Plan Review Details - Permit 16050966
Plan Review Stops For Permit 16050966
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-10-05 Cont ID  
Sent By shill Date 2016-10-05 Time 13:41 Rev Time 0.00
Received By shill Date 2016-10-05 Time 13:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-26 Cont ID  
Sent By shill Date 2016-07-26 Time 15:41 Rev Time 0.00
Received By shill Date 2016-07-26 Time 15:41 Sent To  
Notes
2016-07-26 15:57:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. IF A STAIR IS PROPOSED, PROVIDE A DETAIL FOR THE
 STAIR AND LANDING, FBC 1009, 1009.8.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT THIS IS NOT
 REQUIRED TO BE ACCESSIBLE. THE CODE SECTION REFERENCED
 IS FROM CHAPTER 10, FLORIDA BUILDING CODE, BUILDING.
 THIS IS A STAIR IN THE EXIT DISCHARGE AND IS TO COMPLY
 WITH THE REQUIREMENTS OF FBC 1009.
  
 REVISE PLAN TO SHOW A LANDING WHICH COMPLIES WITH
 1009.8 OR REVISE TO INCLUDE EXCEPTION.
  
 IF THE STAIR IS NOT INTENDED TO MEET THE REQUIREMENTS
 OF FBC 5TH EDITION ACCESSIBILITY, REVISE PLAN TO
 INCLUDE APPLICABLE EXCEPTIONS INCLUDING CODE SECTION.
  
 THE STAIR SHOWN DOES NOT HAVE HANDRAILS, FBC BUILDING
 1009.15. PROVIDE A DETAIL.
  
 FBC 553, A 4X PLAN REVIEW FEE IS REQUIRED TO BE
 ASSESSED IF COMMENT IS NOT ADDRESSED A THIRD TIME (LIFE
 SAFETY)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-01 Cont ID  
Sent By shill Date 2016-06-01 Time 10:06 Rev Time 0.00
Received By shill Date 2016-06-01 Time 10:06 Sent To Z
Notes
2016-06-01 10:08:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SCOPE NOT CLEAR, FBC 107. IF A STAIR IS PROPOSED,
 PROVIDE A DETAIL FOR THE STAIR AND LANDING, FBC 1009,
 1009.8. PROVIDE A SITE PLAN SHOWING LOCATION OF THE
 PROPOSED DOOR AND STAIR IN RELATION TO THE PROPERTY
 LINE.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-28 Cont ID  
Sent By mvaldes Date 2016-09-28 Time 14:53 Rev Time 0.00
Received By mvaldes Date 2016-09-28 Time 14:24 Sent To  
Notes
2016-09-28 14:54:55REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 PASSED WITH THE FOLLOWING PROVISO
  
 1] NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL
 BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-21 Cont ID  
Sent By mvaldes Date 2016-07-21 Time 14:56 Rev Time 0.00
Received By mvaldes Date 2016-07-21 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-02 Cont ID  
Sent By njwira Date 2016-06-02 Time 08:07 Rev Time 0.00
Received By mvaldes Date 2016-06-02 Time 08:56 Sent To  
Notes
2016-06-02 09:04:55REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL BE
 FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.
  
 - 1006.2 THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL
 NOT BE LESS THAN 1 FOOTCANDLE (11 LUX) AT THE WALKING
 SURFACE. THE MEANS OF EGRESS, INCLUDING THE EXIT
 DISCHARGE, SHALL BE ILLUMINATED AT ALL TIMES THE
 BUILDING SPACE SERVED BY THE MEANS OF EGRESS IS
 OCCUPIED.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-09-19 Cont ID  
Sent By scaldero Date 2016-09-19 Time 12:43 Rev Time 0.00
Received By scaldero Date 2016-09-19 Time 12:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-25 Cont ID  
Sent By scaldero Date 2016-07-25 Time 11:07 Rev Time 0.00
Received By scaldero Date 2016-07-25 Time 11:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-24 Cont ID  
Sent By scaldero Date 2016-05-24 Time 09:39 Rev Time 0.00
Received By scaldero Date 2016-05-24 Time 09:23 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-05 Cont ID  
Sent By shill Date 2016-10-05 Time 13:41 Rev Time 0.00
Received By shill Date 2016-09-16 Time 12:54 Sent To  
Notes
2016-09-16 12:54:17B19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-26 Cont ID  
Sent By shill Date 2016-07-26 Time 15:57 Rev Time 0.00
Received By shill Date 2016-07-15 Time 11:38 Sent To  
Notes
2016-07-15 11:39:31B04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-02 Cont ID  
Sent By mvaldes Date 2016-06-02 Time 09:05 Rev Time 0.00
Received By mvaldes Date 2016-05-23 Time 12:34 Sent To  
Notes
2016-06-01 10:20:576/1 TO ZONING BOX
  
  
2016-05-23 12:35:07ROUTED TO FIRE

Review Stop Z ZONING
Rev No 3 Status P Date 2016-09-23 Cont ID  
Sent By njwira Date 2016-09-23 Time 16:38 Rev Time 0.00
Received By njwira Date 2016-09-23 Time 16:05 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-19 Cont ID  
Sent By njwira Date 2016-07-19 Time 11:44 Rev Time 0.00
Received By njwira Date 2016-07-19 Time 11:44 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-06-02 Cont ID  
Sent By njwira Date 2016-06-02 Time 08:07 Rev Time 0.00
Received By njwira Date 2016-06-02 Time 08:07 Sent To E
Notes
***NONE***