Plan Review Details - Permit 16051191
Plan Review Stops For Permit 16051191
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-06-03 Cont ID  
Sent By jwitmer Date 2016-06-03 Time 07:59 Rev Time  
Received By jwitmer Date 2016-06-03 Time 07:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-11 Cont ID  
Sent By mvaldes Date 2016-07-11 Time 11:15 Rev Time 0.00
Received By mvaldes Date 2016-07-11 Time 11:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By mvaldes Date 2016-06-06 Time 14:12 Rev Time 0.00
Received By mvaldes Date 2016-06-06 Time 13:33 Sent To  
Notes
2016-06-06 14:13:31JOB PERMIT NUMBER: 16051191
 JOB ADDRESS: 1801 S FLAGLER DRIVE SUITE # 305
 WEST PALM BEACH FLORIDA
 DATE: JUNE 6 2016
  ELECTRICAL PLAN REVIEW COMMENTS
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 - SHOW KITCHEN COUNTERTOPS RECEPTACLE OUTLETS AS BEING
 GFCI PROTECTED IN ACCORDANCE WITH NEC 210.8(A)
 - FBC-E R402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 - FBC-E R404.1 A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS.
 - NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL.
 - NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT. OR
 MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. (DOUBLE CHECK
 MASTER, GUEST ROOM, LIVING/DINING, AND ENTRANCE.)
 - FBC-E 808.3.1 ENCLOSED AREAS. ALL ENCLOSED AREAS,
 OTHER THAN CLOSETS, KITCHENS, BASEMENTS, GARAGES,
 HALLWAYS, LAUNDRY AREAS, UTILITY AREAS, STORAGE AREAS
 AND BATHROOMS SHALL HAVE A MINIMUM OF TWO DUPLEX
 RECEPTACLE OUTLETS OR ONE DUPLEX RECEPTACLE OUTLET AND
 ONE CEILING OR WALL-TYPE LIGHTING OUTLET.( EXCEPTION TO
 WALL SPACE REQUIREMENT )
 - PANEL SCHEDULE REFLECTS INCORRECT OCPD & WIRE SIZES
 FOR EXAMPLE THE RANGE SHOWS 1500 VA ON A 50 AMP BKR ?,
 THE W/H SHOWS 1000 VA ON A 20 AMP BKR ?, THE OVEN 1500
 VA ON A 15 AMP BKR?, ALL SINGLE POLE ?, UNLESS THESE
 ARE GAS PLEASE REVISE. KEEP IN MIND CODE REQUIRES
 MINIMUM A 20 AMP CIRCUIT FOR THE BATHROOM WHICH ISN?T
 PROVIDED NEC 210.11(C)(3).
 - IN ACCORDANCE WITH NEC 220.82(A)(B) THE CALCULATION
 MUST INCLUDE THE MINIMUM OF GENERAL LIGHTING LOAD(3 VA
 X SQ FT), 2 SMALL APPLIANCE 1500 VA EACH AND 1 LAUNDRY
 1500 VA UNLESS FACILITIES ARE PROVIDED SEPARATELY, PLUS
 THE NAME PLATE OF OTHER EQUIPMENT AND AC VS HEAT LOADS.
 PLEASE VERIFY ?
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-06-30 Cont ID  
Sent By mvaldes Date 2016-07-11 Time 11:15 Rev Time 0.00
Received By pleduc Date 2016-06-30 Time 10:41 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-31 Cont ID  
Sent By pleduc Date 2016-05-31 Time   Rev Time 0.00
Received By pleduc Date 2016-05-31 Time 14:23 Sent To  
Notes
2016-05-31 14:55:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 00-A- THERE IS NO REFERENCE OF REVIEW AND/OR
 COMPLIANCE WITH THE FIRE CODE. PLEASE PROVIDE A NOTE
 AND ENSURE COMPLIANCE WITH THE FOLLOWING:
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
 2) SHEET 01-A - THERE IS NO INDICATION OF ANY EXISTING
 FIRE SPRINKLERS AND/OR FIRE ALARM. PLEASE PROVIDE A
 NOTE AND PROPER INDICATIONS.
  
 3) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 PLEASE PROVIDE A NOTE:
 ANY EXISITNG LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-11 Cont ID  
Sent By mvaldes Date 2016-07-11 Time 11:15 Rev Time 0.00
Received By mvaldes Date 2016-06-29 Time 13:22 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-08 Cont ID  
Sent By gearl Date 2016-06-08 Time 15:25 Rev Time 0.00
Received By gearl Date 2016-05-26 Time 15:02 Sent To  
Notes
2016-05-26 15:02:27B09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-06-03 Cont ID  
Sent By jwitmer Date 2016-06-03 Time 07:38 Rev Time 0.00
Received By jwitmer Date 2016-06-03 Time 07:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-08 Cont ID  
Sent By gearl Date 2016-06-08 Time 15:24 Rev Time 0.00
Received By gearl Date 2016-06-08 Time 15:24 Sent To  
Notes
***NONE***