Plan Review Details - Permit 16050887
Plan Review Stops For Permit 16050887
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-06-07 Cont ID  
Sent By jwitmer Date 2016-06-03 Time 15:07 Rev Time 0.00
Received By jwitmer Date 2016-06-03 Time 11:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-27 Cont ID  
Sent By vperez Date 2016-05-27 Time 09:24 Rev Time 0.00
Received By vperez Date 2016-05-27 Time 09:24 Sent To  
Notes
2016-05-27 09:30:39 
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVISO: LOW VOLTAGE SYSTEMS UNDER SEPARATE PERMITS
 2. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-24 Cont ID  
Sent By scaldero Date 2016-05-24 Time 10:30 Rev Time 0.00
Received By scaldero Date 2016-05-24 Time 10:24 Sent To  
Notes
2016-05-24 10:30:44PERMIT #16050887
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-07 Cont ID  
Sent By eschneid Date 2016-06-07 Time 17:19 Rev Time 0.00
Received By eschneid Date 2016-05-19 Time 13:38 Sent To  
Notes
2016-05-20 13:38:28C26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-06-03 Cont ID  
Sent By jwitmer Date 2016-06-03 Time 11:48 Rev Time 0.00
Received By jwitmer Date 2016-06-03 Time 11:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-05-23 Cont ID  
Sent By hmoser Date 2016-05-23 Time 14:37 Rev Time 0.00
Received By hmoser Date 2016-05-23 Time 10:37 Sent To  
Notes
2016-05-23 14:37:47PASS PROVISO
 CONDENSATE CAN NOT DRAIN INTO MOP SINK
 PER SECTION 90-126 PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE # 5 WEST PALM
 BEACH CODE OF ORDINANCES.
 #5
 STORMWATER, SURFACE WATER, GROUNDWATER,
 ARTESIAN WELL WATER, ROOF RUNOFF. SUBSURFACE
 DRAINAGE, SWIMMING POOL DISCHARGE,
 UNCONTAMINATED COOLING WATER,
 AIR CONDITIONING CONDENSATE,
  
 REFER TO SECTION 604.8 LINING INSTALLATION.
 2014 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-01 Cont ID  
Sent By gjohnson Date 2016-06-01 Time 14:56 Rev Time 0.00
Received By gjohnson Date 2016-06-01 Time 14:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-08 Cont ID  
Sent By eschneid Date 2016-07-08 Time 10:48 Rev Time 0.50
Received By eschneid Date 2016-07-08 Time 10:32 Sent To  
Notes
2016-07-08 10:48:15SIGNS REQUIRE SEPARATE PERMITS WITH PLANS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-07 Cont ID  
Sent By eschneid Date 2016-06-07 Time 16:48 Rev Time 0.00
Received By eschneid Date 2016-06-07 Time 10:32 Sent To  
Notes
2016-06-07 17:19:42FAILED
  
 1) PROVIDE THE PALM BEACH OUTLETS MANAGEMENT APPROVAL
 STAMP ON THE PLANS.
  
 2) PLEASE PROVIDE MORE INFORMATION AS TO HOW THE
 DISPLAY AREA ON THE WEST SIDE OF THE STORE WILL
 FUNCTION/HOW WILL IT APPEAR. HOW DEEP IS THE GRAPHIC
 BANNER? WHAT WILL BE ON THE GRAPHIC BANNER? THERE SHALL
 BE SOME DISPLAY MERCHANDISE IN THE WESTERN FACING
 WINDOW DISPLAY.
  
 3) PLEASE PROVIDE A PHOTOGRAPHIC EXAMPLE OF THE LINEAR
 LED LIGHT MOUNTED ON THE SOFFET FROM A LOCATION WHERE
 IT IS IN USE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  