OF SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT MAY |
| | BE ISSUED. |
| | THE SPECIAL INSPECTOR FORMS SUBMITTED TO THE BUILDING |
| | DEPARTMENT ARE NOT COMPLETE, MISSING THE NOTARIZED |
| | SIGNATURES OF OWNER & CONTRACTOR. |
| | |
| | 2C) MISSING STATEMENT. THRESHOLD BUILDING, REQUIRED. |
| | W.P.B. AMENDMENT 110.3.7.4.4. ALL PLANS FOR THE |
| | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, ?TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | F.S.? |
| | |
| | 2D) NOT COMPLETED. FOR THE SPECIAL INSPECTOR & |
| | DESIGNATED JOB INSPECTORS - PLEASE PROVIDE A RESUME? OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECTS. THE RESUME? |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME?. AFTER THE RESUME? IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. |
| | |
| | 2E) DENIED. JOB INSPECTOR ? GUILLERMO PABRON. FBC |
| | 110.3.7.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL |
| | INSPECTOR TO CONDUCT THE MINIMUM STRUCTURAL INSPECTION |
| | OF THRESHOLD BUILDINGS REQUIRED BY THIS CODE, SECTION |
| | 553.73,FLORIDA STATUTES, WITHOUT DUPLICATIVE INSPECTION |
| | BY THE BUILDING DEPARTMENT. THE BUILDING OFFICIAL IS |
| | RESPONSIBLE FOR ENSURING THAT ANY PERSON CONDUCTING |
| | INSPECTIONS IS QUALIFIED AS A BUILDING INSPECTOR UNDER |
| | PART XII OF CHAPTER 468, FLORIDA STATUTES, OR CERTIFIED |
| | AS A SPECIAL INSPECTOR UNDER CHAPTER 471 OR 481, |
| | FLORIDA STATUTES. INSPECTIONS OF THRESHOLD BUILDINGS |
| | REQUIRED BY SECTION 553.79(5), FLORIDA STATUTES, ARE IN |
| | ADDITION TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | |
| | 2F) NOT COMPLETED. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 2G) NOT COMPLETED. NOTE FOR PAPER PLANS, 3 SETS OF |
| | DOCUMENTS ARE REQUIRED. |
| | |
| | 2H) 110.3.7.4.1 THE SPECIAL INSPECTOR, UPON COMPLETION |
| | OF THE BUILDING AND PRIOR TO THE ISSUANCE OF A |
| | CERTIFICATE OF OCCUPANCY OR COMPLETION, FILE A SIGNED |
| | AND SEALED STATEMENT WITH THE ENFORCEMENT AGENCY IN |
| | SUBSTANTIALLY THE FOLLOWING FORM: ?TO THE BEST OF MY |
| | KNOWLEDGE AND BELIEF, THE ABOVE DESCRIBED CONSTRUCTION |
| | OF ALL STRUCTURAL LOAD-BEARING COMPONENTS COMPLIES WITH |
| | THE PERMITTED DOCUMENTS AND THE SHORING AND RESHORING |
| | CONFORMS TO THE SHORING AND RESHORING PLANS SUBMITTED |
| | TO THE ENFORCEMENT AGENCY?. |
| | |
| | 2I) 110.3.7.4.2 ANY PROPOSAL TO INSTALL AN ALTERNATE |
| | STRUCTURAL PRODUCT OR SYSTEM TO WHICH BUILDING CODES |
| | APPLY SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR |
| | REVIEW FOR COMPLIANCE WITH THE CODES AND MADE PART OF |
| | THE ENFORCEMENT AGENCY?S RECORDED SET OF PERMIT |
| | DOCUMENTS. 110.3.7.4.3 ALL SHORING AND RESHORING |
| | PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE |
| | ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND |
| | RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED |
| | AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 2J) NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM |
| | BEACH?S AUTOMATED TELEPHONE INSPECTION LINE @ (561) |
| | 805-6700 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN |
| | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 3) PLEASE PROVIDE A SITE PLAN SHOWING THE PROPERTY |
| | LINES, CONSTRUCTION AREAS, STAGING AREAS, HOW THE |
| | OCCUPANTS OF THE BUILDING WILL BE SAFE GUARDED DURING |
| | THEIR ENTRY AND EXIT OF THE BUILDING. SHOW COMPLIANCE |
| | WITH 2014 FBC 3306.7 ? COVERED WALKWAYS, INCLUDING |
| | LIGHTING FOR THE EXIT DISCHARGE. 2014 FBC 3310.2 ? |
| | MAINTENANCE OF MEANS OF EGRESS. REQUIRED MEANS OF |
| | EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING |
| | CONSTRUCTION, DEMOLITION, REMODELING OR ALTERATIONS AND |
| | ADDITIONS TO ANY BUILDING. |
| | |
| | 4A) IF SCAFFOLDING EXTENDS BEYOND THE PRIVATE PROPERTY |
| | AND ONTO CITY RIGHT OF WAY, ENGINEERING WILL REQUIRE |
| | RIGHT OF WAY PERMITS. PLEASE CONTACT MANNY GONZALEZ AT |
| | THE ENGINEERING DEPARTMENT ? (561) 494-1085. |
| | |
| | 4B) IF SCAFFOLDING IS TO BE USED FOR THE HEIGHT OF THE |
| | BUILDING, PLEASE PROVIDE HOW THE SCAFFOLDING WILL BE |
| | BUILT AS WELL AS HOW THE SCAFFOLDING WILL BE ANCHORED |
| | TO RESIST LATERAL WIND LOADING. THERE APPEARS SAND |
| | BLASTING WILL ALSO BE AN ELEMENT OF THE OPERATION, HOW |
| | WILL THE SANDBLASTING BE CONTAINED, WILL THERE BE WIND |
| | SCREENS, IF SO PLEASE PROVIDE WHAT ELEMENTS WILL BE |
| | INTRODUCED TO KEEP THE SCAFFOLDING FROM MOVING WITH THE |
| | LATERAL EFFECT OF WIND ON THE WIND SCREENS. AT WHAT |
| | SAFETY FACTOR ARE THESE ELEMENTS FACTORED? 107.2.1.3 |
| | ADDITIONAL INFORMATION. 2014 FBC 3302.1 & 3306.1. |
| | |
| | 5)PROVIDE COMPLIANCE WITH FBC 3309.1 WHERE REQUIRED. |
| | ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR |
| | DEMOLITION SHALL BE PROVIDED WITH NO FEWER THAN ONE |
| | APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH |
| | SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD |
| | AS FOLLOWS: |
| | |
| | 5A) AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| | COMBUSTIBLE MATERIALS HAVE ACCUMULATED. |
| | |
| | 5B) IN EVERY STORAGE AND CONSTRUCTION SHED. |
| | |
| | 5C) ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| | PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| | STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| | |
| | 6) DURING THE RESTORATION WORK ON THE BALCONIES, |
| | DEMONSTRATE HOW THE TENANTS WILL BE SAFE GUARDED FROM |
| | THE WORK AREA AND EGRESS ONTO THE BALCONIES. FBC 3306.1 |
| | PROTECTION REQUIRED. |
| | |
| | 7) ALL ADD-MIXTURES RHINO PLASTIC CONCRETE ADDITIVES |
| | ARE TO BE REVIEWED BY THE ENGINEER OF RECORD AS WELL AS |
| | ALL OTHER ADDITIVES. 107.3.4 DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE. |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER ? PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| 2016-06-15 09:04:08 | SENT TO KC FOR REVIEW. |