Plan Review Details - Permit 16050763
Plan Review Stops For Permit 16050763
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-20 Cont ID  
Sent By sathomas Date 2016-05-20 Time 15:12 Rev Time 0.00
Received By sathomas Date 2016-05-20 Time 15:00 Sent To M
Notes
2016-05-20 15:11:19PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL BE
 LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10
 FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST
 SYSTEM. THE DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE
 THE FLOOR AND SHALL CLEARLY IDENTIFY THE HAZARD
 PROTECTED.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 PROVIDE AN 8? TALL STEEL BAFFLE OR PROVIDE 16? OF SPACE
 BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE
 ADJACENT EQUIPMENT.
  
 UPON INSPECTION, CONTRACTOR TO PROVIDE INSTALLATION
 MANUAL.
  
 SANDRA THOMAS 7805
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-27 Cont ID  
Sent By ccole Date 2016-05-27 Time 13:48 Rev Time 0.00
Received By ccole Date 2016-05-18 Time 15:00 Sent To  
Notes
2016-05-19 15:00:50ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-05-27 Cont ID  
Sent By ccole Date 2016-05-27 Time 13:48 Rev Time 0.00
Received By ccole Date 2016-05-27 Time 13:42 Sent To  
Notes
***NONE***