Plan Review Details - Permit 16050640
Plan Review Stops For Permit 16050640
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-01 Cont ID  
Sent By jwitmer Date 2016-08-01 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2016-08-01 Time 11:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-01 Cont ID  
Sent By jwitmer Date 2016-06-01 Time 14:45 Rev Time 0.00
Received By jwitmer Date 2016-06-01 Time 13:50 Sent To  
Notes
2016-06-01 14:27:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050640
 ADD: 525 OKEECHOBEE BLVD. 9TH FLOORSUITE # 900
 CONT: HOLT LEE CONSTRUCTION
 TEL: 954-725-4881
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 01/ 2016
 ACTION: DENIED
  
 1) THE SUITE NUMBER IS NOT GIVEN ON THE PERMIT
 APPLICATION NOR PROVIDED IN THE TITLEBLOCK. 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJECT.
  
 2) PLEASE NOTE THIS IS A HIGHRISE BUILDING THAT
 REQUIRES FIRE SPRINKLERS PER FBC-B 403.3. THERE IS AN
 EXISITNG FIRE SPRINKLER SYSTEM WITHIN THE TENANT SPACE.
 IF LESS THAN 50 HEADS NEED TO BE MOVED THE FIRE
 SPRINKLER CONTRACTOR CAN DRAW THE PLANS, OTHERWISE THE
 FIRE SPRINKLER PLANS NEED TO BE ENGINEERED. WITHIN THE
 PLANS SUBMITTED THERRE WAS NO FIRE SPRINKLER PLANS.
 PLANS SHALL COMPLY WITH FBC-B 903.2.11.3.1.
  
 3A) SHEET A1.1 SHOWS A ASSEMBLY USAGE IN THE RECEPTION
 AND CONFERENCE ROOM AREAS. THESE ROOMS WILL HAVE AN
 OCCUPANT LOAD OF GREATER THAN 50 REQUIRING (2) MEANS OF
 EGRESS. THE DOOR LABELED NUMBER 9 WOULD BE THE 2 ND
 REQUIRED MEANS OF EGRESS FROM THIS AREA AND THE DOOR
 NEEDS TO SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE
 SERVING A ROOM OR AREA CONTAINING AN OCCUPANT LOAD OF
 50 OR MORE PERSONS. FBC-B 1008.1.2.
  
 3B) NOTE SHEET E2.1 THE EGRESS DIRECTIONAL LIGHT CLOSE
 TO THE BREAK ROOM WILL NEED TO BE RE-DIRECTED TO THE
 DOOR # 9 FOR THE 2ND MEANS OF EGRESS FOR THIS AREA.
 FBC-B TABLE 1015.1.
  
 4) SHEET A1.1 THE DOOR # 9 WILL ALSO NEED TO COMPLY
 WITH FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 5) SHEET A1.1 FILE ROOM 947 & 948 DOES THE FLOOR
 LOADING OF THIS FILE ROOM EXCEED THE SAFE FLOOR LIMITS
 WITHOUT ADDITIONAL FLOOR FRAMING. THE FLOOR LOADING IN
 OFFICE AREAS LIVE LOADS IS BUSINESS AREAS 50 SQ. FT.
 WHEREAS FILE ROOMS SHALL BE DESIGNED FOR HEAVIER LOADS
 ANTICIPATED USAGE. FBC-B TABLE 1607.1.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION15110652
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-13 Cont ID  
Sent By mvaldes Date 2016-07-13 Time 14:35 Rev Time 0.00
Received By mvaldes Date 2016-07-13 Time 14:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-23 Cont ID  
Sent By mvaldes Date 2016-05-23 Time 10:59 Rev Time 0.00
Received By mvaldes Date 2016-05-23 Time 09:57 Sent To  
Notes
2016-05-23 11:24:01JOB PERMIT NUMBER: 16050640
 JOB ADDRESS: 525 OKEECHOBEE BLVD
 WEST PALM BEACH FLORIDA (9TH FLOOR)
 DATE: MAY 23 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - BREAKROOM AND COFFEE ROOMS RECEPTACLE OUTLET SHALL
 HAVE GFCI PROTECTION NEC 210.8(5)(6) NEAR 6? OF SINKS
 AND WET LOCATIONS INDOOR.
 - THE APPLICABLE CODE IS THE NEC 2011, THE COVER PAGE
 REFERENCES THE NEC 2014 AND E0.1 SHOWS NO CURRENT YEAR.
 - ADD THE CODE SECTION NEC 300.22 TO NOTE ?CEILING IS A
 COMMON PLENUM NO COMBUSTIBLE MATERIAL ALLOWED.?
 - RUNS TO FLOOR BOXES MUST BE IN SEPARATE RACEWAYS AND
 ENCLOSURES UNLESS CONDUCTORS PROVIDED WITH SAME VOLTAGE
 INSULATION RATING IN ACCORDANCE WITH NEC 300.3(C)(1).
 - NEC 410.36(B) SUPPORT OF LUMINAIRES IN SUSPENDED
 CEILINGS SHALL BE FASTENED BY MECHANICAL MEANS TO
 FRAMING MEMBERS THAT WILL BE SECURELY ATTACHED TO THE
 BUILDING STRUCTURE. NEC 300.11 WIRING IN THE FIRE RATED
 ASSEMBLIES SHALL BE SUPPORTED BY AN INDEPENDENT SUPPORT
 WIRE DISTINGUISHABLE AND PART OF THE CEILING ASSEMBLY.
 - RISER DIAGRAM TO INCLUDE NEC 110.16 ARC-FLASH HAZARD
 WARNING LABELS AND NEC 110.24 AVAILABLE FAULT CURRENT
 MARKINGS, BOTH IDENTIFICATIONS SHALL BE SUITABLE FOR
 THE ENVIRONMENT INVOLVED.
 - PANEL SCHEDULE NEEDS TO SHOW AIC RATING OF OCPD AND
 ELECTRICAL APPARATUS MUST SHOW SCR OF EQUIPMENT. NEC
 110.9, 110.10
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-26 Cont ID  
Sent By wjolin Date 2016-07-14 Time 13:46 Rev Time 0.00
Received By wjolin Date 2016-07-14 Time 13:32 Sent To  
Notes
2016-07-14 13:46:16525 OKEECHOBEE BOULEVARD - 9TH FLOOR
 PERMIT #16050640
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****I WILL CHANGE MY REVIEW FROM FAIL TO
 PASS WITH PROVISO TODAY. IF RBK IS BOTH THE SPRINKLER
 INSTALLER AND ENGINEER OF RECORD FOR THE SYSTEM, THEY
 CAN SUBMIT SIGNED/SEALED DRAWINGS UNDER YOUR MASTER
 PERMIT #16070656 TO ENSURE THE REQUIREMENTS OF THE
 FLORIDA ADMINISTRATIVE CODE HAVE BEEN MET.
  
 REPEAT COMMENT - GENERAL: ENGINEERED FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-17 Cont ID  
Sent By wjolin Date 2016-05-17 Time 16:56 Rev Time 0.00
Received By wjolin Date 2016-05-17 Time 14:20 Sent To  
Notes
2016-05-17 15:17:59525 OKEECHOBEE BOULEVARD - 9TH FLOOR
 PERMIT #16050640
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 GENERAL: ENGINEERED FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 SHEET A1.1: THE CLUSTER OF CONFERENCE ROOMS CREATES AN
 ASSEMBLY OCCUPANCY THAT IS NOT FIRE SEPARATED FROM THE
 BUSINESS OCCUPANCY SO ALL EXIT ACCESS DOORS (1, 9, 12,
 36, 55 ETC.) WILL NEED TO BE EQUIPPED WITH PANIC
 HARDWARE. FOR ASSEMBLYL OCCUPANCIES WITH AN OCCUPANT
 LOAD OF 50 OR MORE PERSONS, PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE.
  
 SHEET A1.1: DOOR #9 SWINGS AGAINST THE FLOW OF TRAFFIC.
  
 SHEET A1.1: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING
 FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM
 POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM
 THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET FA1.1: PLAN INDICATES THE USE OF HORN-STROBE
 DEVICES. THIS IS AN EXISTING HIGH-RISE EQUIPPED WITH
 VOICE EVACUATION.
  
 SHEET FA1.1: NO NOTIFICATION PROVIDED IN FILE ROOMS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-01 Cont ID  
Sent By jwitmer Date 2016-08-01 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2016-07-06 Time 14:26 Sent To  
Notes
2016-07-06 14:26:36C04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-01 Cont ID  
Sent By jwitmer Date 2016-06-01 Time 14:45 Rev Time 0.00
Received By jwitmer Date 2016-05-16 Time 14:07 Sent To  
Notes
2016-05-16 14:07:34C02
 TRAVELLING WITH 16050639

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-06-01 Cont ID  
Sent By jwitmer Date 2016-06-01 Time 14:45 Rev Time 0.00
Received By jwitmer Date 2016-06-01 Time 14:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-01 Cont ID  
Sent By hmoser Date 2016-07-29 Time 09:20 Rev Time 0.00
Received By hmoser Date 2016-07-29 Time 09:09 Sent To  
Notes
2016-07-29 09:20:10PLAN DENIED
 BUILDING HAS SMOKE EVAC.
 1) REFER TO SECTION 607.5.2 FIRE BARRIERS
 EXCEPTION # 2 FBC(M) 2014
 2) SHOW THE PATH OF TRAVEL THE SMOKE WILL TAKE
 ON THE PLAN.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-05-19 Cont ID  
Sent By jvalido Date 2016-05-19 Time 14:31 Rev Time 0.00
Received By jvalido Date 2016-05-19 Time 09:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-07-30 Cont ID  
Sent By tklarge Date 2016-07-30 Time 04:13 Rev Time 0.00
Received By tklarge Date 2016-07-30 Time 03:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-23 Cont ID  
Sent By tklarge Date 2016-05-23 Time 14:54 Rev Time 0.00
Received By tklarge Date 2016-05-23 Time 14:19 Sent To  
Notes
***NONE***