Plan Review Details - Permit 16050731
Plan Review Stops For Permit 16050731
Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2016-07-11 Cont ID  
Sent By scaldero Date 2016-07-11 Time 10:34 Rev Time 0.00
Received By scaldero Date 2016-07-11 Time 10:34 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-06-27 Cont ID  
Sent By ccole Date 2016-06-28 Time 07:59 Rev Time 0.00
Received By scaldero Date 2016-06-27 Time 11:02 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-06-15 Cont ID  
Sent By pleduc Date 2016-06-15 Time   Rev Time 0.00
Received By pleduc Date 2016-06-15 Time 16:50 Sent To PC
Notes
2016-06-15 16:54:202ND REVIEW
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE PERMIT PLAN IS SUBMITTED UNDER THE ARCHITECT AND
 THE ARCHITECT'STITLE BLOCK AND IS A VIOLATION OF
 FLORIDA STATUTE AS IS REJECTED.
  
 COMPLIED
  
 2) THE SHOP DRAWINGS ARE TO BE SUBMITTED UNDER A
 QUALIFIED ENGINEER'S REVIEW AND/OR TITLE BLOCK.
  
 COMPLIED.
  
 3) THE SUBMITTED PLANS ARE TOO SMALL AND UNREADABLE.
 PROVIDE LARGER AND READABLE PLANS.
  
 DID NOT COMPLY, SEE ALSO MECHANICAL COMMENT.
  
 4) SHEET M 1 - THE HORIZONTAL VIEW INDCATES INCOMPLETE
 HOOD VENT COVERAGE AS IT SHOWS IT SHORT ON ONE SIDE OF
 COVERING THE PROPOSED EQUIPMENT. THE HOOD VENT SHALL
 COVER ALL EQUIPMENT PER NFPA AND MECHANICAL CODES.
  
 LARGER VIEW WITH MORE CLARITY MAY ADDRESS THIS ISSUE.
  
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-20 Cont ID  
Sent By pleduc Date 2016-05-20 Time   Rev Time 0.00
Received By pleduc Date 2016-05-20 Time 15:50 Sent To M
Notes
2016-05-20 16:15:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE PERMIT PLAN IS SUBMITTED UNDER THE ARCHITECT AND
 THE ARCHITECT'STITLE BLOCK AND IS A VIOLATION OF
 FLORIDA STATUTE AS IS REJECTED.
  
 2) THE SHOP DRAWINGS ARE TO BE SUBMITTED UNDER A
 QUALIFIED ENGINEER'S REVIEW AND/OR TITLE BLOCK.
  
 3) THE SUBMITTED PLANS ARE TOO SMALL AND UNREADABLE.
 PROVIDE LARGER AND READABLE PLANS.
  
 4) SHEET M 1 - THE HORIZONTAL VIEW INDCATES INCOMPLETE
 HOOD VENT COVERAGE AS IT SHOWS IT SHORT ON ONE SIDE OF
 COVERING THE PROPOSED EQUIPMENT. THE HOOD VENT SHALL
 COVER ALL EQUIPMENT PER NFPA AND MECHANICAL CODES.
  
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-07-11 Cont ID  
Sent By scaldero Date 2016-07-11 Time 10:34 Rev Time 0.00
Received By scaldero Date 2016-07-05 Time 09:33 Sent To  
Notes
2016-07-05 09:34:15HAND DELIVERED TO CHRIS COLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-28 Cont ID  
Sent By ccole Date 2016-06-28 Time 07:59 Rev Time 0.00
Received By ccole Date 2016-06-23 Time 13:47 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-15 Cont ID  
Sent By pleduc Date 2016-06-15 Time   Rev Time 0.00
Received By pleduc Date 2016-06-09 Time 10:30 Sent To  
Notes
2016-06-10 10:31:05RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-24 Cont ID  
Sent By ccole Date 2016-05-24 Time 14:05 Rev Time 0.00
Received By ccole Date 2016-05-18 Time 11:44 Sent To  
Notes
2016-05-18 11:44:53ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-07-05 Cont ID  
Sent By ccole Date 2016-07-05 Time 09:55 Rev Time 0.00
Received By ccole Date 2016-07-05 Time 09:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-06-28 Cont ID  
Sent By ccole Date 2016-06-28 Time 07:29 Rev Time 0.00
Received By ccole Date 2016-06-28 Time 07:28 Sent To FIRE
Notes
2016-06-28 07:35:403RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050731
 6/28/16
  
 1) THE TYPE II EXHAUST FAN SHALL TERMINATE 30" ABOVE
 THE ROOF SURFACE- SEE SECTION 506.4.2(4).
  
 2) AS PREVIOUSLY REQUESTED PROVIDE AN EQUIPMENT
 SCHEDULES ON THE PLAN THAT INCLUDES THE MAKE AND MODEL
 OF THE FAN. THE SUBMITTED NOA HAS MULTIPLE MODELS AND
 SIZES. PLEASE CIRCLE, HIGHLIGHT, OR OTHERWISE MARK THE
 MODEL AND SIZE OF THE FAN AND ALL OTHER APPLICABLE
 DETAILS ON THE NOA.
  
 3) THE EXHAUST APPEARS TO BE TERMINATING LESS THAN 30"
 FROM THE VERTICAL WALL ABOVE THE ROOF- SECTION
 506.4.2(5). PLEASE NOTE THAT IF THE WALL IS ALSO A FIRE
 WALL BETWEEN TWO PROPERTIES, THE EXHAUST TERMINATION
 SHALL NOT BE LESS THAN 10' FROM THE WALL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-06-13 Cont ID  
Sent By ccole Date 2016-06-13 Time 11:00 Rev Time 0.00
Received By ccole Date 2016-06-13 Time 11:00 Sent To  
Notes
2016-06-13 11:12:182ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050731
 6/13/16
  
 1) INDICATE THE EXHAUST FAN TERMINATION HEIGHT ABOVE
 THE ROOF SURFACE PER SECTION 506.4.2(4).
  
 2) PROVIDE AN EQUIPMENT SCHEDULE FOR THE FAN AND SUBMIT
 A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA.
  
 3) PLEASE ENLARGE ALL PRINT AND SCHEDULES SHOWN IN
 DETAILS #1, 2, & 3- SECTION 107.2.1 WPB AMENDMENTS TO
 THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-24 Cont ID  
Sent By ccole Date 2016-05-24 Time 13:37 Rev Time 0.00
Received By ccole Date 2016-05-24 Time 13:37 Sent To  
Notes
2016-05-24 14:05:211ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050731
 5/24/16
  
 1) SUBMIT COMPLETE DRAWINGS, EQUIPMENT SCHEDULES, AND
 EXHAUST AND AIR BALANCE CALCULATIONS FOR THE PROPOSED
 TYPE II HOOD. THE SUBMITTED DRAWINGS ARE NOT ACCEPTABLE
 BECAUSE THEY COPIES, ARE IMCOMPLETE, AND DO NOT BEAR
 THE ARCHITECT'S RAISED SIGNATURE AND SEAL. SHOP
 DRAWINGS FOR THE PROPOSED EXHAUST HOOD MAY BE SUBMITTED
 BUT THEY MUST BE REVIEWED AND APPROVED
 BY THE ARCHITECT OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  