Plan Review Details - Permit 16050622
Plan Review Stops For Permit 16050622
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-27 Cont ID  
Sent By shill Date 2016-05-27 Time 13:01 Rev Time 0.00
Received By shill Date 2016-05-27 Time 13:01 Sent To  
Notes
2016-05-27 13:01:53REVISION REQUIRED - SUBMIT A DETAIL FOR BREAK AREA SINK
 IN COMPLIANCE WITH FBC 5TH ACCESSIBILITY 606.
 SHOW CLEAR FLOOR SPACE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-05-19 Cont ID  
Sent By shill Date 2016-05-19 Time 17:41 Rev Time 0.00
Received By shill Date 2016-05-19 Time 17:41 Sent To  
Notes
2016-05-19 17:49:20REVISION REQUIRED - SUBMIT A DETAIL FOR BREAK AREA SINK
 IN COMPLIANCE WITH FBC 5TH ACCESSIBILITY 606.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By vperez Date 2016-06-01 Time 11:50 Rev Time 0.00
Received By vperez Date 2016-06-01 Time 11:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-20 Cont ID  
Sent By vperez Date 2016-05-20 Time 14:02 Rev Time 0.00
Received By vperez Date 2016-05-20 Time 14:02 Sent To  
Notes
2016-05-20 14:10:47INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE A REVISED PANEL LOAD CALCULATION TO
 REFLECT NEW 4TON AC UNIT. FBC 107.3.5
 2. LABEL ALL RECEPTACLES WITHIN 6FT OF SINKS TO BE GFCI
 PROTECTED PER NEC 210.8B7
 3. ALL LOW VOLTAGE SYSTEMS TO BE PERMITTED SEPARATELY,
 A NOTE WILL SUFFICE.
 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-17 Cont ID  
Sent By wjolin Date 2016-05-17 Time 12:41 Rev Time 0.00
Received By wjolin Date 2016-05-17 Time 12:35 Sent To  
Notes
2016-05-17 12:41:49500 SOUTH AUSTRALIAN AVENUE - SUITE #700
 PERMIT #16050622
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND/OR FIRE
 ALARM SYSTEM.
  
 PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 "FIRE BARRIER-PROTECT ALL OPENINGS." CHARACTERS SHALL
 BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-01 Cont ID  
Sent By cpuell Date 2016-06-01 Time 16:00 Rev Time 0.00
Received By cpuell Date 2016-05-26 Time 14:23 Sent To  
Notes
2016-05-26 14:23:21B04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-23 Cont ID  
Sent By lmarchan Date 2016-05-23 Time 10:15 Rev Time 0.00
Received By lmarchan Date 2016-05-16 Time 12:54 Sent To  
Notes
2016-05-16 12:54:15B03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-05-20 Cont ID  
Sent By shill Date 2016-05-20 Time 14:16 Rev Time 0.00
Received By shill Date 2016-05-20 Time 14:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By jvalido Date 2016-06-01 Time 15:27 Rev Time 0.00
Received By jvalido Date 2016-06-01 Time 15:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-17 Cont ID  
Sent By jvalido Date 2016-05-17 Time 18:09 Rev Time 0.00
Received By jvalido Date 2016-05-17 Time 17:50 Sent To  
Notes
2016-05-17 18:06:06CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE EQUIPMENT SCHEDULE ( TO INCLUDE BRAND,
 MODEL #, TOTAL CFM, TOTAL BTU)
 (2) PROVIDE HANGING DETAIL OF AIR HANDLER EQUIPMENT
 (3) PROVIDE LOCATION OF CONDENSERS
 (4) PROVIDE CONDENSER TIE DOWN DETAIL
 (5) PROVIDE CFM QUANTITIES OF ALL SUPPLY DROPS.
 (6) PROVIDE O/A CALCULATIONS AND QUANTITIES PER AHU.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By gjohnson Date 2016-06-01 Time 13:19 Rev Time 0.00
Received By gjohnson Date 2016-06-01 Time 13:18 Sent To  
Notes
2016-06-01 14:03:51GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  
 PLUMBING PROVISO
  
 1. HOT OR TEMPERED WATER SHALL BE SUPPLIED TO SINK PER
 FBC PL 607.1
  
 2. SINK SHALL COMPLY WITH FLORIDA BUILDING CODE 5TH
 EDITION (2014) ACCESSIBILITY 606.2 -606.3

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-18 Cont ID  
Sent By gjohnson Date 2016-05-18 Time 17:17 Rev Time 0.00
Received By gjohnson Date 2016-05-18 Time 17:17 Sent To  
Notes
2016-05-18 17:25:591ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SANITARY AND WATER RISER DIAGRAM PER WPB
 AMEND TO FBC SEC107.3.5.1.3(13)
  
 2. PROVIDE DETAILED SCOPE OF PLUMBING WORK. PER WPB
 AMEND TO FBC SEC107.2.1
  
 3. BREAKROOM SINK SHALL COMPLY WITH FBC ACC SEC. 606
 SHOW DIMENSIONS ON PLAN PER WPB AMEND TO FBC SEC107.2.1