Plan Review Details - Permit 16050921
Plan Review Stops For Permit 16050921
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-20 Cont ID  
Sent By gjohnson Date 2016-05-20 Time 17:01 Rev Time 0.00
Received By gjohnson Date 2016-05-20 Time 17:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By gjohnson Date 2016-06-01 Time 14:12 Rev Time 0.00
Received By gjohnson Date 2016-05-31 Time 15:22 Sent To  
Notes
2016-05-31 15:24:55RESUB CORRECT MANUFATURE SPECS APPROVED SENT TO
 UTILITIES.

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-20 Cont ID  
Sent By gjohnson Date 2016-05-20 Time 17:02 Rev Time 0.00
Received By gjohnson Date 2016-05-20 Time 17:02 Sent To  
Notes
2016-05-20 17:24:41 
  
 PLUMBING COMMENTS:
  
 1. THE WILKINS MODEL 720 A DOES NOT MEET THE .25% PB TO
 MEET THE LEAD FREE NSF 61 STANDARDS IT IS ON THE USC
 LIST BUT IF YOU LOOK AT THE .25% PB IT INDICATES A NO.
  
 TYPE: PVB MANUFACTURER: WILKINS MODEL: 720A
 SIZE: 1 ORIENTATION: VUH METERS:
 MANUAL: 5 ( 0.25% PB: NO) SPARE PARTS ONLY: NO
 APPROVED: 28-AUG-1978 RENEWED: 28-AUG-2014 BYPASS:
 SHUTOFFS: (II),OOO
 NOTES: BEGINNING WITH SERIAL NO. T00001 THE TEST COCKS
 WERE MOVED FROM THE BODY TO THE SHUTOFF VALVES.
 2015 ? UNIVERSITY OF SOUTHERN CALIFORNIA
  
 THE WILKINS MODEL 420 XL IS THE ONLY WILKINS MODEL THAT
 MEETS THE LEAD FREE REQUIREMENT.
  
 TYPE: PVB MANUFACTURER: WILKINS MODEL: 420XL
 SIZE: 1 ORIENTATION: VUH METERS:
 MANUAL: 9 ( 0.25% PB: YES) SPARE PARTS ONLY: YES
 APPROVED: 03-AUG-2011 RENEWED: 03-AUG-2014 BYPASS:
 SHUTOFFS: (IIII)
  
  
 2.PLEASE INDICATE ON THE PERMIT APPLICATION AND
 MANUFACTURE SPEC WHAT SIZE YOUR USING.
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  