Plan Review Details - Permit 16051031
Plan Review Stops For Permit 16051031
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-18 Cont ID  
Sent By skennedy Date 2016-07-18 Time 11:01 Rev Time 0.00
Received By skennedy Date 2016-07-18 Time 11:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-29 Cont ID  
Sent By jgomez Date 2016-06-28 Time 15:15 Rev Time 0.00
Received By jgomez Date 2016-06-28 Time 13:45 Sent To  
Notes
2016-06-28 15:47:04NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO.
 CONTRACTOR MAY SUBMIT REQUIRED INFORMATION AFTER PERMIT
 IS ISSUED AND BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME.
  
 1- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- DESIGNER OF RECORD TO SPECIFY ALL LIVE LOADS
 INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY NOTES "B"
 AND "G" OF TABLE R301.5 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 3- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING NAILS OR SCREWS, THEN SPECIFY TYPE AND
 NUMBER. IF SPECIFYING ROOF TILE ADHESIVE, THEN PROVIDE
 PRODUCT APPROVAL.
  
 4- ENERGY CALCULATIONS SUBMITTED:
 A) CLARIFY WHY SPACES IN PAGE 2 OF 4 SPECIFIES THAT
 THERE IS NO KITCHEN IN THIS SINGLE FAMILY RESIDENCE?.
 REVISE AS REQUIRED TO MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) CLARIFY WHERE ARE THE TWO INSULATED DOORS SPECIFIED
 ON PAGE 3 OF 4. REVISE AS REQUIRED TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: LABEL FOR DOORS AND WINDOWS WILL BE REQUIRED
 SHOWING THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE
 ENERGY CALCULATIONS WHEN THE ENERGY CALCULATIONS ARE
 NOT USING THE DEFAULT FACTOR FOR GLAZING.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 C) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON THE TRUSS
 CONNECTOR SCHEDULE. NOTE: NEED TO UPDATE THE FLORIDA
 PRODUCT APPROVAL NUMBERS LISTED ON THE TRUSS CONNECTOR
 SCHEDULE. FLORIDA PRODUCT APPROVAL NEEDS TO BE FOR THE
 2014 CODE VERSION NOT 2010.
  
 6- DESIGNER OR RECORD TO APPROVE ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. NOTE:
 PLEASE PLACE REVIEW STAMP ON THE FRONT OF THE COVER
 PAGE OF THE PRODUCT APPROVAL NOT ON THE BACK. STAMP ON
 THE BACK OF THE PAGE DON'T ALLOW FOR PROPER SCANNING OF
 THE DOCUMENTS FOR FILING PURPOSES. SEC. 107.2.1.4 CITY
 AMENDMENTS.
  
 7- TRUSS PACKAGE SUBMITTED:
 A) NEED ENGINEER'S ORIGINAL SIGNATURE (NOT COPY OR
 RUBBER STAMP) AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 B) THE TRUSS PACKAGE NEEDS TO BE REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD AS REQUIRED BY SEC. 107.3.4.2
 CITY AMENDMENTS.
  
 C) THE COVER PAGE IS MISSING THE BUILDING PROFESSIONAL
 DESIGNER OF RECORD INFORMATION AS REQUIRED BY F.A.C.
 SEC. 61G15-31.003.
  
 D) ALL GENERAL DETAILS NEED TO BE SIGNED AND SEALED AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 E) INDIVIDUAL TRUSSES ARE DESIGNED BASED ON THE 2010
 FBC. NEED TO REVISE USING THE CURRENT BUILDING CODE.
 REVISE THE GENERAL INFORMATION IN THE MIDDLE PAGE OF
 EACH INDIVIDUAL TRUSS AND NOTE #1 OF EACH INDIVIDUAL
 TRUSS. REVISE AS REQUIRED. CHAPTER 553 FLORIDA-STATUTE.
  
 F) INDIVIDUAL TRUSSES NEED TO BE DESIGNED FOR THE ATTIC
 LIVE LOAD AS REQUIRED BY NOTES "B" AND "G" OF TABLE
 R301.5 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED.
  
 G) THE INDIVIDUAL TRUSSES ARE NOT PROPERLY NUMBERED TO
 MATCH INDEX SHEET AS REQUIRED BY F.A.C. SEC.
 61G15-31.003.
  
 H) THE LETTERING OF THE INDIVIDUAL TRUSSES IS TOO
 SMALL. IT'S NOT LEGIBLE. PROVIDE BIGGER AND LEGIBLE
 LETTERING. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD
 SHEET. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-06-23 Cont ID  
Sent By mvaldes Date 2016-06-23 Time 09:49 Rev Time 0.00
Received By mvaldes Date 2016-06-23 Time 08:52 Sent To  
Notes
2016-06-23 09:53:31REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO'S
  
 - FBC-E R404.1 A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS.
  
 - FBC-E R402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
  
 - NEC 680.21(C), 680.22 POOL PUMPS, POOL LIGHTS SHALL
 HAVE GFCI PROTECTION FOR THERE DEDICATED BRANCH
 CIRCUITS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-07-18 Cont ID  
Sent By skennedy Date 2016-07-18 Time 11:01 Rev Time 0.00
Received By skennedy Date 2016-07-18 Time 11:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By gjohnson Date 2016-06-06 Time 10:22 Rev Time 0.00
Received By gjohnson Date 2016-06-06 Time 10:22 Sent To  
Notes
2016-06-06 10:37:461ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1.GAS SIZING TABLE LISTED ON THE PLAN FOR THE PE PIPES
 NOT CORRECT IT'S FOR CSST AT 5PSI PLEASE CORRECT ON
 PLAN.
 PER WPB AMEND. TP FBC 107.2.1
  
 2.THE PE PIPE SHALL BE SIZED FOR 100FT LONGEST LENGTH
 IT SHOULD BE 11/2IN PER FBC FUEL GAS TABLE 402.4(21)
  
 3. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOK TOP
 AND WATER HEATER USING STANDARD METHOD PER FBC FUEL GAS
 SEC. 304.5.1
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2016-07-18 Cont ID  
Sent By skennedy Date 2016-07-18 Time 11:02 Rev Time 0.00
Received By skennedy Date 2016-07-18 Time 10:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-29 Cont ID  
Sent By jgomez Date 2016-06-29 Time 13:53 Rev Time 0.00
Received By jgomez Date 2016-05-24 Time 12:52 Sent To  
Notes
2016-05-25 12:52:59R29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-07-18 Cont ID  
Sent By skennedy Date 2016-07-18 Time 10:43 Rev Time 0.00
Received By skennedy Date 2016-07-18 Time 10:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-06-28 Cont ID  
Sent By jgomez Date 2016-06-28 Time 15:49 Rev Time 0.00
Received By jgomez Date 2016-06-28 Time 15:49 Sent To  
Notes
2016-06-28 15:52:121- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-06-09 Cont ID  
Sent By jvalido Date 2016-06-09 Time 13:20 Rev Time 0.00
Received By jvalido Date 2016-06-09 Time 12:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-06 Cont ID  
Sent By gjohnson Date 2016-06-06 Time 10:22 Rev Time 0.00
Received By gjohnson Date 2016-06-06 Time 10:22 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-07-18 Cont ID  
Sent By skennedy Date 2016-07-18 Time 11:02 Rev Time 0.00
Received By skennedy Date 2016-07-18 Time 11:02 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-06-29 Cont ID  
Sent By jgomez Date 2016-06-29 Time 13:51 Rev Time 0.00
Received By jgomez Date 2016-06-29 Time 07:39 Sent To  
Notes
2016-06-29 13:53:221- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
  
  
 APPROVED PRODUCT APPROVALS:
 A) OFF-RIDGE VENT FL16588-R1.
  
 B) ROOFING TILES FL7473-R6.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-06-14 Cont ID  
Sent By awooten Date 2016-06-14 Time 11:13 Rev Time 0.00
Received By awooten Date 2016-06-14 Time 11:12 Sent To  
Notes
***NONE***