| 2016-05-24 09:49:54 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- THE VALUE OF THE HOUSE IS MORE THAN $750.000 AND |
| | THIS HOUSE WAS BUILT BEFORE THE FLORIDA BUILDING CODE |
| | WAS IN EFFECT. OPENING PROTECTION IS REQUIRED BY SEC. |
| | 105.15 CITY AMENDMENTS. SEE COPY OF CITY AMENDMENT |
| | BELOW. PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE |
| | WINDOWS AND DOORS OPENING PROTECTION. |
| | |
| | 105.15 OPENING PROTECTION. |
| | WHEN ANY ACTIVITY REQUIRING A BUILDING PERMIT THAT IS |
| | APPLIED FOR ON OR AFTER JULY 1, 2008, AND FOR WHICH THE |
| | ESTIMATED COST IS $50,000 OR MORE FOR A SITE BUILT |
| | SINGLE-FAMILY DETACHED RESIDENTIAL STRUCTURE THAT IS |
| | LOCATED IN THE WIND BORNE DEBRIS REGION AS DEFINED IN |
| | THIS CODE AND THAT HAS AN INSURED VALUE OF $750,000 OR |
| | MORE, OR, IF THE SITE BUILT SINGLE-FAMILY DETACHED |
| | RESIDENTIAL STRUCTURE IS UNINSURED OR FOR WHICH |
| | DOCUMENTATION OF INSURED VALUE IS NOT PRESENTED, HAS A |
| | JUST VALUATION FOR THE STRUCTURE FOR PURPOSES OF AD |
| | VALOREM TAXATION OF $750,000 OR MORE; OPENING |
| | PROTECTIONS AS REQUIRED WITHIN THIS CODE OR FLORIDA |
| | BUILDING CODE, RESIDENTIAL FOR NEW CONSTRUCTION SHALL |
| | BE PROVIDED. |
| | |
| | EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES |
| | PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT |
| | REQUIRED TO COMPLY WITH THIS SECTION. |
| | |
| | 2- FLAT ROOF: |
| | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7 OF NOA 14-0224.03 |
| | SUBMITTED. CALCULATIONS REQUIRED TO MEET THE DESIGN |
| | PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES ) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR THE ROOF VENTS TO BE INSTALLED. |
| | |