Plan Review Details - Permit 16051209
Plan Review Stops For Permit 16051209
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-16 Cont ID  
Sent By vperez Date 2016-06-16 Time 08:42 Rev Time 0.00
Received By vperez Date 2016-06-16 Time 08:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-01 Cont ID  
Sent By vperez Date 2016-06-01 Time 13:34 Rev Time 0.00
Received By vperez Date 2016-06-01 Time 13:34 Sent To  
Notes
2016-06-01 13:35:00INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY IF THERE IS A NEW A/C COMPRESSOR
 BEING INSTALLED ALONG WITH THE NEW AHU SHOWN. ALSO
 PROVIDE EXISTING PANEL RATING AND A REVISED PANEL LOAD
 CALCULATION TO DETERMINE IF PANEL IS ADEQUATE TO
 WITHHOLD NEW EQUIPMENT. FBC 107.3.5 MINIMUM CRITERIA
 PLAN REVIEW.
 2.CLARIFY IF THERE IS A MECHANICAL PERMIT FOR AHU. IF
 SO PROVIDE PERMIT NUMBER ISSUED
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-16 Cont ID  
Sent By vperez Date 2016-06-16 Time 08:42 Rev Time 0.00
Received By vperez Date 2016-06-16 Time 08:42 Sent To  
Notes
2016-06-07 14:11:26VPEREZ'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-01 Cont ID  
Sent By vperez Date 2016-06-01 Time 13:35 Rev Time 0.00
Received By vperez Date 2016-06-01 Time 13:35 Sent To  
Notes
2016-05-31 13:36:49ELEC - $5000