| 2016-06-16 15:01:55 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16050572 |
| | ADD: 7110 OKEECHOBEE BLVD. / PENDING / SITE ENTRY TOWER |
| | CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER |
| | TEL: 561-891-0414 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JUNE 16/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE SITE ADDRESS AND BUILDING ADDRESS ARE STILL |
| | PENDING UNTIL THE NEW PCN NUMBER IS PUBLISHED BY PALM |
| | BEACH COUNTY APPRAISERS OFFICE. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION OF THE PROJECT, |
| | |
| | 2) THE PLANS WERE SUBMITTED DIGITALLY, PLEASE NOTE NONE |
| | OF THE ARCHITECTURAL SHEETS ARE SIGNED FOR ELECTRONIC |
| | SIGNATURES. 61G15-23.005 PROCEDURES FOR SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 3) SHEET A1.10A UNDER THE DESIGN HEADING INDICATES THE |
| | EXPOSURE AS A "B" EXPOSURE, PLEASE UPDATE PLANS, REVIEW |
| | SECTION 2014 FBC-B 1609.4.2 SURFACE ROUGHNESS |
| | CATEGORIES. SURFACE ROUGHNESS C. OPEN TERRAIN WITH |
| | SCATTERED OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS |
| | THAN 30 FEET (9144 MM). THIS CATEGORY INCLUDES FLAT |
| | OPEN COUNTRY, AND GRASSLANDS. THIS SURFACE ROUGHNESS |
| | SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN SURFACE |
| | ROUGHNESS BTYPE TERRAIN WHERE THE BUILDING IS WITHIN |
| | 100 FEET (30 M) HORIZONTALLY IN ANY DIRECTION OF OPEN |
| | AREAS OF SURFACE ROUGHNESS C OR D-TYPE TERRAIN THAT |
| | EXTENDS MORE THAN 600 FEET (182.9 M) IN THE UPWIND |
| | DIRECTION AND A WIDTH GREATER THAN 150 FEET (46 M). |
| | |
| | 4) SHEET A1.10B THE CUT SECTION THROUGH THE TOWER SHOWS |
| | WHAT IS ASSUMED AS A 16 INCH TOP BOND BEAM W/ TOP AND |
| | BOTTOM STEEL, OR MAYBE A LINTEL USED ON THE BOTTOM |
| | COURSE WITH REBAR IN EACH COURSE, SIZE OF REBAR NOT |
| | INDICATED, NOR THE LENGTH OF THE CORNER BARS, NO HOOPS, |
| | STIRRUPS OR HAIRPINS SHOWN SHOW COMPLIANCE WITH . THERE |
| | IS NOT ENOUGH DETAIL ON THE PLANS. SHOW COMPLIANCE WITH |
| | FBC-B 2107.3 ACI 530/ASCE 5, SECTION 2.1.7.7, SPLICES |
| | OF REINFORCEMENT. 7.5.3.1 SHEAR REINFORCEMENT IN |
| | MASONRY BEAMS. |
| | |
| | 5) SHEET A1.10B THE CUT SECTION THROUGH THE TOWER SHOW |
| | COMPLIANCE WITH 2014 FBC-B 1609.6.4.4.1 COMPONENTS & |
| | CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(B) BAHAMA STYLE SHUTTERS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |