Plan Review Details - Permit 16050922
Plan Review Stops For Permit 16050922
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-10 Cont ID  
Sent By cthroop Date 2016-06-10 Time 09:32 Rev Time 0.00
Received By cthroop Date 2016-06-10 Time 09:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-26 Cont ID  
Sent By cthroop Date 2016-05-26 Time 10:55 Rev Time 0.00
Received By cthroop Date 2016-05-26 Time 10:55 Sent To  
Notes
2016-05-26 11:35:55BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
 W/ 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHPT. 1, ADMINISTRATION
  
 1ST REVIEW
 DATE: 5/26/16
 ACTION: FAILED
  
 1. DESIGN PROFESSIONAL TO SIGN AND SEAL DRAWINGS PER
 FBC 107.1. PHOTO COPIES ARE NOT ACCEPTABLE.
 2. SUBMITTED PLANS ARE GENERIC IN NATURE. PLEASE
 PROVIDE SITE SPECIFIC DESIGN. SPECIFY VULT MPH, RISK
 CATAGORY AND EXPOSURE PARAMETERS. INDICATE SPECIFIC
 DETAIL OF PV SYSTEM ATTACHMENT TO EXISTING ROOF SYSTEM.
 3. DESIGN PROFESSIONAL TO EVALUATE EXISTING STRUCTURE
 TO DETERMINE IF STRUCTURE CAN ACCOMODATE ADDITIONAL
 DEAD LOAD OF PV SYSTEM. SUBMITTED DOCUMENTS PROVIDE
 SATELLITE VIEW OF STRUCTURE ONLY.
 4. PROVIDE WIND DESIGN LOADS PER FBCR 301.
  
 FBC-107.1 GENERAL - FAC 61G1-16.004 - A TITLE BLOCK
 MUST APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION IDENTIFICATION SHEETS THAT
 ARE REQUIRED TO BE SIGNED AND SEALED. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
 (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE
 REVISED.
 (8) FOR THE PURPOSES OF THIS RULE, FIRM IS DEFINED TO
 BE A CORPORATION, LIMITED LIABILITY COMPANY,
 PARTNERSHIP, PERSON PRACTICING UNDER A FICTITIOUS NAME,
 OR PERSON PRACTICING ARCHITECTURE OR INTERIOR DESIGN IN
 HIS OR HER OWN NAME.
  
 R301.1 APPLICATION.
 BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, SHALL
 BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING
 DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW
 LOADS, WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY
 THIS CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES
 IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS ALL REQUIREMENTS FOR THE TRANSFER OF ALL
 LOADS FROM THEIR POINT OF ORIGIN THROUGH THE
 LOAD-RESISTING ELEMENTS TO THE FOUNDATION. BUILDINGS
 AND STRUCTURES CONSTRUCTED AS PRESCRIBED BY THIS CODE
 ARE DEEMED TO COMPLY WITH THE REQUIREMENTS OF THIS
 SECTION.
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-09 Cont ID  
Sent By mvaldes Date 2016-06-09 Time 18:49 Rev Time 0.00
Received By mvaldes Date 2016-06-09 Time 18:49 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-23 Cont ID  
Sent By mvaldes Date 2016-05-23 Time 15:52 Rev Time 0.00
Received By mvaldes Date 2016-05-23 Time 15:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-10 Cont ID  
Sent By cthroop Date 2016-06-10 Time 09:32 Rev Time 0.00
Received By cthroop Date 2016-06-07 Time 14:06 Sent To  
Notes
2016-06-07 14:07:13MVALDES' S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-26 Cont ID  
Sent By cthroop Date 2016-05-26 Time 10:55 Rev Time 0.00
Received By cthroop Date 2016-05-20 Time 09:56 Sent To  
Notes
2016-05-23 09:56:14ROUTED TO ELECTRICAL INBOX