Plan Review Details - Permit 16050593
Plan Review Stops For Permit 16050593
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-06-16 Cont ID  
Sent By pleduc Date 2016-06-16 Time   Rev Time 0.00
Received By pleduc Date 2016-06-16 Time 16:24 Sent To G
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-17 Cont ID  
Sent By pleduc Date 2016-05-17 Time   Rev Time 0.00
Received By pleduc Date 2016-05-17 Time 08:29 Sent To M
Notes
2016-05-17 16:43:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THERE IS INSUFFICIENT DETAIL PROVIDED ON THIS SUBMITTAL
 TO PROVIDE A PROPER REVIEW.
  
 1) THE INFORMATION ON THE SITE PLAN IS MINIMAL AND
 VAGUE.
  
 THE SITE PLAN SHALL INDICATE ALL ACCURATE SEPARATION
 DIMENSIONS DISTANCES FROM THE BUILDING, WINDOWS, DOORS,
 A/C INTAKES, PROPERTY LINES AND EACH TANK, IN
 COMPLAINCE WITH THE MINIMUMS DISTANCES PER NFPA.
  
 2) THERE IS NO INTERIOR FLOOR PLAN.
  
 THE BUILDING FLOOR PLAN SHALL BE INCLUDED SHOWING THE
 AREAS OF WHERE THE PIPE WILL BE INSTALLED, HOW IT WILL
 BE SECURED AND AT WHAT HEIGHT.
  
 3) IS THE BOILER A NEW INSTALLATION OR EXISTING?
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-06-20 Cont ID  
Sent By tklarge Date 2016-06-20 Time 15:13 Rev Time 0.00
Received By tklarge Date 2016-06-20 Time 15:13 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-06-20 Cont ID  
Sent By tklarge Date 2016-06-20 Time 06:38 Rev Time 0.00
Received By tklarge Date 2016-06-20 Time 06:03 Sent To  
Notes
2016-06-20 06:31:131) INDICATE THE TYPE OF PIPE AND THE SIZE OF THE PIPE
 FROM THE TANKS TO THE FIRST STAGE REGULATOR.
 2) THE ANCHORING DETAILS FOR THE LP TANKS FROM STEPHEN
 WALSH, P.E. SHALL BEAR AN ORIGINAL SEAL AND SIGNATURE
 PER THE FL. ADMIN. CODE SEC. 61G15-23.001.
 3) SHT.P-100 THAT HAS BEEN SUBMITTED IS ILLEGIBLE.
 4) SUBMIT TWO SETS OF PLANS FOR REVIEW. CURRENTLY THERE
 ARE 4 SETS OF PLANS FOR THIS PERMIT. DELETE ALL OLD
 PLANS. WPB AMEND. TO FBC SEC. 107.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-06-20 Cont ID  
Sent By tklarge Date 2016-05-23 Time 10:30 Rev Time 0.00
Received By tklarge Date 2016-05-23 Time 06:07 Sent To  
Notes
2016-05-23 10:30:251) INDICATE THE TYPE OF PIPE AND THE SIZE OF THE PIPE
 FROM THE TANKS TO THE FIRST STAGE REGULATOR.
 2) INDICATE THE DISTANCE, THE TYPE OF PIPE AND THE SIZE
 OF THE PIPE FROM THE FIRST STAGE REGULATOR TO THE 2ND
 STAGE REGULATOR.
 3) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE PIPE
 BETWEEN THE FIRST AND SECOND STAGE REGULATOR.
 4) PER THE SIZING TABLE THAT HAS BEEN SUBMITTED, THE
 MAXIMUM BTU LOAD OF A 3/4 INCH PIPE AT 30 FT. IS
 336,000 BTU'S. SUBMIT THE CORRECT SIZING TABLE.
 5) THE LOCATION OF THE CONTAINER PRESSURE RELIEF AND
 BUILDING OPENINGS AND SOURCES OF IGNITION SHALL COMPLY
 WITH TABLE 6.3.8 OF NFPA 58.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-20 Cont ID  
Sent By tklarge Date 2016-06-20 Time 06:38 Rev Time 0.00
Received By tklarge Date 2016-06-15 Time 14:48 Sent To  
Notes
2016-06-15 14:48:14RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-23 Cont ID  
Sent By tklarge Date 2016-05-23 Time 10:30 Rev Time 0.00
Received By tklarge Date 2016-05-13 Time 12:39 Sent To  
Notes
2016-05-16 12:39:41ROUTED TO FIRE