Plan Review Details - Permit 16050780
Plan Review Stops For Permit 16050780
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-23 Cont ID  
Sent By shill Date 2016-06-23 Time 13:05 Rev Time 0.00
Received By shill Date 2016-06-23 Time 13:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-24 Cont ID  
Sent By shill Date 2016-05-24 Time 17:32 Rev Time 0.00
Received By shill Date 2016-05-24 Time 17:32 Sent To  
Notes
2016-05-24 17:37:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 5TH EDITION 2014
  
 1. THE FLOORING UNDERLAYMENT SPECS ARE ILLEGIBLE AND
 HAVE OTHER PERMIT NUMBERS STAMPED ON THEM. PROVIDE THE
 FOLLOWING LEGIBLE TEST REPORTS (CLEAN DOCUMENTS, NOT
 FROM OTHER PERMITS):
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-23 Cont ID  
Sent By mvaldes Date 2016-05-23 Time 18:58 Rev Time 0.00
Received By mvaldes Date 2016-05-23 Time 18:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-20 Cont ID  
Sent By pleduc Date 2016-05-20 Time   Rev Time 0.00
Received By pleduc Date 2016-05-20 Time 15:15 Sent To  
Notes
2016-05-20 15:47:16THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) PROTECT THE FIRE SPRINKLERS AND FIRE ALARM DEVICES
 AND EQUIPMENT.
  
 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-23 Cont ID  
Sent By shill Date 2016-06-23 Time 13:05 Rev Time 0.00
Received By shill Date 2016-06-14 Time 09:39 Sent To  
Notes
2016-06-15 09:39:42RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-24 Cont ID  
Sent By shill Date 2016-05-24 Time 17:37 Rev Time 0.00
Received By shill Date 2016-05-18 Time 15:04 Sent To  
Notes
2016-05-19 15:04:59B09

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-24 Cont ID  
Sent By tklarge Date 2016-05-24 Time 04:34 Rev Time 0.00
Received By tklarge Date 2016-05-24 Time 04:18 Sent To  
Notes
***NONE***