Plan Review Details - Permit 16051216
Plan Review Stops For Permit 16051216
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-09-28 Cont ID  
Sent By cthroop Date 2016-09-28 Time 08:59 Rev Time 0.00
Received By cthroop Date 2016-09-28 Time 08:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-09-22 Cont ID  
Sent By cthroop Date 2016-09-22 Time 13:15 Rev Time 0.00
Received By cthroop Date 2016-09-22 Time 13:10 Sent To  
Notes
2016-09-22 13:17:01BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW AND
 DOOR SUBMITTALS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-31 Cont ID  
Sent By cthroop Date 2016-08-31 Time 10:42 Rev Time 0.00
Received By cthroop Date 2016-08-31 Time 10:11 Sent To E
Notes
2016-08-31 10:45:52BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS.
  
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW AND
 DOOR SUBMITTALS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-22 Cont ID  
Sent By cthroop Date 2016-07-22 Time 09:36 Rev Time 0.00
Received By cthroop Date 2016-07-22 Time 09:35 Sent To  
Notes
2016-07-22 09:44:38 
 BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/22/16
  
 1. VALUE APPEARS LOW.
 2. PROVIDE PRODUCT APPROVALS FOR ALL NEW WINDOWS AND
 EXT. DOORS.
 3. PROVIDE WIND DESIGN LOADS FOR ALL NEW OPENINGS.
 4. OWNER TO HAVE ARCHITECT TO RE-DESIGN SLAB OVERPOUR.
 5. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED.
  
 SUBMITTAL IS DEFICIENT. FULL REVIEW CANNOT BE PERFORMED
 AT THIS TIME.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW AND
 DOOR SUBMITTALS.
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-09-21 Cont ID  
Sent By mvaldes Date 2016-09-21 Time 18:37 Rev Time 0.00
Received By mvaldes Date 2016-09-21 Time 17:45 Sent To B
Notes
2016-09-21 18:40:33ROUTED TO CT

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-09-01 Cont ID  
Sent By cthroop Date 2016-08-31 Time 10:44 Rev Time 0.00
Received By mvaldes Date 2016-09-01 Time 10:26 Sent To  
Notes
2016-09-01 10:42:12PLEASE REFERENCE 2ND REVIEW COMMENTS. NOTHING WAS
 ADDRESSED AS REQUESTED. PLANS ROUTED TO JORGE VALIDO.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-08-01 Cont ID  
Sent By mvaldes Date 2016-08-01 Time 16:40 Rev Time 0.00
Received By mvaldes Date 2016-08-01 Time 15:15 Sent To  
Notes
2016-08-01 17:00:25REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1) 2ND REQUEST, PROVIDE INTERSYSTEM BONDING TERMINAL
 PER NEC 250.94 / FBC-R SECTION E3609.3
  
 2) 2ND REQUEST, ADD A NOTE FOR FBC-E R404.1 A MINIMUM
 OF 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY
 LAMPS.
  
 3) OVERCURRENT DEVICES SHALL NOT BE LOCATED IN THE
 VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN
 CLOTHES CLOSETS. NEC 240.24(D) / FBC-R SECTION E3705.7
 (RELOCATE ACCORDINGLY)
  
 4) RISER DIAGRAM REFLECTS THE FOLLOWING DEFFICIENCIES
 FBC 107 MINIMUM PLAN REVIEW
 A- LABEL FPL METER ENCLOSURE WITH AMPERE RATING
 B- 250 AWG MCM WIRE MUST BE USED UP TOO THE FIRST
 DISCONNECTING MEANS THAT CARRIES THE ENTIRE LOAD
 C- CLARIFY HOW EXISTING SUB PANELS ARE BEING FED WITH A
 3/4'' CONDUIT. VERIFY ANNEX C BECAUSE CONDUIT FILL
 DOESN'T CORRELATE.
  
 5) PANEL SCHEDULE REFLECTS THE FOLLOWING DEFFICIENCIES
 FBC 107 MINIMUM PLAN REVIEW
 A- PANEL #1 200 AMP BUS RATING IS BEING EXCEEDED PLEASE
 MODIFY ACCORDINGLY NEC 408.36(A)
 B- SCHEDULE #1 HAS INCORRECT BREAKERS PROTECTING SUB
 PANELS, LOOK AT CIRCUIT # 2,4 & CIRCUIT # 14,16
  
 6) 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-13 Cont ID  
Sent By mvaldes Date 2016-06-13 Time 09:18 Rev Time 0.00
Received By mvaldes Date 2016-06-13 Time 09:18 Sent To  
Notes
2016-06-13 10:40:56JOB PERMIT NUMBER: 16051216
 JOB ADDRESS: 520 51 STREET
 WEST PALM BEACH FLORIDA
 DATE: JUNE 13 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED. NEC 250.56 SERVICE GROUNDING ELECTRODE TO BE
 AUGMENTED BY AN ADDITIONAL ELECTRODE 6FEET AWAY OR
 PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR
 LESS.
 - FBC-E R404.1 A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS. ADD A NOTE.
 - FBC-E R402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES. ADD A NOTE.
 - LOAD CALCS ARE MISSING POOL AND SPRINKLER PUMP PLEASE
 INCLUDE, FURTHERMORE ACCORDING TO OUR ?PROPERTY
 APPRAISAL? INFORMATION THE AREA UNDER AIR IS 1777 SQ
 FT. RE-CALCULATE AND ADJUST ACCORDINGLY. NEC
 220.82(B)(1)(2)(3)(4)
 - PANEL SCHEDULE REFLECTS THE 100 AMP SUB PANEL BEING
 FED WITH A # 10 AWG AND A 30 AMP OCPD ? NEC 210.19,
 210.20 (RATINGS)
 - NEC 408.36 A PANELBOARD SHALL BE PROTECTED BY AN
 OVERCURRENT PROTECTIVE DEVICE HAVING A AMPACITY RATING
 NOT GREATER THAN THAT OF THE PANELBOARD. EXPLAIN HOW
 YOUR COMING OFF A 200 A PANEL TO A 125 DISCONNECT TO
 PROTECT A 100 AMP PANELBOARD ?
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-09-28 Cont ID  
Sent By cthroop Date 2016-09-28 Time 08:59 Rev Time 0.00
Received By cthroop Date 2016-09-26 Time 14:39 Sent To  
Notes
2016-09-27 14:39:57RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-22 Cont ID  
Sent By cthroop Date 2016-09-22 Time 13:09 Rev Time 0.00
Received By cthroop Date 2016-09-20 Time 08:50 Sent To  
Notes
2016-09-21 08:50:49RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-02 Cont ID  
Sent By cpuell Date 2016-09-02 Time 10:23 Rev Time 0.00
Received By cpuell Date 2016-07-27 Time 15:42 Sent To  
Notes
2016-07-27 15:43:07R17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-25 Cont ID  
Sent By cpuell Date 2016-07-25 Time 14:20 Rev Time 0.00
Received By cpuell Date 2016-05-27 Time 14:52 Sent To  
Notes
2016-05-27 14:52:35R15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-08-31 Cont ID  
Sent By cthroop Date 2016-08-31 Time 10:47 Rev Time 0.00
Received By cthroop Date 2016-08-31 Time 10:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-07-22 Cont ID  
Sent By cthroop Date 2016-07-22 Time 09:44 Rev Time 0.00
Received By cthroop Date 2016-07-22 Time 09:44 Sent To  
Notes
2016-07-22 09:46:01BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/22/16
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-01 Cont ID  
Sent By jvalido Date 2016-09-01 Time 15:49 Rev Time 0.00
Received By jvalido Date 2016-09-01 Time 15:29 Sent To  
Notes
2016-09-01 15:48:22SEE PROVISIONALS ON PLANS.
  
 (1) EXISTING BEDROOMS REQUIRE RETURN AIR.
 (2) INSPECTOR TO CONFIRM VENTILATION REQUIREMENT OF
 EXISTING BATHROOM.
 (3) ALL MECHANICAL WORK IS SUBJECT TO FIELD INSPECTOR"S
 APPROVAL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-25 Cont ID  
Sent By jvalido Date 2016-07-25 Time 13:22 Rev Time 0.00
Received By jvalido Date 2016-07-25 Time 10:32 Sent To  
Notes
2016-07-25 11:47:29CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE ON PLANS GRILL SIZES AND TOTAL CFM OF ALL
 EXISTING ROOMS.
  
 R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED
 IN ACCORDANCE WITH ACCA MANUAL S
 BASED ON THE EQUIPMENT LOADS CALCULATED IN ACCORDANCE
 WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING
 LOADS FOR THE DIRECTIONAL ORIENTATION OF THE BUILDING.
 THE MANUFACTURER AND MODEL
 NUMBER OF THE OUTDOOR AND INDOOR UNITS (IF SPLIT
 SYSTEM) SHALL BE SUBMITTED ALONG
 WITH THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE
 DESIGN CONDITIONS DESCRIBED IN
 SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER
 SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING
 CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL
 INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS.
  
 (2) PROVIDE ON EQUIPMENT SCHEDULE THE MANUFACTURER AND
 MODEL NUMBER OF THE OUTDOOR AND INDOOR UNITS.
 (3) THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE
 DESIGN CONDITIONS DESCRIBED IN
 SECTION R302.1.
 (4) CFM TOTAL OF AHU.
 (5) SEER
 (6) AHRI OF EQUIPMENT ON PLANS.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-08-30 Cont ID  
Sent By skennedy Date 2016-08-30 Time 14:35 Rev Time 0.00
Received By skennedy Date 2016-08-30 Time 14:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-08-23 Cont ID  
Sent By gjohnson Date 2016-08-23 Time 15:52 Rev Time 0.00
Received By gjohnson Date 2016-08-23 Time 15:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-16 Cont ID  
Sent By tklarge Date 2016-06-16 Time 08:17 Rev Time 0.00
Received By tklarge Date 2016-06-16 Time 07:42 Sent To  
Notes
***NONE***