Plan Review Details - Permit 16050541
Plan Review Stops For Permit 16050541
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By rmcdouga Date 2016-06-13 Time 15:43 Rev Time 0.00
Received By rmcdouga Date 2016-06-13 Time 15:31 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-26 Cont ID  
Sent By rmcdouga Date 2016-05-26 Time 08:12 Rev Time 0.00
Received By rmcdouga Date 2016-05-25 Time 18:45 Sent To E
Notes
2016-05-26 08:12:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE
 ROOFING MATERIALS.
  
 2) IF THE PRODUCT APPROVALS FOR THE ROOFING REQUIRES
 ENHANCED FASTENING IN THE PERIMETER AND CORNER AREAS,
 SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS.
  
 3) THE EDITIONS OF SEVERAL CODES AND STANDARDS ARE
 LISTED ON SHEET 1.1 ARE INCORRECT. THESE ARE THE
 CORRECT EDITIONS: 2011 NFPA-70 (NEC), NFPA 101 (2012
 EDITION) AND THE FIRE PREVENTION CODE (2014). FBC-R
 CHAPTER 46.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By mvaldes Date 2016-06-13 Time 16:24 Rev Time 0.00
Received By mvaldes Date 2016-06-13 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-01 Cont ID  
Sent By mvaldes Date 2016-06-01 Time 08:55 Rev Time 0.00
Received By mvaldes Date 2016-06-01 Time 08:55 Sent To  
Notes
2016-06-01 09:03:15REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
  
 - NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
  
 - NEC 210.52(E)(3) PORCHES THAT ARE ACCESSIBLE FROM
 INSIDE THE DWELLING UNIT SHALL HAVE AT LEAST ONE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE PORCH. OUTDOOR
 RECEPTACLE SHALL BE GFCI PROTECTED IN ACCORDANCE WITH
 210.8(A)

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-06-10 Cont ID  
Sent By destabro Date 2016-06-10 Time 12:01 Rev Time 0.00
Received By destabro Date 2016-06-10 Time 12:01 Sent To  
Notes
2016-06-10 12:02:476/10/16 - HPD APPROVED 340 SF REAR LOGGIA OPEN ADDITION
 (COUNTS AT HALF TOWARDS LOT COVERAGE REQUIREMENTS =
 170SF). APPROVED COA (HPB 16-55). DLE

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-05-25 Cont ID  
Sent By destabro Date 2016-05-25 Time 15:46 Rev Time 0.00
Received By destabro Date 2016-05-25 Time 15:46 Sent To  
Notes
2016-05-25 15:49:575/25/16 - APPLICANT INFORMED (5/16) THAT COA WILL BE
 REQUIRED TO ADD A LOGGIA TO THE REAR OF THE PROPERTY
 SINCE THIS IS A CONTRIBUTING PROPERTY TO THE EL CID
 HISTORIC DISTRICT. NO COA RECEIVED TO DATE, FAILED FOR
 HISTORIC. DLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-13 Cont ID  
Sent By mvaldes Date 2016-06-13 Time 16:24 Rev Time 0.00
Received By mvaldes Date 2016-06-07 Time 09:57 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-01 Cont ID  
Sent By mvaldes Date 2016-06-01 Time 09:04 Rev Time 0.00
Received By mvaldes Date 2016-05-12 Time 10:49 Sent To  
Notes
2016-05-13 10:49:27ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-25 Cont ID  
Sent By mvaldes Date 2016-06-13 Time 16:24 Rev Time 0.00
Received By destabro Date 2016-05-25 Time 15:52 Sent To  
Notes
***NONE***