Plan Review Details - Permit 16051054
Plan Review Stops For Permit 16051054
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By tklarge Date 2016-06-13 Time 09:01 Rev Time 0.00
Received By tklarge Date 2016-06-13 Time 09:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-05-27 Cont ID  
Sent By tklarge Date 2016-05-27 Time 05:34 Rev Time 0.00
Received By tklarge Date 2016-05-27 Time 05:24 Sent To  
Notes
2016-05-27 05:32:261) THE MINIMUM SIZE PIPE TO THE TANKLESS WATER HEATER
 SHALL BE 1 INCH PER 2014 FGC TABLE 402.4 (2).
 2) THE PE TABLE NOTED ON THE PLANS IS LISTED FOR CSST
 IN THE 2014 FUEL GAS CODE. THE PLAN REFERENCES THE 2010
 FBC. THE 2010 CODE HAS NOT BEEN IN EFFECT FOR ALMOST A
 YEAR. SIZE THE SYSTEM ACCORDING TO THE TABLES IN THE
 2014 CODE.
 3) SPECIFY THE SIZING TABLE ON THE PLANS THAT IS BEING
 USED FOR THE SCH. 40 METALLIC PIPE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-13 Cont ID  
Sent By tklarge Date 2016-06-13 Time 09:01 Rev Time 0.00
Received By tklarge Date 2016-06-13 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-27 Cont ID  
Sent By tklarge Date 2016-05-27 Time 05:34 Rev Time 0.00
Received By tklarge Date 2016-05-24 Time 14:54 Sent To  
Notes
2016-05-24 14:54:18PLUMB -$5000