Plan Review Details - Permit 16051255
Plan Review Stops For Permit 16051255
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-28 Cont ID  
Sent By cthroop Date 2016-06-28 Time 13:19 Rev Time 0.00
Received By cthroop Date 2016-06-28 Time 13:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-16 Cont ID  
Sent By cthroop Date 2016-06-16 Time 10:19 Rev Time 0.00
Received By cthroop Date 2016-06-15 Time 09:03 Sent To  
Notes
2016-06-16 12:57:38BUILDING PLAN REVIEW
 W.P.B. PERMIT NO.: 16051255
 ADD: 1200 S. FLAGLER DR.
 CONTR: CONCRETE RESTORATION SERVICES
 TEL: 561-833-3573
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 6/16/16
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE WORK UNDER THE
 SCOPE OF THIS PERMIT LIST THE SITE ADDRESS AS 1200 S.
 FLAGLER DR. WHEREAS THE SPECIAL INSPECTOR AGREEMENT
 LIST THE ADDRESS AS 120 S. FLAGLER DR. PLEASE CORRECT
 THE DISCREPANCY IN THE ADDRESS.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJECT. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) THIS BUILDING MEETS THE DEFINITION OF: THRESHOLD
 BUILDING F.S. 553.71 (7)
 ?THRESHOLD BUILDING? ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND HAS AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) UPDATE THE SPECIAL INSPECTOR AGREEMENT TO THE
 CORRECT ADDRESS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS, A SPECIAL INSPECTOR IS REQUIRED BY F.S.
 553.79 (5) TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE
 FILLED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND
 RETURNED TO THIS OFFICE AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE. CONTACT KEN
 CONRAD, MANAGER OF SPECIAL INSPECTOR PROGRAM AT (561)
 805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT MAY
 BE ISSUED.
 THE SPECIAL INSPECTOR FORMS SUBMITTED TO THE BUILDING
 DEPARTMENT ARE NOT COMPLETE, MISSING THE NOTARIZED
 SIGNATURES OF OWNER & CONTRACTOR.
  
 2C) MISSING STATEMENT. THRESHOLD BUILDING, REQUIRED.
 W.P.B. AMENDMENT 110.3.7.4.4. ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, ?TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 F.S.?
  
 2D) NOT COMPLETED. FOR THE SPECIAL INSPECTOR &
 DESIGNATED JOB INSPECTORS - PLEASE PROVIDE A RESUME? OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECTS. THE RESUME?
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME?. AFTER THE RESUME? IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED.
  
 2E) DENIED. JOB INSPECTOR ? GUILLERMO PABRON. FBC
 110.3.7.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL
 INSPECTOR TO CONDUCT THE MINIMUM STRUCTURAL INSPECTION
 OF THRESHOLD BUILDINGS REQUIRED BY THIS CODE, SECTION
 553.73,FLORIDA STATUTES, WITHOUT DUPLICATIVE INSPECTION
 BY THE BUILDING DEPARTMENT. THE BUILDING OFFICIAL IS
 RESPONSIBLE FOR ENSURING THAT ANY PERSON CONDUCTING
 INSPECTIONS IS QUALIFIED AS A BUILDING INSPECTOR UNDER
 PART XII OF CHAPTER 468, FLORIDA STATUTES, OR CERTIFIED
 AS A SPECIAL INSPECTOR UNDER CHAPTER 471 OR 481,
 FLORIDA STATUTES. INSPECTIONS OF THRESHOLD BUILDINGS
 REQUIRED BY SECTION 553.79(5), FLORIDA STATUTES, ARE IN
 ADDITION TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
  
 2F) NOT COMPLETED. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2G) NOT COMPLETED. NOTE FOR PAPER PLANS, 3 SETS OF
 DOCUMENTS ARE REQUIRED.
  
 2H) 110.3.7.4.1 THE SPECIAL INSPECTOR, UPON COMPLETION
 OF THE BUILDING AND PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY OR COMPLETION, FILE A SIGNED
 AND SEALED STATEMENT WITH THE ENFORCEMENT AGENCY IN
 SUBSTANTIALLY THE FOLLOWING FORM: ?TO THE BEST OF MY
 KNOWLEDGE AND BELIEF, THE ABOVE DESCRIBED CONSTRUCTION
 OF ALL STRUCTURAL LOAD-BEARING COMPONENTS COMPLIES WITH
 THE PERMITTED DOCUMENTS AND THE SHORING AND RESHORING
 CONFORMS TO THE SHORING AND RESHORING PLANS SUBMITTED
 TO THE ENFORCEMENT AGENCY?.
  
 2I) 110.3.7.4.2 ANY PROPOSAL TO INSTALL AN ALTERNATE
 STRUCTURAL PRODUCT OR SYSTEM TO WHICH BUILDING CODES
 APPLY SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR
 REVIEW FOR COMPLIANCE WITH THE CODES AND MADE PART OF
 THE ENFORCEMENT AGENCY?S RECORDED SET OF PERMIT
 DOCUMENTS. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2J) NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTION LINE @ (561)
 805-6700 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3) PLEASE PROVIDE A SITE PLAN SHOWING THE PROPERTY
 LINES, CONSTRUCTION AREAS, STAGING AREAS, HOW THE
 OCCUPANTS OF THE BUILDING WILL BE SAFE GUARDED DURING
 THEIR ENTRY AND EXIT OF THE BUILDING. SHOW COMPLIANCE
 WITH 2014 FBC 3306.7 ? COVERED WALKWAYS, INCLUDING
 LIGHTING FOR THE EXIT DISCHARGE. 2014 FBC 3310.2 ?
 MAINTENANCE OF MEANS OF EGRESS. REQUIRED MEANS OF
 EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING
 CONSTRUCTION, DEMOLITION, REMODELING OR ALTERATIONS AND
 ADDITIONS TO ANY BUILDING.
  
 4A) IF SCAFFOLDING EXTENDS BEYOND THE PRIVATE PROPERTY
 AND ONTO CITY RIGHT OF WAY, ENGINEERING WILL REQUIRE
 RIGHT OF WAY PERMITS. PLEASE CONTACT MANNY GONZALEZ AT
 THE ENGINEERING DEPARTMENT ? (561) 494-1085.
  
 4B) IF SCAFFOLDING IS TO BE USED FOR THE HEIGHT OF THE
 BUILDING, PLEASE PROVIDE HOW THE SCAFFOLDING WILL BE
 BUILT AS WELL AS HOW THE SCAFFOLDING WILL BE ANCHORED
 TO RESIST LATERAL WIND LOADING. THERE APPEARS SAND
 BLASTING WILL ALSO BE AN ELEMENT OF THE OPERATION, HOW
 WILL THE SANDBLASTING BE CONTAINED, WILL THERE BE WIND
 SCREENS, IF SO PLEASE PROVIDE WHAT ELEMENTS WILL BE
 INTRODUCED TO KEEP THE SCAFFOLDING FROM MOVING WITH THE
 LATERAL EFFECT OF WIND ON THE WIND SCREENS. AT WHAT
 SAFETY FACTOR ARE THESE ELEMENTS FACTORED? 107.2.1.3
 ADDITIONAL INFORMATION. 2014 FBC 3302.1 & 3306.1.
  
 5)PROVIDE COMPLIANCE WITH FBC 3309.1 WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NO FEWER THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD
 AS FOLLOWS:
  
 5A) AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
  
 5B) IN EVERY STORAGE AND CONSTRUCTION SHED.
  
 5C) ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
 6) DURING THE RESTORATION WORK ON THE BALCONIES,
 DEMONSTRATE HOW THE TENANTS WILL BE SAFE GUARDED FROM
 THE WORK AREA AND EGRESS ONTO THE BALCONIES. FBC 3306.1
 PROTECTION REQUIRED.
  
 7) ALL ADD-MIXTURES RHINO PLASTIC CONCRETE ADDITIVES
 ARE TO BE REVIEWED BY THE ENGINEER OF RECORD AS WELL AS
 ALL OTHER ADDITIVES. 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE.
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
2016-06-15 09:04:08SENT TO KC FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-28 Cont ID  
Sent By cthroop Date 2016-06-28 Time 13:18 Rev Time 0.00
Received By cthroop Date 2016-06-28 Time 13:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-16 Cont ID  
Sent By cthroop Date 2016-06-16 Time 10:19 Rev Time 0.00
Received By cthroop Date 2016-05-27 Time 09:16 Sent To  
Notes
2016-05-31 09:16:56BLDG MISC 1

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2016-06-28 Cont ID  
Sent By cthroop Date 2016-06-28 Time 13:19 Rev Time 0.00
Received By cthroop Date 2016-06-28 Time 13:19 Sent To  
Notes
2016-06-28 13:19:28PER KEN CONRAD.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-06-16 Cont ID  
Sent By cthroop Date 2016-06-16 Time 10:18 Rev Time 0.00
Received By cthroop Date 2016-06-16 Time 10:18 Sent To  
Notes
2016-06-16 10:18:54SEE BUILDING REVIEW COMMENTS.