Plan Review Details - Permit 16050779
Plan Review Stops For Permit 16050779
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By jwitmer Date 2016-06-06 Time 16:05 Rev Time 0.00
Received By jwitmer Date 2016-06-06 Time 11:13 Sent To  
Notes
2016-06-06 13:40:53BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050779
 ADD: 2161PALM BEACH LAKES BLVD 1ST FLOOR
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-350-3091
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 06/2016
 ACTION: DENIED
  
 1) SHEET C-1 THE COVERSHEET INDICATES BUILDING
 CONSTRUCTION TYPE AS A III-B/ UNSPRINKLERED BUILDING.
 PLEASE NOTE THIS IS A 4 STORY NON-SPRINKLERED BUILDING
 WITH BUSINESS OCCUPANCIES ABOVE THE A2 RESTARAUNT
 LOCATED ON THE 1ST FLOOR. THE 2014 FBC-B TABLE 503
 REQUIRE THIS BUILDING TO BE A MINIMUM BUILDING TYPE OF
 III-A.
 PLEASE CORRECT THE PLANS. PLEASE PROVIDE HOW THE FIRE
 RATINGS FOR A BUILDING TYPE III-A ARE GOING TO BE MET
 SEE TABLE601 FIRE-RESISTANCE RATING REQUIREMENTS FOR
 BUILDING ELEMENTS (HOURS).
  
 2) SHEET C-1 THE COVERSHEET LIST INTERIOR SEATING AND
 EXTERIOR SEATING BUT THERE ARE NO OCCUPANT LOADS FOR
 THE KITCHEN AREA, BENIND THE BARS( WORK AREAS) NOR FOR
 STORAGE AREAS, PLEASE PROVIDE THE SQUARE FEET FOR EACH
 OF THESE AREAS AND THE OCCUPANT LOADS BASED FROM FBC-B
 TABLE 1004.1.2. SHEET A1.4 THE LIFE SAFETY SHEET LIST A
 OCCUPANT LOAD ALOT LESS THAN THE SEATING COUNT FOUND ON
 THE COVER SHEET. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3) SHEET C-1 THE COVERSHEET ALSO INDICATES THIS IS A
 LEVEL 3 ALTERATION. THE 2014 FBC-EXISTING BUILDING CODE
 904.1 AUTOMATIC SPRINKLER SYSTEMS. AUTOMATIC SPRINKLER
 SYSTEMS SHALL BE PROVIDED IN ALL WORK AREAS WHEN
 REQUIRED BY SECTION 804.2 OR THIS SECTION. THE EXISTING
 BUILDING CODE SECTION 804.2.2 GROUP A OCCUPANCY. WILL
 REQUIRE AUTOMATIC SPRINKLER PROTECTION WHERE ALL OF THE
 FOLLOWING CONDITIONS OCCUR:
 1. THE WORK AREA IS REQUIRED TO BE PROVIDED WITH
 AUTOMATIC SPRINKLER PROTECTION IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING AS APPLICABLE TO NEW
 CONSTRUCTION; AND
 2. THE WORK AREA EXCEEDS 50 PERCENT OF THE FLOOR AREA.
  
 4) SHEET 1.4A THE LIFE SAFETY SHEET:
  
 4A) SHOWS WHAT APPEARS TO BE THE WOMENS RESTROOM WITH 3
 WATER CLOSETS WITHIN THE ROOM. JUST ABOVE THIS ROOM
 THERE ARE AN ADDITIONAL 3 WATER CLOSETS BUT NO DOOR TO
 GAIN ENTRY INTO THIS RESTROOM. 107.2.1.3 ADDITIONAL
 INFORMARION IS REQUIRED.
  
 4B) THE D1 SHEET SHOWS (1) ACCESSIBLE RESTROOM AT THE
 REAR OF THE TENANT SPACE, BUT THIS ROOM IS NOT
 IDENTIFIED ON EITHER SHEET 1.2A NOR 1.4A, PLEASE
 PROVIDE WHAT THE USAGE OF THIS ROOM WILLBE? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4C) THE MAIN ENTRY THERE IS EMERGENCY POWERED EXIT
 LIGHTING BUT TO THE LEFT OF THIS AREA THERE IS A LARGE
 AREA WITHOUT ANY EMERGENCY POWERED BACKUP LIGHTS. THERE
 IS ALSO NO EMERGENCY LIGHTING SOURE IN EITHER OF HE
 LADIES RESTROOMS NOR WHAT APPEARS TO BE THE UNI-SEX
 RESTROOM INTHE REAR OF THE TENANT SPACE. PLEASE PROVIDE
 COMPLIANCE WITH FBC-B 1006.1.
  
 4D) PLEASE SHOW HOW MANY AND WHICH OF THE EXITS HAVE
 LEVEL EXIT DISCHARGES TO THE PUBLIC WAY. MEANING THERE
 ARE NO DROPS IN ELEVATION OVER 1/4 INCH OR THERE IS
 SLOPED OR RAMPED SIDEWALKS, DROPPED CURB CUTS ETC...
 2014 FBC-ACCESSIBILITY CODE 207.1 ACCESSIBLE MEANS OF
 EGRESS SHALL COMPLY WITH THE 2003 IBC SECTION 1007.
 2003 IBC-B 1007.1. WHERE 2 OR MORE MEANS OF EGRESS IS
 REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT
 LESS THAN TWO ACCESSIBLE MEANS OF EGRESS. PLEASE NOTE
 WITH A NON-SPRINKLERED BUILDING THE EXITS NEED TO BE
 1/2 THE OVERALL DIAGONAL DISTANCE APART. 2014 FBC-B
 1015.2.1.
  
 4E) NEITHER SHEET 1.2A NOR 1.4A SHOW COMPLIANCE WITH
 COMPLIANCE WITH 2014 FBC-ACCESS. CODE 226.1. WHERE
 DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF
 FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES
 AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. THE COVERSHEET LIST 292 SEATS X 0.05 = 15
 ACCESSIBLE SEATS.
  
 4F) PLEASE NOTE COMPLIANCE WITH ACCESS. CODE 226.2
 DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED
 TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE
 SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK
 SURFACES.
  
 4G)SHOW COMPLIANCE WITH FBC-ACCESS. CODE 902.1DINING
 SURFACES AND WORK SURFACES SHALL COMPLY WITH 902.2 AND
 902.3.
  
 4G)(1) FBC-ACCESS. 902.2 CLEAR FLOOR OR GROUND SPACE. A
 CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4G)(2) FBC-ACCESS. 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES SHALL BE 28 INCHES AND 34 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 4H) PLEASE SHOW (LIST) HOW UP TO AN ADDITIONAL
 $48,000.00 DOLLARS WILL BE SPENT IN ACCESSIBLE
 UPGRADES. 2014 FBC-ACCESS. CODE 202.4.1
 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 4I) DISCREPANCY IN PLANS BETWEEN SHEET 1.2A AND 1.4A
 WITH THE COOLER FREEZERS. PLEASE PROVIE THE TOATL
 SQUARE FOOTAGE OF THE FREZER . NOTE IN NON-SPRINKLERED
 BUILDINGS THE AGGERIGATE FLOOR AREA OF THE WALKIN-IN
 COOLER CANT BE OVER 400 SQ. FT. FBC-B 2603.4.1.3.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-27 Cont ID  
Sent By vperez Date 2016-05-27 Time 14:27 Rev Time 0.00
Received By vperez Date 2016-05-27 Time 10:14 Sent To  
Notes
2016-05-27 14:50:43INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE SHOW AND REFLECT ON CONSTRUCTION RECORD
 DRAWINGS, COMPLIANCE WITH FBC ENERGY CONSERVATION 2014
 CODE AND METHOD TO ACHIEVE THE REQUIRED MEANS OF
 CONTROL OF LIGHTING, LIGHTING LEVELS ETC. C405.2.1- 2.4
 2. PLEASE PROVIDE SUFFICIENT INFORMATION REGARDING THE
 EXTENT OF THE ALTERATION. CLARIFY THE EXISTING POWER
 OUTLETS IN RELATION TO THE RELOCATED OR NEW OUTLETS
 BEING INSTALLED. FBC 107.3.5 MINIMUM PLAN REVIEW. NOTE
 THAT SHEET 2.0E AND 2.1E ARE VERY VAGUE AS TO REQUIRED
 CIRCUIT DESIGNATION AND LABELING.
 3. LABEL ALL REQUIRED GFCI PROTECTED OUTLET WITHIN THE
 FOOD PREPARATION AREA AND WITHIN 6FT OF ALL SINKS. NEC
 210.8B
 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS OR
 CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-01 Cont ID  
Sent By wjolin Date 2016-06-01 Time 12:02 Rev Time 0.00
Received By wjolin Date 2016-06-01 Time 11:19 Sent To  
Notes
2016-06-01 12:02:062161 PALM BEACH LAKES BOULEVARD
 PERMIT #16050779
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET C1: UPDATE THE CODE LIST TO REFERENCE THE 5TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2012 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET 1.4A: PLANS INDICATE AN OCCUPANT LOAD OF 157
 PERSONS; HOWEVER, THE ACTUAL NUMBER OF SEATS PROVIDED
 IS 306 AND THIS DOES NOT EVEN INCLUDE RESTAURANT STAFF.
 PROVIDE AN ACCURATE OCCUPANCY LOAD CALCULATION PER NFPA
 101. ALL AREAS WILL HAVE OCCUPANT LOADS EXCEEDING 50
 PERSONS AND WILL NEED AT LEAST TWO PROPERLY ILLUMINATED
 EXITS.
  
 PER SECTION NFPA 101 SECTION 43.6.4.1, IN A BUILDING
 WITH REHABILITATION WORK AREAS INVOLVING OVER 50
 PERCENT OF THE AGGREGATE BUILDING AREA, AUTOMATIC
 SPRINKLER SYSTEMS SHALL BE PROVIDED WITH THE
 REQUIREMENTS OF OTHER SECTIONS OF THIS CODE APPLICABLE
 TO NEW CONSTRUCTION FOR THE OCCUPANCY. PER NFPA 101
 SECTION 12.3.5.2 (NEW ASSEMBLY OCCUPANCY) ANY BUILDING
 CONTAINING ONE OR MORE ASSEMBLY OCCUPANCIES WHERE THE
 AGGREGATE OCCUPANT LOAD OF THE ASSEMBLY OCCUPANCIES
 EXCEEDS 300 SHALL BE PROTECTED BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM.
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 INSUFFICIENT EXIT SIGNAGE AND EMERGENCY LIGHTING
 PROVIDED. EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR
 A MINIMUM OF 1.5 HOURS IN THE EVENT OF FAILURE OF
 NORMAL LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS/GATES TO RELEASE THE LOCK/LATCH. NO
 OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE.
  
 NO ENGINEERED FIRE ALARM PLANS SUBMITTED. PER NFPA 101
 SECTION 12.3.4.3.3, PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES AS ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM
 NOTIFICATION BY VISIBLE SIGNALS AND VOICE
 ANNOUNCEMENTS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-06 Cont ID  
Sent By jwitmer Date 2016-06-06 Time 16:05 Rev Time 0.00
Received By jwitmer Date 2016-05-18 Time 15:21 Sent To  
Notes
2016-05-19 15:21:44C36

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-06-06 Cont ID  
Sent By jwitmer Date 2016-06-06 Time 16:05 Rev Time 0.00
Received By jwitmer Date 2016-06-06 Time 11:13 Sent To  
Notes
2016-06-06 12:16:25 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-23 Cont ID  
Sent By jvalido Date 2016-05-23 Time 12:53 Rev Time 0.00
Received By jvalido Date 2016-05-23 Time 09:30 Sent To  
Notes
2016-05-23 12:50:22WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 (1) AHU #1 - AS PER TRANE DUCULATOR 12"X12" [email protected]
 FRICTION LOST PER 100' IS 850 CFM. PLAN IS SHOWING 2000
 CFM DUMPING INTO A 12"X12" DUCT.
 AHU ON EQUIPMENT SCHEDULE IS SHOWING 1800 CFM. DESIGN
 CFM ON PLANS IS 2000 CFM.
 RETURN AIR GRILL ON PLANS IS A200. AS PER CEILINGOUTLET
 SCHEDULE RETURMN AIR GRILL SHOULD BE D 2000.
 CHECK YOUR CALCULATIONS AND MAKE THE CORRECTIONS.
 ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR.
 (AS PER FBC MECHANICAL CODE 2014)
  
 (2) AHU #2 - PLANS SHOW RETURN AIR IS 1300CFM. TOTAL
 SUPPLY AIR IS 2800.
 AS PER TRANE DUCULATOR 12"X12" [email protected] FRICTION LOST
 PER 100' IS 850 CFM. PLAN IS SHOWING 2800 CFM DUMPING
 INTO A 12"X12" DUCT.
 CHECK YOUR CALCULATIONS AND MAKE THE CORRECTIONS.
 ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR.
 (AS PER FBC MECHANICAL CODE 2014)
  
 (3) AHU #3 - PROVIDE RETURN AIR.
 ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR.
 (AS PER FBC MECHANICAL CODE 2014)
  
 (4) AHU #4 - AHU ON EQUIPMENT SCHEDULE IS SHOWING 1800
 CFM. DESIGN CFM ON PLANS IS 2000 CFM.
 DRAWING OF SUPPLY DUCT ON PLANS SHOW PHYSICAL REDUCTION
 IN DUCT SIZES BUT DUCT IS IDENTIFIED AS 18" DUCT
 THROUGHOUT.
 CHECK YOUR CALCULATIONS AND MAKE THE CORRECTIONS.
 ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR.
 (AS PER FBC MECHANICAL CODE 2014)
  
 (5) AHU #5 - AHU ON EQUIPMENT SCHEDULE IS SHOWING 1800
 CFM. DESIGN CFM ON PLANS IS 2000 CFM.
 PROVIDE ON PLANS RETURN AIR.
 SHOW ALL OUTSIDE AIR DUCTS FOR AHU.
 ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR.
 (AS PER FBC MECHANICAL CODE 2014)
  
 CHANGE #2 ON EQUIPMENT SCHEDULE TO ALL SMOKE DETECTORS
 WILL BE INSTALLED IN RETURN AIR. (AS PER FBC MECHANICAL
 CODE 2014)
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-24 Cont ID  
Sent By tklarge Date 2016-05-24 Time 13:49 Rev Time 0.00
Received By tklarge Date 2016-05-24 Time 04:38 Sent To  
Notes
2016-05-24 13:48:531) SHT.3.0 P REFERS TO THE 2007 & THE 2010 FBC. THE
 CODE IN EFFECT IS THE 2014 FBC. REVISE THE NOTES.
 2) IDENTIFY THE NEW WAIT STATION ON THE PLAN WHERE THE
 PLUMBING WORK IS BEING DONE. FBC 107.2.1.
 3) THE NOTES REFER TO A PIZZA OVEN BUT I DID NOT SEE
 THIS LISTED ON THE EQUIPMENT SCHEDULE. CLARIFY.
 4) SHOW THE CLEAR INSIDE DIMENSIONS OF THE ACCESSIBLE
 TOILET ROOM ON THE PLANS. THE MINIMUM WIDTH IS 85
 INCHES IF ALL FIXTURES ARE ON THE SAME WALL AND THE
 ROOM IS BUILT PERFECT. 86 INCHES ALLOWS FOR TOLERANCES.
 5) THE LAYOUT OF THE SANITARY AND GREASE RISERS ON SHT.
 P3.1 P DO NOT MATCH THE PLAN VIEW ON 3.0 P. CLARIFY.
 6) SHOW THE TERMINATION POINT OF THE VENT FOR THE MS
 FIXTURE SHT.3.1 P.
 7) SHT. C-1 SHOWS THE NUMBER OF SEATS AS 292 AND ON
 SHT.3.2 P THE GREASE INTERCEPTOR CALCULATION SHOWS 150
 SEATS.CLARIFY.
 8) SHT.1.0 A - NOTE #21 REFERS TO THE REPAIR OF
 PLUMBING IN THE KITCHEN AREA. CLARIFY AS TO WHAT THE
 SCOPE OF WORK IS IN THE KITCHEN.
 9) CLEARLY IDENTIFY THE NEW ACCESSIBLE RESTROOM ON THE
 PLANS.
 10) THE PLANS REFER TO WORK TO BE DONE IN THE LADIES
 ROOM BUT ARE VAGUE. CLEARLY DESCRIBE THE SCOPE OF WORK
 TO BE DONE IN THE LADIES ROOM. THE SAME APPLIES TO THE
 MEN'S ROOM.
 11) HOW IS ACCESSED GAINED TO THE THREE WATER CLOSETS
 IN THE WOMEN'S RESTROOM BY THE THE OFFICE? CLARIFY.
 12) SHOW THE GAS LINE ON SHT.3.0 P.
 13) THE GAS LOAD CALCULATIONS SHOW A BTU LOAD OF
 1,052,000 BTU'S BUT MY CALCULATIONS ARRIVE AT 1,154,000
 BTU' S FOR THE 2 PSI LINE WITH THE TWO PATIO HEATERS
 INCLUDED, CLARIFY.
 14) SHT. 3.1 P - THE GAS LOAD CALCULATIONS SHOW
 1,052,000 BTU'S ON THE 2 PSI SYSTEM BUT THE GAS RISER
 SHOWS 880 K. CLARIFY.
 15) SHT.3.1 P - THE PLAN NOTES A DISTANCE OF 180 FT.
 FOR THE 2 PSI SYSTEM BUT MY CALCULATIONS SHOW 170 FT.
 CLARIFY.
 16) SHT. 3.1 P - THE BTU LOAD FOR THE LOW PRESSURE
 SYSTEM SHOWN ON THE PLAN DOES NOT CORRELATE TO THE SUM
 OF ALL THE APPLIANCES. MY CALCULATIONS COME TO 838 K,
 NOT 722K. CLARIFY.
 17) THE LOW PRESSURE SYSTEM SEEMS TO BE OVERSIZED FOR
 THE BTU LOAD WHEN USING TABLE 402.4 (4) AS REFERENCED.
 CLARIFY. HYBRID PRESSURE SYSTEMS SHALL BE SIZED IN
 ACCORDANCE WITH 2014 FGC SEC.402.4.3.
 18) SHOW THE LOCATION OF THE TANKLESS WATER HEATER ON
 THE PLANS.
 19) CLEARLY SHOW ON THE GAS PLANS WHAT IS NEW AND
 EXISTING.
 20) SUBMIT A WATER RISER DIAGRAM FOR ANY CHANGES TO THE
 WATER DISTRIBUTION SYSTEM.FBC 107.1.
 21) ALL GAS EQUIPMENT SHALL BE LISTED AND LABELED PER
 2014 FGC SEC.301.3. SUBMIT SPECIFICATIONS.
 22) SUBMIT CALCULATIONS FOR COMBUSTION AIR. FGC
 SEC.304.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  