Plan Review Details - Permit 16050444
Plan Review Stops For Permit 16050444
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-11 Cont ID  
Sent By shill Date 2016-07-11 Time 14:12 Rev Time 0.00
Received By shill Date 2016-07-11 Time 12:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-23 Cont ID  
Sent By shill Date 2016-05-23 Time 17:58 Rev Time 0.00
Received By shill Date 2016-05-23 Time 17:56 Sent To  
Notes
2016-05-23 18:08:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 5TH ED.
 ACCESSIBILITY 225.
  
 2. REVISE PLAN TO INCLUDE A DETAIL FOR THE COFFEE BAR
 AND SINK, CONCIERGE DESK, CUSTOMER LOUNGE SEATING, FBC
 107, FBC 5TH ED. ACCESSIBILITY 226, 227.
  
 3. PLAN STATES THAT OCCUPANCY IS S2, BUT THE CUSTOMER
 LOUNGE AREA IS NOT STORAGE OCCUPANCY. REVISE, FBC
 CHAPTER 3.
  
 4. REVISE PLAN TO SHOW SQUARE FOOT AREA OF THE CUSTOMER
 LOUNGE AREA AND STORAGE AREA, FBC 107, FBC 1004. IT IS
 NOT CLEAR HOW AN OCCUPANT LOAD OF 10 HAS BEEN DERIVED.
  
 5. THE REAR DOOR IS SHOWN AS AN EXIT, BUT THIS AREA
 APPEARS TO BE FENCED. CLARIFY USE OF SPACE AND EXITING
 STRATEGY, FBC 1003.6, 1003.5, 1027.1, 1027.5.
  
 6. FBC 5TH ED. EXISTING BUILDING 301, REVISE THE PLAN
 TO STATE THE COMPLIANCE METHOD ELECTED. IF THIS IS A
 CHANGE OF OCCUPANCY, INCORPORATE THIS INTO THE PLAN AND
 SHOW COMPLIANCE.
  
 7. AS IT IS NOT CLEAR WHETHER OR NOT THIS IS A CHANGE
 OF OCCUPANCY, IT IS NOT CLEAR WHETHER OR NOT IMPACT
 FEES ARE REQUIRED. PLEASE CONTACT 561-233-5025 FOR MORE
 INFORMATION. IF THEY DETERMINE THAT IMPACT FEES ARE NOT
 REQUIRED, YOU MAY HAVE THE PALM BEACH COUNTY IMPACT FEE
 OFFICE SEND AN EMAIL VERIFYING THIS. OTHERWISE, HAVE
 THE PLANS STAMPED BY THEM AND, IF FEES ARE DUE, PROVIDE
 THE RECEIPT SHOWING THAT FEES WERE PAID AT TIME OF
 RESUBITTAL.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-13 Cont ID  
Sent By mvaldes Date 2016-07-13 Time 16:16 Rev Time 0.00
Received By mvaldes Date 2016-07-13 Time 16:16 Sent To  
Notes
2016-07-13 16:19:00REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO
  
 - FBC ADA 308.3.1 WHERE A CLEAR FLOOR OR GROUND SPACE
 ALLOWS A PARALLEL APPROACH TO AN ELEMENT AND THE SIDE
 REACH IS UNOBSTRUCTED, THE HIGH SIDE REACH SHALL BE 48
 INCHES (1220 MM) MAXIMUM AND THE LOW SIDE REACH SHALL
 BE 15 INCHES (380 MM) MINIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-12 Cont ID  
Sent By mvaldes Date 2016-05-12 Time 15:17 Rev Time 0.00
Received By mvaldes Date 2016-05-12 Time 14:36 Sent To  
Notes
2016-05-12 15:18:12JOB PERMIT NUMBER: 16050444
 JOB ADDRESS: 3234 S DIXIE
 WEST PALM BEACH FLORIDA
 DATE: MAY 12 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. A
 BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE.
 - FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING AND EXIT
 SIGNS SHALL BE FED BY LIGHTING CIRCUIT OF SAME LOCAL
 AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY THE AREA,
 EM LIGHTS MAY BE ON OWN CIRCUIT.
 - C405.2 LIGHTING CONTROLS (MANDATORY). LIGHTING
 SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS SPECIFIED IN
 SECTIONS C405.2.1, C405.2.2, C405.2.3 AND C405.2.4.
 - C405.2.2.2 OCCUPANCY SENSORS.
 - OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL
 CLASSROOMS, CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH
 AND BREAK ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE
 ROOMS AND JANITORIAL CLOSETS, AND OTHER SPACES 300
 SQUARE FEET (28 M2) OR LESS ENCLOSED BY
 FLOOR-TO-CEILING HEIGHT PARTITIONS. THESE AUTOMATIC
 CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY
 TURN OFF LIGHTS WITHIN 30 MINUTES OF ALL OCCUPANTS
 LEAVING THE SPACE, AND SHALL EITHER BE MANUAL ON OR
 SHALL BE CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING
 ON TO NOT MORE THAN 50 PERCENT POWER.
 - NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY.
 - NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 - NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20
 AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET
 LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF
 WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL
 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING
 RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE
 ?WR?.
 - NEC 210.8(B) GFCI PROTECTION REQUIRED IN BATHROOMS
 AND COUNTERTOP SPACES WITHIN 6? OF A SINK.
 - NEC 300.21 OPENINGS AROUND ELECTRICAL PENETRATIONS
 INTO OR THROUGH FIRE-RESISTANT-RATED WALLS, PARTITIONS,
 FLOORS, OR CEILINGS SHALL BE FIRE STOPPED USING
 APPROVED METHODS TO MAINTAIN THE FIRE RESISTANCE
 RATING.
 - GENERATOR MUST BE SUBMITTED UNDER A SEPARATE PERMIT
 WITH SHOP DRAWINGS WITH MANUFACTURE SPECS ON THE
 EQUIPMENT AND TRANSFER SWITCH.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-06-23 Cont ID  
Sent By pleduc Date 2016-06-23 Time   Rev Time 0.00
Received By pleduc Date 2016-06-23 Time 12:37 Sent To  
Notes
2016-06-23 12:57:08THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET LS 1 & A 1 - THE PLAN INDICATES ONLY ONE
 HANDRAIL ON THE WALL SIDE OF THE REAR STAIR.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
  
 THE EXCEPTIONS DO NOT APPLY TO YOUR INSTALLATION.
  
 PLEASE PROVIDE A HANDRAIL TO THE OPPISITE SIDE OF THE
 STAIR. THE INSTALLATION WILL BE VERIFIED ON FIRE
 INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-19 Cont ID  
Sent By pleduc Date 2016-05-19 Time   Rev Time 0.00
Received By pleduc Date 2016-05-19 Time 15:45 Sent To  
Notes
2016-05-19 16:52:55THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET D 1 - THERE IS NO INDICATION OF REVIEW OF
 COMPLAINCE WITH THE FLORIDA FIRE PREVENTION CODE.
 PLEASE ENSURE COMPALINACE AND PROVIDE A NOTE:
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 2) SHEET D 1 & A 2 - IS THIS A MIXED OR SEPARATED
 OCCUPANCY? THE AREA OF THE STORAGE AND THE AREA IN THE
 FRONT IS BUISNESS/ASSEMBLY AND IS REQUIRED TO BE
 SEPARATED BY A 2 HOUR FIRE RATING. PLEASE
 EXPLAIN/JUSTIFY AND/OR PROVIDE SEPARATION PER NFPA 101,
 CHAPTER 6, 6.1.14.4.1.
  
 3) SHEET A 2 - THE DOOR SCHEDULE DOES NOT INDICATE THE
 TYP OF HARDWARE FOR DOORS INDICATED AS # 2. PLEASE
 PROVIDE HARDWARE COMPLIANT WITH NFPA 101, CHAPTER 7,
 MEANS OF EGRESS, 7.2
  
 4) SHEET LS 1 - THE REAR EEXIT DOES NOT INDCATE A
 DISCHARGE TO A PUBLIC WAY. THE AREA IS FENCED. THIS
 DOES MEET THE REQUIRED EXTING FROM THE STURCTURE PER
 NFPA 101, CHAPTER 7, MEANS OF EGRESS, 7.7
  
 ADDITIONAL COMMENTS MAY BE PROVIDED ON RE-SUBMITTAL OF
 THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2016-07-18 Cont ID  
Sent By tklarge Date 2016-07-18 Time 06:30 Rev Time 0.00
Received By tklarge Date 2016-07-18 Time 05:42 Sent To  
Notes
2016-07-18 06:32:16GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-05-31 Cont ID  
Sent By tklarge Date 2016-05-31 Time 08:49 Rev Time 0.00
Received By tklarge Date 2016-05-31 Time 06:30 Sent To  
Notes
2016-05-31 06:39:211) SHOW THE DISTANCE OF THE LP TANK FROM THE BUILDING
 WALL. COMPLY WITH NFPA 58 SEC.6.3.2.3 - NO PART OF AN
 UNDERGROUND OR MOUNDED ASME CONTAINER
 SHALL BE LESS THAN 10 FT (3 M) FROM A BUILDING OR LINE
 OF ADJOINING PROPERTY THAT CAN BE BUILT UPON
 2) SHOW THE DISTANCE OF THE LP TANK TO THE
 DRIVEWAY.INSTALLATIONS WITHIN 10 FT (3 M) OF A PUBLIC
 VEHICULAR THOROUGHFARE OR DESIGNATED PARKING LOCATION
 SHALL BE PROVIDED WITH
 VEHICULAR BARRIER PROTECTION FOR THE CONTAINER?S
 FITTING HOUSING, COMPLY WITH NFPA 58 SEC.6.6.6.1 (C) &
 (E) - THE INSTALLATION OF A BURIED CONTAINER SHALL
 INCLUDE PROTECTIONFOR THE CONTAINER AND PIPING AGAINST
 PHYSICAL DAMAGE
 FROM VEHICULAR TRAFFIC.
 3) SUBMIT COMPLETE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATIONN MANUAL FOR REVIEW. THE
 GENERATOR SHALL BE UL 2200 LISTED AND BE INSTALED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37. 2014 FBC-FUEL GAS SEC.616.1.
 4) THE GAS SHALL BE SUBMITTED AS A SEPARATE PERRMIT.
 5) SUBMIT DETAILS AS TO HOW THE LP TANK WILL BE
 ANCHORED TO PREVENT FLOTATION. NFPA 58 SEC. 6.6.1.6.
 6) GAS SHALL BE DONE UNDER A SEPARATE PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-18 Cont ID  
Sent By tklarge Date 2016-07-18 Time 06:33 Rev Time 0.00
Received By tklarge Date 2016-06-20 Time 13:29 Sent To  
Notes
2016-06-20 13:30:01C06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-31 Cont ID  
Sent By tklarge Date 2016-05-31 Time 08:54 Rev Time 0.00
Received By tklarge Date 2016-05-11 Time 13:36 Sent To  
Notes
2016-05-11 13:36:26C16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-07-11 Cont ID  
Sent By shill Date 2016-07-11 Time 12:43 Rev Time 0.00
Received By shill Date 2016-07-11 Time 12:42 Sent To  
Notes
2016-07-11 12:43:52MU-2016-15464, $0
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-05-24 Cont ID  
Sent By shill Date 2016-05-24 Time 11:38 Rev Time 0.00
Received By shill Date 2016-05-24 Time 11:38 Sent To  
Notes
2016-05-24 11:38:31SEE BUILDING COMMENTS
 CALL 561-233-5025 FOR MORE INFORMATION
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-05-17 Cont ID  
Sent By jvalido Date 2016-05-17 Time 16:52 Rev Time 0.00
Received By jvalido Date 2016-05-17 Time 16:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-24 Cont ID  
Sent By gearl Date 2016-06-24 Time   Rev Time 0.00
Received By gearl Date 2016-06-24 Time 07:54 Sent To  
Notes
2016-06-24 07:55:33NEED TO HAVE A SEPERATE GAS PERMIT

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-31 Cont ID  
Sent By tklarge Date 2016-05-31 Time 06:30 Rev Time 0.00
Received By tklarge Date 2016-05-31 Time 05:30 Sent To  
Notes
2016-05-31 06:30:151)2) SHT. A-1 - THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE PER 2014 FAC SEC.609.4..
 3) SHT. A 1- THE CENTERLINE OF THE WATER CLOSET SHALL
 BE 16 INCHES (405 MM) MINIMUM TO 18 INCHES (455 MM)
 MAXIMUM FROM THE SIDE WALL. FAC SEC.604.2. SHOW ON THE
 PLANS.
 4) A SERVICE SINK IS REQD. 2014 FBC-PLUMBING, TABLE
 403.1.
 5) THE COFFEE BAR COUNTER AND THE SINK SHALL COMPLY
 WITH THE 2014 FAC SEC. 212.1 & 606.2, 606.3, 606.4,
 606.5.
 6) THE HEIGHT OF THE WATER CLOSET FROM THE FINISH FLOOR
 SHALL COMPLY WITH FAC SEC. 604.4.
 7) THE BACKFLOW PREVENTER SHALL BE PERMITTED UNDER A
 SEPARATE PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-07-20 Cont ID  
Sent By ajones Date 2016-07-20 Time 11:54 Rev Time 0.00
Received By ajones Date 2016-07-20 Time 11:54 Sent To  
Notes
2016-07-20 11:58:367/20/16- PASSED WITH THE PROVISO THAT PRIOR TO THE
 ISSUANCE OF A CERTIFICATE OF COMPLETION THE
 APPLICATION/OWNER MUST SUBMIT REVISED PLANS SHOWING
 THAT THE OFFICE/CONCIERGE AREA IS THE MAJORITY/MAIN USE
 OF THE BUILDING AND THE WINE STORAGE AREA IS AN
 ACCESSORY PART OF THE BUILDING/BUSINESS.
  
 ANGELLA VANN, AICP
 PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-08 Cont ID  
Sent By njwira Date 2016-07-08 Time 10:47 Rev Time 0.00
Received By njwira Date 2016-07-08 Time 10:47 Sent To  
Notes
2016-07-08 10:48:317/8/16- FAILED
  
 1. CLUBS WITHIN THE NEIGHBORHOOD COMMERCIAL DISTRICT
 REQUIRES A CLASS B SPECIAL USE PERMIT.
  
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-05-17 Cont ID  
Sent By nwiar Date 2016-05-17 Time 12:24 Rev Time 0.00
Received By njwira Date 2016-05-17 Time 12:23 Sent To  
Notes
2016-05-17 12:26:065/17/16- FAILED- NEED TO PROVIDE A SURVEY OF THE
 PROPERTY. WHAT IS THE USE OF THIS PROPERTY?
  
 AFTER TALKING TO THE DEVELOPER ON 5/18/16 THEIR
 PROPOSED CHANGE OF USE THE PROPERTY IS TRYING TO BE
 TURNED INTO A 32 STORAGE UNIT WINE COOLER. THIS IS
 CONSIDERED WAREHOUSING FACILITIIES FOR FAMILIES AND
 SMALL BUISINESSES. THE ZONING FOR THIS PROPERTY IS NC
 ZONING DISTRICT AND THIS USE IS NOT PERMITTED ON THIS
 PROPERTY.
  
 NATHAN WIRA
 (561)822-1442
 [email protected]