Plan Review Details - Permit 16050650
Plan Review Stops For Permit 16050650
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-13 Cont ID  
Sent By cthroop Date 2016-06-13 Time 13:48 Rev Time 0.00
Received By cthroop Date 2016-06-10 Time 16:07 Sent To  
Notes
2016-06-13 13:52:44BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-7918
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 DATE: 6/13/16
 ACTION: FAIL
  
 1. ROOFING PERMIT REQUIRED.
 2. ENERGY CALCULATIONS REQUIRED.
 3. P.B.C. IMPACT FEES REQUIRED.
 4. TWO TYPES OF ROOFING SYSTEMS FOR MAIN ROOF SHOWN ON
 PLANS. PLEASE CLARIFY.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-19 Cont ID  
Sent By mvaldes Date 2016-05-19 Time 16:00 Rev Time 0.00
Received By mvaldes Date 2016-05-19 Time 14:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-05-18 Cont ID  
Sent By gjohnson Date 2016-05-18 Time 17:42 Rev Time 0.00
Received By gjohnson Date 2016-05-18 Time 17:42 Sent To  
Notes
2016-05-18 17:44:50GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-13 Cont ID  
Sent By cthroop Date 2016-06-13 Time 13:48 Rev Time 0.00
Received By cthroop Date 2016-05-16 Time 09:39 Sent To  
Notes
2016-05-17 09:39:52R22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-06-13 Cont ID  
Sent By cthroop Date 2016-06-13 Time 13:44 Rev Time 0.00
Received By cthroop Date 2016-06-13 Time 13:44 Sent To  
Notes
2016-06-13 13:46:03BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-7918
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 DATE: 6/13/16
 ACTION: FAIL
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-07 Cont ID  
Sent By jvalido Date 2016-06-07 Time 16:53 Rev Time 0.00
Received By jvalido Date 2016-06-07 Time 16:38 Sent To  
Notes
2016-06-07 16:53:10WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
 107.1 GENERAL- 107.2 CONSTRUCTION DOCUMENTS- 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL PLANS
  
 FLORIDA ENERGY CODE FBC 2014 - SECTION R202 RENOVATED
 BUILDINGS - A RESIDENTIAL OR NONRESIDENTIAL BUILDING
 UNDERGOING ALTERATION THAT VARIES INSULATION, HVAC
 SYSTEMS, WATER HEATING SYSTEMS, OR EXTERIOR ENVELOPE
 CONDITIONS, PROVIDED THE ESTIMATED COST OF RENOVATION
 EXCEEDS 30 PERCENT OF THE ASSESSED VALUE OF THE
 STRUCTURE.
  
 (2) PROVIDE ENERGY CALCULATIONS.
 (3) PROVIDE HEAT LOAD CALCULATIONS.
 (4) PROVIDE AHRI
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-18 Cont ID  
Sent By gjohnson Date 2016-05-18 Time 17:41 Rev Time 0.00
Received By gjohnson Date 2016-05-18 Time 17:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-06-13 Cont ID  
Sent By cthroop Date 2016-06-13 Time 13:46 Rev Time 0.00
Received By cthroop Date 2016-06-13 Time 13:46 Sent To  
Notes
2016-06-13 13:48:38BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-7918
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 DATE: 6/13/16
 ACTION: FAIL
  
 1. CONFLICT EXISTS BETWEEN ROOF SYSTEMS. SEE PG. A.05 &
 A.06. TWO SEPERATE ROOF SYSTEMS ARE SHOWN. 1. CEMENT
 TILE ROOF. 2. METAL ROOF. PLEASE CLARIFY.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2016-05-31 Time   Rev Time  
Received By   Date 2016-05-31 Time   Sent To B
Notes
2016-05-31 10:49:211. NEED SURVEY(2)
 2. NEED PROJECTION WITHIN THE 5FT. OVERHANG CANNOT
 PROJECT MORE THAN 3FT. WITHIN THE SETBACK 94-305.
 3. NEED SEPARATE DRIVEWAY PERMIT
 4. NO MEASUREMENTS FOR A/C UNITS INTO A SETBACK CANNOT
 PROJECT MORE THAN 18IN. INTO A SETBACK 94-305
 5. NO MEASUREMENTS FOR DRIVEWAY INTO THE SIDE SETBACK
 6. NEED FRONT SETBACK FROM THE CLOSEST PART OF THE
 HOUSE.
 7. NEED A LANDSCAPE PLAN BECAUSE PROJECT EXCEEDS 50% OF
 THE VALUE OF THE PROPERTY 94-441C(2)
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  