Plan Review Details - Permit 16050574
Plan Review Stops For Permit 16050574
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-17 Cont ID  
Sent By jwitmer Date 2016-08-17 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2016-08-17 Time 07:02 Sent To  
Notes
2016-08-17 07:14:57PROVISO/ DEFERRED SUBMITTAL. SHEET A1.07 ALSO SHOWS 3
 FT X 4 FT OPAQUE WOOD ACCESS DOORS W/ COMPACTOR CHUTE
 BEHIND. PLEASE GIVE ADDITIONAL DETAIL ON THE HARDWARE
 FOR OPENING THESE DOORS IN COMPLIANCE WITH 2014
 FBC-ACCESS.
 1A) CODE 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED
 WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED IN
 308.
 1B) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE
 WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-19 Cont ID  
Sent By jwitmer Date 2016-07-19 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2016-07-19 Time 12:01 Sent To  
Notes
2016-07-19 12:25:18BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050572
 ADD: 7110 OKEECHOBEE BLVD. / PENDING / SITE ENTRY TOWER
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. JUNE 16/2016
 ACTION: DENIED
  
 1) THE SITE ADDRESS AND BUILDING ADDRESS ARE STILL
 PENDING UNTIL THE NEW PCN NUMBER IS PUBLISHED BY PALM
 BEACH COUNTY APPRAISERS OFFICE. THE ADDRESS OF THE
 RECREATION/ LEASING BUILDING WILL BE USED FOR THE SITE
 AMENITIES ADDRESS, 7130 OKEECHOBEE BLVD.
  
 2) COMPLIED. ELECTRONIC SIGNATURES. 61G15-23.005
 PROCEDURES FOR SIGNING AND SEALING ELECTRONICALLY
 TRANSMITTED PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 3A) COMPLIED. SHEET A1.07 COMP. THE BUILDING CODE
 INFORMATION LIST THIS COMPACTOR AS FIRE SPRINKLERED
 WITH A 13R SYSTEM. THERE ARE NO FIRE SPRINKLER PLANS IN
 THIS SUBMITTAL. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 3B) SEMI-COMPLIED. NOTE THERE ARE NO STRUCTURAL SHEETS,
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS
 107.3.5.1.1. COMMERCIAL BUILDINGS:
 (8) COMPLIED. STRUCTURAL REQUIREMENTS
  
 WIND DESIGN CRITERIA: DISCREPANCY IN THE PLANS: THE TOP
 CENTER OF THIS SHEET THERE IS A WIND DESIGN 170 VULT
 EXPOSURE B. PLEASE SEE 2014 FBC-B SECTION SURFACE
 ROUGHNESS C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS
 HAVING HEIGHTS GENERALLY LESS THAN 30 FEET. THIS
 CATEGORY INCLUDES FLAT OPEN COUNTRY, AND GRASSLANDS.
 THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING
 LOCATED WITHIN SURFACE ROUGHNESS B TYPE TERRAIN WHERE
 THE BUILDING IS WITHIN 100 FEET HORIZONTALLY IN ANY
 DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR
 D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET IN THE
 UPWIND DIRECTION AND A WIDTH GREATER THAN 150 FEET .
 THE OTHER ISSUE IS IN THE STRUCTURAL NOTES THE WIND
 DESIGN CRITERIA IS TAKEN OUT OF ASCE 7-05, 140 MPH THIS
 IS TAKEN FROM THE 2010 FBC-B NOT THE CURRENT CODE.
  
 4-5) COMPLIED.
  
 6) PROVISO/ DEFERRED SUBMITTAL. SHEET A1.07 ALSO SHOWS
 3 FT X 4 FT OPAQUE WOOD ACCESS DOORS W/ COMPACTOR CHUTE
 BEHIND. PLEASE GIVE ADDITIONAL DETAIL ON THE HARDWARE
 FOR OPENING THESE DOORS IN COMPLIANCE WITH 2014
 FBC-ACCESS.
 6A) CODE 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED
 WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED IN
 308.
 6B) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE
 WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-16 Cont ID  
Sent By jwitmer Date 2016-06-16 Time 16:23 Rev Time  
Received By jwitmer Date 2016-06-16 Time 15:40 Sent To  
Notes
2016-06-16 16:23:35BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050572
 ADD: 7110 OKEECHOBEE BLVD. / PENDING / SITE ENTRY TOWER
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. JUNE 16/2016
 ACTION: DENIED
  
 1) THE SITE ADDRESS AND BUILDING ADDRESS ARE STILL
 PENDING UNTIL THE NEW PCN NUMBER IS PUBLISHED BY PALM
 BEACH COUNTY APPRAISERS OFFICE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION OF THE PROJECT,
  
 2) THE PLANS WERE SUBMITTED DIGITALLY, PLEASE NOTE NONE
 OF THE ARCHITECTURAL SHEETS ARE SIGNED FOR ELECTRONIC
 SIGNATURES. 61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3) SHEET A1.07 COMP. THE BUILDING CODE INFORMATION LIST
 THIS COMPACTOR AS FIRE SPRINKLERED WITH A 13R SYSTEM.
 THERE ARE NO FIRE SPRINKLER PLANS IN THIS SUBMITTAL.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 3) NOTE THERE ARE NO STRUCTURCAL SHEETS, 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1.1. COMMERCIAL BUILDINGS:
 (8) STRUCTURAL REQUIEMENTS
 WIND DESIGN CRITERIA
  
 4) SHEET A1.01 & A1.07 BOTH SHOW A SLOPED RAMP BUT
 THERE IS NO ELEVATIONS PROVIDED AT THE BOTTOM NOR TOP
 LANDING. PLEASE NOTE THE SLOPE IS INDICATED AT 1:20
 BETWEEN, RAMP SLOPES ARE WITHIN THESE TORANCES FOR NEW
 CONSTRUCTION1:12 AND 1A:20. IF THE SLOPE IS ABOVE THE
 1:20, 1:21 IT IS NO LONGER CONSIDERED A RAMP BUT GRADE.
 AT 1:20 HANDRAILS WILL STILL BE REQUIRED. 2014
 FBC-ACCESS. CODE 405.8 HANDRAILS. RAMP RUNS WITH A RISE
 GREATER THAN 6 INCHES (150 MM) SHALL HAVE HANDRAILS
 COMPLYING WITH 505.
  
 5) SHEET A1.07 SHOWS ELEVATIONS AROUND THE DUMPSTER
 ENCLOSURE BUT THERE ARE NONE OF THE RAMP AND THE
 OPENING OF THE COMPACTOR HOPPER SHOWING COMPLIANCE WITH
 REACH RANGES. 2014 FBC-ACCESS. CODE 308 .2 FORWARD AND
 308.3 SIDE REACH RANGES.
  
 6) SHEET A1.07 ALSO SHOWS 3 FT X 4 FT OPAQUE WOOD
 ACCESS DOORS W/ COMPACTOR CHUTE BEHIND. PLEASE GIVE
 ADDITIONAL DETAIL ON THE HARDWARE FOR OPENING THESE
 DOORS IN COMPLIANCE WITH 2014 FBC-ACCESS.
 6A) CODE 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED
 WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED IN
 308.
  
 6B) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE
 WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-15 Cont ID  
Sent By vperez Date 2016-07-15 Time 08:30 Rev Time 0.00
Received By vperez Date 2016-07-15 Time 08:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-06-20 Cont ID  
Sent By vperez Date 2016-06-20 Time 12:03 Rev Time 0.00
Received By vperez Date 2016-06-20 Time 12:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-10-03 Cont ID  
Sent By cpuell Date 2016-10-03 Time 09:09 Rev Time 0.00
Received By cpuell Date 2016-09-14 Time 12:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-18 Cont ID  
Sent By cpuell Date 2016-08-18 Time 14:31 Rev Time 0.00
Received By cpuell Date 2016-08-01 Time 10:54 Sent To  
Notes
2016-08-22 11:28:05THE ARCHITECTURAL SHEETS VERIFIED FOR ELECTRONIC
 SIGNATURE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-19 Cont ID  
Sent By   Date 2016-07-19 Time   Rev Time 0.00
Received By lmarchan Date 2016-07-11 Time 11:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-24 Cont ID  
Sent By skennedy Date 2016-06-24 Time 10:42 Rev Time 0.00
Received By skennedy Date 2016-05-18 Time 14:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2016-08-30 Cont ID  
Sent By skennedy Date 2016-08-30 Time 16:14 Rev Time 0.00
Received By skennedy Date 2016-08-30 Time 16:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-08-26 Cont ID  
Sent By skennedy Date 2016-08-26 Time 09:57 Rev Time 0.00
Received By skennedy Date 2016-08-26 Time 09:57 Sent To  
Notes
2016-08-26 09:58:45PLAN SHEETS ARE DIGITALLY SIGNED, HOWEVER THE
 GEOTECHNICAL REPORT IS NOT. SUBMIT AN ORIGINAL.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
2016-08-01 10:54:45**ORIGINAL SIGNED & SEALED PLANS IN LIBRARY WITH PERMIT
 APP**
  

Review Stop Z ZONING
Rev No 4 Status P Date 2016-09-28 Cont ID  
Sent By ajones Date 2016-09-28 Time 14:45 Rev Time 0.00
Received By ajones Date 2016-09-28 Time 14:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-08-17 Cont ID  
Sent By llouie Date 2016-08-17 Time   Rev Time 0.00
Received By llouie Date 2016-08-17 Time   Sent To  
Notes
2016-08-17 11:45:02** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) RESOLUTION NO. 322-15, APPROVING THE OKEECHOBEE
 COMMONS RESIDENTIAL DSI PROJECT, REQUIRES THAT CERTAIN
 CONDITIONS ARE MET PRIOR TO THE APPROVAL OF ANY
 BUILDING PERMIT BY THE ZONING DIVISION. PLEASE PROVIDE
 ANY DOCUMENTATION TO THE DEVELOPMENT SERVICES
 DEPARTMENT-PLANNING DIVISION VERIFYING THAT THE
 CONDITIONS HAVE BEEN MET. [REPEAT COMMENT 7/14/16 AND
 6/22/16]
  
 2.) THE SITE PLAN DOES NOT MATCH THE LATEST APPROVED
 AMENDMENT TO THE SITE PLAN (REFERENCE: PB 1491K,
 APPROVED BY THE PLANNING DIVISION ON 7/8/16 WITH
 CONDITIONS). THE SITE PLAN WILL NEED TO BE UPDATED FOR
 CONSISTENCY. [REPEAT COMMENT 7/14/16 AND 6/22/16]
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-07-14 Cont ID  
Sent By llouie Date 2016-07-14 Time   Rev Time 0.00
Received By llouie Date 2016-07-14 Time   Sent To  
Notes
2016-07-14 13:58:13** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) RESOLUTION NO. 322-15, APPROVING THE OKEECHOBEE
 COMMONS RESIDENTIAL DSI PROJECT, REQUIRES THAT CERTAIN
 CONDITIONS ARE MET PRIOR TO THE APPROVAL OF ANY
 BUILDING PERMIT BY THE ZONING DIVISION. PLEASE PROVIDE
 ANY DOCUMENTATION TO THE DEVELOPMENT SERVICES
 DEPARTMENT-PLANNING DIVISION VERIFYING THAT THE
 CONDITIONS HAVE BEEN MET. [REPEAT COMMENT 6/22/16]
  
 2.) THE SITE PLAN DOES NOT MATCH THE LATEST APPROVED
 AMENDMENT TO THE SITE PLAN (REFERENCE: PB 1491K,
 APPROVED BY THE PLANNING DIVISION ON 7/8/16 WITH
 CONDITIONS). THE SITE PLAN WILL NEED TO BE UPDATED FOR
 CONSISTENCY. ALSO, THE SITE PLAN MUST ILLUSTRATE ALL
 SETBACKS, DETAILS, ETC. PER THE APPROVED SITE PLAN.
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-22 Cont ID  
Sent By llouie Date 2016-06-22 Time 10:12 Rev Time 0.00
Received By llouie Date 2016-06-22 Time 10:12 Sent To  
Notes
2016-06-22 10:12:50** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) RESOLUTION NO. 322-15, APPROVING THE OKEECHOBEE
 COMMONS RESIDENTIAL DSI PROJECT, REQUIRES THAT CERTAIN
 CONDITIONS ARE MET PRIOR TO THE APPROVAL OF ANY
 BUILDING PERMIT BY THE ZONING DIVISION. PLEASE PROVIDE
 ANY DOCUMENTATION TO THE DEVELOPMENT SERVICES
 DEPARTMENT-PLANNING DIVISION VERIFYING THAT THE
 CONDITIONS HAVE BEEN MET.
  
 2.) ANY CHANGES TO THE SITE PLAN WILL REQUIRE AN
 AMENDMENT TO THE DSI; CHANGES HAVE BEEN DETECTED.
 PLEASE NOTE THAT AN APPLICATION FOR A MINOR DSI
 AMENDMENT WAS SUBMITTED TO PLANNING STAFF ON 5/25/16.
 THE PROPOSED AMENDMENT TO THE SITE PLAN IS CURRENTLY
 PENDING. ONCE APPROVED, THE SITE PLAN WILL NEED TO BE
 UPDATED FOR CONSISTENCY.
  
 3.) PROVIDE SETBACK DIMENSIONS FROM THE FRONT PROPERTY
 LINE (OKEECHOBEE BOULEVARD) TO THE PROPOSED TRASH
 COMPACTOR ENCLOSURE. PLEASE NOTE THAT THE ENCLOSURE IS
 CONSIDERED AN ACCESSORY STRUCTURE AND MUST BE SETBACK
 AT LEAST 25 FT. FROM THE FRONT PROPERTY LINE ON
 OKEECHOBEE BOULEVARD.
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.