Plan Review Details - Permit 16050593
| Plan Review Stops For Permit 16050593 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-06-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-06-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-06-16 |
Time |
16:24 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-05-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-05-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-05-17 |
Time |
08:29 |
Sent To |
M |
|
| Notes |
| 2016-05-17 16:43:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THERE IS INSUFFICIENT DETAIL PROVIDED ON THIS SUBMITTAL | | | TO PROVIDE A PROPER REVIEW. | | | | | | 1) THE INFORMATION ON THE SITE PLAN IS MINIMAL AND | | | VAGUE. | | | | | | THE SITE PLAN SHALL INDICATE ALL ACCURATE SEPARATION | | | DIMENSIONS DISTANCES FROM THE BUILDING, WINDOWS, DOORS, | | | A/C INTAKES, PROPERTY LINES AND EACH TANK, IN | | | COMPLAINCE WITH THE MINIMUMS DISTANCES PER NFPA. | | | | | | 2) THERE IS NO INTERIOR FLOOR PLAN. | | | | | | THE BUILDING FLOOR PLAN SHALL BE INCLUDED SHOWING THE | | | AREAS OF WHERE THE PIPE WILL BE INSTALLED, HOW IT WILL | | | BE SECURED AND AT WHAT HEIGHT. | | | | | | 3) IS THE BOILER A NEW INSTALLATION OR EXISTING? | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2016-06-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-06-20 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-06-20 |
Time |
15:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2016-06-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-06-20 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-06-20 |
Time |
06:03 |
Sent To |
|
|
| Notes |
| 2016-06-20 06:31:13 | 1) INDICATE THE TYPE OF PIPE AND THE SIZE OF THE PIPE | | | FROM THE TANKS TO THE FIRST STAGE REGULATOR. | | | 2) THE ANCHORING DETAILS FOR THE LP TANKS FROM STEPHEN | | | WALSH, P.E. SHALL BEAR AN ORIGINAL SEAL AND SIGNATURE | | | PER THE FL. ADMIN. CODE SEC. 61G15-23.001. | | | 3) SHT.P-100 THAT HAS BEEN SUBMITTED IS ILLEGIBLE. | | | 4) SUBMIT TWO SETS OF PLANS FOR REVIEW. CURRENTLY THERE | | | ARE 4 SETS OF PLANS FOR THIS PERMIT. DELETE ALL OLD | | | PLANS. WPB AMEND. TO FBC SEC. 107.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2016-06-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-05-23 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-05-23 |
Time |
06:07 |
Sent To |
|
|
| Notes |
| 2016-05-23 10:30:25 | 1) INDICATE THE TYPE OF PIPE AND THE SIZE OF THE PIPE | | | FROM THE TANKS TO THE FIRST STAGE REGULATOR. | | | 2) INDICATE THE DISTANCE, THE TYPE OF PIPE AND THE SIZE | | | OF THE PIPE FROM THE FIRST STAGE REGULATOR TO THE 2ND | | | STAGE REGULATOR. | | | 3) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE PIPE | | | BETWEEN THE FIRST AND SECOND STAGE REGULATOR. | | | 4) PER THE SIZING TABLE THAT HAS BEEN SUBMITTED, THE | | | MAXIMUM BTU LOAD OF A 3/4 INCH PIPE AT 30 FT. IS | | | 336,000 BTU'S. SUBMIT THE CORRECT SIZING TABLE. | | | 5) THE LOCATION OF THE CONTAINER PRESSURE RELIEF AND | | | BUILDING OPENINGS AND SOURCES OF IGNITION SHALL COMPLY | | | WITH TABLE 6.3.8 OF NFPA 58. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-06-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-06-20 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-06-15 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2016-06-15 14:48:14 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-05-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-05-23 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-05-13 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2016-05-16 12:39:41 | ROUTED TO FIRE |
|
|
|