Plan Review Details - Permit 16050626
Plan Review Stops For Permit 16050626
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-16 Cont ID  
Sent By ccole Date 2016-05-16 Time 14:56 Rev Time 0.00
Received By ccole Date 2016-05-16 Time 13:08 Sent To  
Notes
2016-05-16 13:08:56REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-17 Cont ID  
Sent By ccole Date 2016-05-17 Time 12:37 Rev Time 0.00
Received By ccole Date 2016-05-17 Time 12:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-16 Cont ID  
Sent By ccole Date 2016-05-16 Time 14:56 Rev Time 0.00
Received By ccole Date 2016-05-16 Time 14:56 Sent To  
Notes
2016-05-16 15:01:031ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050626
 5/16/16
  
 1) THE PRINT INDICATING THE SUPPLY CFM'S ON THE PLAN IS
 TOO SMALL TO READ AND SCAN FOR PUBLIC RECORD- SEE
 SECTION 107.2.4.1 WPB AMENDMENTS TO THE FBC.
 2) IDENTIFY ALL ROOMS AND SPACES ON THE PLAN AND
 PROVISDE A BALANCED RETURN AIR SYSTEM- SECTION 601.5
 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER