Plan Review Details - Permit 16050607
Plan Review Stops For Permit 16050607
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-29 Cont ID  
Sent By skennedy Date 2016-07-29 Time 12:53 Rev Time 0.00
Received By skennedy Date 2016-07-29 Time 12:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-21 Cont ID  
Sent By cthroop Date 2016-06-21 Time 15:28 Rev Time 0.00
Received By cthroop Date 2016-06-21 Time 14:58 Sent To  
Notes
2016-06-21 15:33:42BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 DATE: 6/21/16
 ACTION: DENIED
  
 1. PROVIDE FLOOR PLAN INDICATING LOCATION OF ALL WORK.
 IDENTIFY WALL TYPES TO BE REMOVED AND IN-FILLED.
 IDENTIFY WHAT WALLS WILL HAVE JUST DRYWALL REMOVED.
 INCLUDE DEMENSIONS.
 2. DESIGNER TO SIGN DRAWINGS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-18 Cont ID  
Sent By mvaldes Date 2016-07-18 Time 17:10 Rev Time 0.00
Received By mvaldes Date 2016-07-18 Time 16:32 Sent To  
Notes
2016-07-29 12:54:33SUPERVISOR OVER RIDE.
2016-07-18 17:36:38REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - ALL KITCHEN COUNTERTOP RECEPTACLES MUST BE GFCI
 PROTECTED NEC 210.8 (A)(6) / FBC R E3902.6 ( MARK ON
 PLANS )
  
 - A RECEPTACLE IS SHOWN BEHIND OR ON TOP OF THE
 COUNTERTOP SPACE OCCUPIED BY THE RANGE CLARIFY SPACING
 OR CHANGE THE SYMBOL IF THE INTENT IS A 220 V OUTLET
 FOR THE RANGE. NEC 210.52(C)(4) / FBC R E3901.4.4
  
 - ALL BATHROOM RECEPTACLES SHALL BE GFCI PROTECTED NEC
 210.8(A)(1) / FBC R E3902.1 ( MARK ON PLANS )
  
 - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS
 314 & 315, IF EXISTING MARK ON PLANS.
  
 - ALL NEWLY INSTALLED LIGHTING SHALL BE HIGH EFFICIENCY
 AND IC RATED PLEASE ADD A NOTE. FBC E R404.1
  
 THE ANSWER TO MY INITIAL COMMENTS IN YOUR RESPONSE
 LETTER WERE CORRECT HOWEVER NOTHING WAS REFLECTED ON
 THE PLANS PLEASE ADD THE NOTES IN THE FLOOR PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-23 Cont ID  
Sent By mvaldes Date 2016-05-23 Time 18:33 Rev Time 0.00
Received By mvaldes Date 2016-05-23 Time 18:17 Sent To  
Notes
2016-05-23 18:34:37JOB PERMIT NUMBER: 16050607
 JOB ADDRESS: 122 WORTH COURT NORTH
 WEST PALM BEACH FLORIDA
 DATE: MAY 23 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A RECEPTACLE
 OUTLET SHALL BE INSTALLED AT EACH WALL COUNTERTOP SPACE
 THAT IS 12 IN. OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 24 IN. MEASURED HORIZONTALLY FROM A RECEPTACLE
 OUTLET IN THAT SPACE.
 - NEC 210.52(C)(2)(3) ISLAND & PENINSULAR COUNTERTOP
 SPACES. AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH ISLAND & PENINSULAR COUNTERTOP.
 - NEC 210.8(A)(6)(7) GFCI PROTECTION REQUIRED IN
 KITCHENS WHERE RECEPTACLES SERVE THE COUNTER-TOP
 SURFACES AND ALSO WITHIN 6? OF THE OUTER EDGE OF SINKS.
 - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE 314 AND
 315.
 - NEC 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING
 UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT,
 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER
 RESISTANT RECEPTACLES.
 - FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-07-29 Cont ID  
Sent By skennedy Date 2016-07-29 Time 12:53 Rev Time 0.00
Received By skennedy Date 2016-07-29 Time 12:53 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-05-20 Cont ID  
Sent By gjohnson Date 2016-05-20 Time 16:02 Rev Time 0.00
Received By gjohnson Date 2016-05-20 Time 16:02 Sent To  
Notes
2016-05-20 16:12:021ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. THE FLOOR PLAN OF KITCHEN SHOWS RANGE ON OUT SIDE
 WALL WITH THE MEETER RITE OUT SIDE YOUR GAS DRAWING
 SHOWS IT AT 20FT PLEASE CLARIFY . PER WPB AMEND. TO FBC
 107.2.1
  
 2. SHOW THE EHD NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. WPB AMENDMENTS
 TO FBC SEC. 107.2.1.
  
 3.SHOW LOCATION OF REGULATOR . PER WPB AMEND. TO FBC
 107.2.1
  
 4. THE INFORMATION WAS CUT OF ON THE COPY OF THE GAS
 PAGE THAT WAS SUBMITTED PLEASE PROVIDE NEW ONE WITH ALL
 INFORMATION CLEAR. . PER WPB AMEND. TO FBC 107.2.1
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-29 Cont ID  
Sent By skennedy Date 2016-07-29 Time 12:53 Rev Time 0.00
Received By skennedy Date 2016-07-05 Time 10:04 Sent To  
Notes
2016-07-06 10:07:04R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-21 Cont ID  
Sent By cthroop Date 2016-06-21 Time 15:27 Rev Time 0.00
Received By cthroop Date 2016-05-16 Time 12:46 Sent To  
Notes
2016-05-16 12:46:57R21

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-07-29 Cont ID  
Sent By skennedy Date 2016-07-29 Time 12:53 Rev Time 0.00
Received By skennedy Date 2016-07-29 Time 12:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-09 Cont ID  
Sent By jvalido Date 2016-06-09 Time 10:23 Rev Time 0.00
Received By jvalido Date 2016-06-09 Time 10:05 Sent To  
Notes
2016-06-09 10:23:26CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5)
  
 PROVIDE DUCT DIMENSIONS.
 PROVIDE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
  
  
 FBC MECHANICAL 2014
  
 FYI
  
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED
 WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE
 EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE
 EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE
 AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  
 EXCEPTION: IN A SINGLE-FAMILY DWELLING, MAKE-UP AIR IS
 NOT REQUIRED FOR RANGE HOOD EXHAUST SYSTEMS CAPABLE OF
 EXHAUSTING:
  
 (A) FOUR HUNDRED CUBIC FEET PER MINUTE OR LESS; OR
  
 (B) MORE THAN 400 CUBIC FEET PER MINUTE BUT NO MORE
 THAN 800 CUBIC FEET PER MINUTE IF THERE ARE NO GRAVITY
 VENT APPLIANCES WITHIN THE CONDITIONED LIVING SPACE OF
 THE STRUCTURE.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6732
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2016-07-27 Cont ID  
Sent By shill Date 2016-07-27 Time 14:32 Rev Time 0.00
Received By shill Date 2016-07-27 Time 14:32 Sent To  
Notes
2016-07-27 14:51:11SUBSTANTIAL IMPROVEMENT 12100037; ORIGINAL ELEVATION
 CERTIFICATE PROVIDED AT THAT TIME
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-07-29 Cont ID  
Sent By skennedy Date 2016-07-29 Time 12:53 Rev Time 0.00
Received By skennedy Date 2016-07-29 Time 12:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-20 Cont ID  
Sent By gjohnson Date 2016-05-20 Time 15:49 Rev Time 0.00
Received By gjohnson Date 2016-05-20 Time 15:49 Sent To  
Notes
2016-05-20 16:02:051ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE PLUMBING RISER DIAGRAM FOR ALL NEW
 WORK. PER WPB AMEND. TO FBC SEC. 107.3.5.3(11)
  
 2. PLEASE PROVIDE FULL FLOOR PLAN EXISTING AND PROPOSED
 . PER WPB AMEND. TO FBC 107.2.1
  
  