Plan Review Details - Permit 16050949
Plan Review Stops For Permit 16050949
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-05-28 Cont ID  
Sent By shill Date 2016-05-28 Time 14:42 Rev Time 0.00
Received By shill Date 2016-05-28 Time 14:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-16 Cont ID  
Sent By vperez Date 2016-06-16 Time 11:51 Rev Time 0.00
Received By vperez Date 2016-06-16 Time 11:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-25 Cont ID  
Sent By vperez Date 2016-05-25 Time 13:49 Rev Time 0.00
Received By vperez Date 2016-05-25 Time 13:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-24 Cont ID  
Sent By scaldero Date 2016-05-24 Time 09:18 Rev Time 0.00
Received By scaldero Date 2016-05-24 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-16 Cont ID  
Sent By vperez Date 2016-06-16 Time 11:51 Rev Time 0.00
Received By vperez Date 2016-06-16 Time 11:51 Sent To  
Notes
2016-06-15 09:44:14RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-08 Cont ID  
Sent By ccole Date 2016-05-25 Time 10:26 Rev Time 0.00
Received By ccole Date 2016-05-20 Time 09:54 Sent To  
Notes
2016-05-23 09:54:43B08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-15 Cont ID  
Sent By ccole Date 2016-06-15 Time 14:11 Rev Time 0.00
Received By ccole Date 2016-06-15 Time 14:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-25 Cont ID  
Sent By ccole Date 2016-05-25 Time 17:37 Rev Time 0.00
Received By ccole Date 2016-05-25 Time 17:37 Sent To  
Notes
2016-05-25 17:52:481ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050949
 5/25/16
  
 1) INDICATE THE MAKE AND MODEL AND COOLING AND HEATING
 CAPACITIES OF THE EXISTING AC SYSTEM.
 2) THE 8X12" TRUNK AND 10" ROUND DUCT ARE UNDERSIZED
 FOR 750 CFM'S OF SUPPLY AIR PER BY STANDARD ACCA DUCT
 SIZING CALCULATORS. PROVIDE A MINIMUM 8X16" TRUNK AND
 12" ROUND DUCT AND SHOW THEIR POINT OF CONNECTION.
 3) THE 6" RETURN AIR TRANSFER DUCT FROM BEDROOM-3 TO
 THE LIVING ROOM SHALL BE MINIMUM 8"- SECTION 601.5
 FBC-14 MECHANICAL.
 4) PROVIDE AN EXHAUST VENTILATION PLAN FOR THE NEW
 COOKTOP IN COMPLIANCE WITH SECTION 505.1. SHOW THE HOOD
 AND EXHAUST DUCT SIZES, EXHAUST DUCT RUN, AND
 TERNINATION LOCATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE COOKTOP AND THE EXHAUST SYSTEM.
 PLEASE NOTE THAT MAKEUP AIR WILL BE REQUIRED IF THE
 SYST3EM IS CAPABLE OF EXHAUSTING IN EXCESS OF 400
 CFM'S.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-01 Cont ID  
Sent By gjohnson Date 2016-06-01 Time 16:28 Rev Time 0.00
Received By gjohnson Date 2016-06-01 Time 16:28 Sent To  
Notes
***NONE***