Plan Review Details - Permit 16050357
Plan Review Stops For Permit 16050357
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-25 Cont ID  
Sent By shill Date 2016-06-25 Time 12:31 Rev Time 0.00
Received By shill Date 2016-06-25 Time 12:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-24 Cont ID  
Sent By shill Date 2016-05-24 Time 16:59 Rev Time 0.00
Received By shill Date 2016-05-24 Time 16:59 Sent To  
Notes
2016-05-24 17:00:15****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SCOPE NOT CLEAR. DETAILS FOR THE BATHROOM ARE SHOWN
 BUT A01.502 INDICATE THAT THIS IS NOT WITHIN THE SCOPE
 OF WORK.
  
 SEE PLUMBING COMMENTS REGARDING ACCESSIBLE ELEMENTS AND
 REVISE PLAN, FBC 5TH ED. ACCESSIBILITY, OR PROVIDE MORE
 INFORMATION (SEE FBC 5TH EDITION ACCESSIBILITY 202.4).
 IF ALL ELEMENTS ARE NOT BROUGHT INTO COMPLIANCE DUE TO
 DISPROPORTIONATE COST, PROVIDE A WRITTEN BREAKDOWN AND
 NARRATIVE.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-17 Cont ID  
Sent By vperez Date 2016-05-17 Time 06:52 Rev Time 0.00
Received By vperez Date 2016-05-17 Time 06:52 Sent To  
Notes
2016-05-17 06:56:06INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVISO- ADD A GENERAL NOTE TO INDICATE LOW VOLTAGE
 SYSTEMS TO BE PERMITTED SEPARATELY, ACCESS, DATA/TEL,
 FIRE ALARM ETC.
 2. CONFIRM CLEARANCE FOR THE NEW PANEL BOARD INSTALLED
 IN EXISTING ELECTRICAL ROOM. A NOTE WILL SUFFICE NEC
 110.26.
 3. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-12 Cont ID  
Sent By pleduc Date 2016-05-12 Time   Rev Time 0.00
Received By pleduc Date 2016-05-12 Time 15:25 Sent To  
Notes
2016-05-12 16:19:08THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET G0.601 - THERE IS A NOTE INDICATING EGREESS
 DOOR LOCKS WILL RELEASE ON ACTIVATION OF THE FIRE
 ALARM.
  
 EXIT DOOR LOCKS SHALL COMPLY WITH NFPA 101, CHAPTER 7;
 7.2.1.6.
  
 7.2.1.6* SPECIAL LOCKING ARRANGEMENTS.
 7.2.1.6.1 DELAYED-EGRESS LOCKING SYSTEMS.
 7.2.1.6.1.1 APPROVED, LISTED, DELAYED-EGRESS LOCKING
 SYSTEMS SHALL BE PERMITTED TO BE INSTALLED ON DOOR
 ASSEMBLIES SERVING LOW AND ORDINARY HAZARD CONTENTS IN
 BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE WITH SECTION
 9.6 OR AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION 9.7, AND WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43, PROVIDED THAT ALL
 OF THE FOLLOWING CRITERIA ARE MET:
 (1) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF
 EGRESS UPON ACTUATION OF ONE OF THE FOLLOWING:
 (A) APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7
 (B) NOT MORE THAN ONE HEAT DETECTOR OF AN APPROVED,
 SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE WITH SECTION 9.6
 (C) NOT MORE THAN TWO SMOKE DETECTORS OF AN APPROVED,
 SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE WITH SECTION 9.6
 (2) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF
 EGRESS UPON LOSS OF POWER CONTROLLING THE LOCK OR
 LOCKING MECHANISM.
 (3)* AN IRREVERSIBLE PROCESS SHALL RELEASE THE LOCK IN
 THE DIRECTION OF EGRESS WITHIN 15 SECONDS, OR 30
 SECONDS WHERE APPROVED BY THE AUTHORITY HAVING
 JURISDICTION, UPON APPLICATION OF A FORCE TO THE
 RELEASE DEVICE REQUIRED IN 7.2.1.5.10 UNDER ALL OF THE
 FOLLOWING CONDITIONS:
 (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF
 (67 N).
 (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY
 APPLIED FOR MORE THAN 3 SECONDS.
 (C) THE INITIATION OF THE RELEASE PROCESS SHALL
 ACTIVATE AN AUDIBLE SIGNAL IN THE VICINITY OF THE DOOR
 OPENING.
 (D) ONCE THE LOCK HAS BEEN RELEASED BY THE APPLICATION
 OF FORCE TO THE RELEASING DEVICE, RELOCKING SHALL BE BY
 MANUAL MEANS ONLY.
 (4)* A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT
 LESS THAN 1 IN. (25 MM) HIGH AND NOT LESS THAN 1?8 IN.
 (3.2 MM) IN STROKE WIDTH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS SHALL BE LOCATED ON THE DOOR LEAF
 ADJACENT TO THE RELEASE DEVICE IN THE DIRECTION OF
 EGRESS:
 PUSH UNTIL ALARM SOUNDS
 DOOR CAN BE OPENED IN 15 SECONDS
 (5) THE EGRESS SIDE OF DOORS EQUIPPED WITH
 DELAYED-EGRESS LOCKS SHALL BE PROVIDED WITH EMERGENCY
 LIGHTING IN ACCORDANCE WITH SECTION 7.9.
  
  
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR
 ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH ELECTRICAL LOCK HARDWARE THAT PREVENTS
 EGRESS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE
 MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO UNLOCK THE DOOR LEAF IN THE DIRECTION OF
 EGRESS UPON DETECTION OF AN APPROACHING OCCUPANT.
 (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE
 DIRECTION OF EGRESS UPON LOSS OF POWER TO THE SENSOR OR
 TO THE PART OF THE ACCESS CONTROL SYSTEM THAT LOCKS THE
 DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 COMPLYING WITH ALL OF THE FOLLOWING CRITERIA:
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM )
 VERTICALLY ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM)
 OF THE SECURED DOOR OPENINGS.
 (B) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 AS FOLLOWS: PUSH TO EXIT.
 (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK
 INDEPENDENT OF THE LOCKING SYSTEM ELECTRONICS .AND THE
 LOCK SHALL REMAIN UNLOCKED FOR NOT LESS THAN 30
 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE
 FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY
 RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM
 SPECIFIED IN 7.2.1.6.2 (4) SHALL NOT BE REQUIRED TO
 UNLOCK THE DOOR LEAVES.
 (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE
 FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY
 RESET.
 (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS,
 OTHER THAN EXISTING ACCESS-CONTROLLED EGRESS DOORS,
 SHALL BE PROVIDED WITH EMERGENCY LIGHTING IN ACCORDANCE
 WITH SECTION 7.9.
  
 ENSURE COMPLIANCE WITH THE APPLICABLE CODE. ALL LACKS
 SHALL BE INSPECTED AND TESTED FOR FIRE FINALS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-25 Cont ID  
Sent By shill Date 2016-06-25 Time 12:31 Rev Time 0.00
Received By shill Date 2016-06-15 Time 13:56 Sent To  
Notes
2016-06-15 13:56:44C34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-15 Cont ID  
Sent By cpuell Date 2016-06-15 Time 10:26 Rev Time 0.00
Received By cpuell Date 2016-05-09 Time 11:19 Sent To  
Notes
2016-05-10 11:19:21C31

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-21 Cont ID  
Sent By ccole Date 2016-06-21 Time 08:42 Rev Time 0.00
Received By ccole Date 2016-06-21 Time 08:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-18 Cont ID  
Sent By ccole Date 2016-05-18 Time 13:01 Rev Time 0.00
Received By ccole Date 2016-05-18 Time 13:01 Sent To  
Notes
2016-05-18 13:23:26 
 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16050357
 5/18/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 2) PROVIDE OUTDOOR AIR SHUTOFF DAMPER CONTROLS FOR EACH
 AC SYSTEM IN COMPLIANCE WITH SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION .
 3) SHEET M02.102: PROVIDE DUCT SMOKE DETECTORS IN THE
 RETURN AIR SYSTEMS OF RTU-2 AND RTU-4.
 4) M02.102: PROVIDE A LABEL TO IDENTIFY RTU-2
 5) M02.102: PROVIDE THE FLEX DUCT SIZES AND CFMS AT ALL
 DIFFUSERS AND RETURN GRILLS.
 6) M02.102: INCLUDE THE FLEX DUCTS IN THE SCHEDULE.
 7) M02.102, NOTE #5: THE EXHAUST CAPACITY IN THE MEN'S
 BATHROOM SHALL BE MINIMUM 100 CFMS UNLESS THE EXHAUST
 WILL RUN CONTINUOUSLY- TABLE 403.3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-23 Cont ID  
Sent By gjohnson Date 2016-06-23 Time 10:57 Rev Time 0.00
Received By gjohnson Date 2016-06-23 Time 10:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-12 Cont ID  
Sent By gjohnson Date 2016-05-12 Time 11:08 Rev Time 0.00
Received By gjohnson Date 2016-05-12 Time 11:08 Sent To  
Notes
2016-05-12 11:47:10 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHOW CLEAR FLOOR SPACE FOR BREAKROOM SINKS AND
 COFFEE BAR. SHALL COMPLY WITH FBC ACC. SEC. 305.3-
 303.5
  
 2. THE DIMENSION YOU HAVE FOR TOILET HEIGHT OF 15IN. IS
 TO LOW. TOILET SEATS SHALL COMPLY WITH FBC ACC. SEC.
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 3. THE HEIGHT OF THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE FROM FINISHED FLOOR AT A
 MIN OF 33IN. AND A MAX OF 36IN PLEASE SHOW ON PLAN THAT
 WAY. TO COMPLY WITH FBC ACC.SEC. 609.4
  
 4. THE DIMENSION FROM SIDE WALL TO CENTER OF TOILET
 SHOULD SHOW A MIN OF 16IN AND MAX OF 18IN TO COMPLY
 WITH FBC ACC SEC. 604.2
  
 5. THE TOILET DISPENSER SHALL COMPLY WITH FBC
 ACC.SEC.604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 5. THE GRAB BAR ON SIDE WALL SHALL IS MISSING THE 12IN
 MAX FROM REAR WALL TO COMPLY WITH FBC ACC SEC.604.5.1
 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL
  
 6. PROVIDE A BACKFLOW FOR ICE MACHINES IN REF AND
 COFFEE MAKERS. PER FBC ACC SEC. 608.16.1 -608.3
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-26 Cont ID  
Sent By ajones Date 2016-05-26 Time 15:57 Rev Time 0.00
Received By ajones Date 2016-05-26 Time 15:57 Sent To  
Notes
***NONE***