Plan Review Details - Permit 16050924
Plan Review Stops For Permit 16050924
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-24 Cont ID  
Sent By vperez Date 2016-05-24 Time 08:32 Rev Time 0.00
Received By vperez Date 2016-05-24 Time 08:32 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-25 Cont ID  
Sent By ccole Date 2016-05-25 Time 16:22 Rev Time 0.00
Received By ccole Date 2016-05-20 Time 09:14 Sent To  
Notes
2016-05-23 09:14:56REVISION ROUTED TO VPEREZ

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-25 Cont ID  
Sent By ccole Date 2016-05-25 Time 16:19 Rev Time 0.00
Received By ccole Date 2016-05-25 Time 16:19 Sent To  
Notes
2016-05-25 16:21:541ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050924
 5/25/16
  
 1) PROVIDE THE EXISTING DUCT SIZES ON THE REVISED
 PLANS, AND PLEASE ENLARGE OR CLARIFY THE SUPPLY
 DIFFUSER AND AND RETURN GRILL DESIGNATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-25 Cont ID  
Sent By tklarge Date 2016-05-25 Time 14:03 Rev Time 0.00
Received By tklarge Date 2016-05-25 Time 13:06 Sent To  
Notes
2016-05-25 14:03:111) SUBMIT A REVISED SANITARY RISER DIAGRAM FOR THE
 CHANGES MADE TO THE SANITARY SYSTEM.
 2) IT APPEARS AS THOUGH A GREASE TRAP/INTERCEPTOR HAS
 BEEN ADDED BY THE BACK BAR.IDENTIFY THE SQUARE SYMBOL
 ON THE PLAN AND SUBMIT 2 COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THIS DEVICE. FBC 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  