Plan Review Details - Permit 16050355
Plan Review Stops For Permit 16050355
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-16 Cont ID  
Sent By mvaldes Date 2016-05-16 Time 14:47 Rev Time 0.00
Received By mvaldes Date 2016-05-16 Time 14:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-12 Cont ID  
Sent By mvaldes Date 2016-05-12 Time 09:40 Rev Time 0.00
Received By mvaldes Date 2016-05-12 Time 09:40 Sent To  
Notes
2016-05-12 10:15:59REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 25? OF MECHANICAL EQUIPMENT.
  
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
  
 SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS 314
 & 315.
  
 PVC RUN FROM 200 AMP PANEL TO 100 AMP PANEL SHOWS NO
 EQUIPMENT GROUNDING CONDUCTOR OR MISSING NUETRAL DUE TO
 THE FACT IT SHOWS 2- # 4 THHN AND 1-# 6 THHN. PLEASE
 CLARIFY ?
  
 NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A RECEPTACLE
 OUTLET SHALL BE INSTALLED AT EACH WALL COUNTERTOP SPACE
 THAT IS 12 IN. OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 24 IN. MEASURED HORIZONTALLY FROM A RECEPTACLE
 OUTLET IN THAT SPACE.
  
 NEC 210.8 GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION.
 (A) DWELLING UNITS??. MARK GFCI ON FLOOR PLANS.
  
 SHOW DISCONNECTS FOR W/H AND A/C UNITS ON FLOOR PLANS.
 WPBA 107
  
 TAMPER RESISTANT RECEPTACLES REQUIRED PER NEC 406.11
  
 BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH
 PART III OF ARTICLE 250. NEC 250.32 ( PLEASE SHOW SIZE
 OF GROUNDING ELECTRODE CONDUCTOR ON DETACHED BUILDING)
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-16 Cont ID  
Sent By mvaldes Date 2016-05-16 Time 14:47 Rev Time 0.00
Received By mvaldes Date 2016-05-16 Time 12:45 Sent To  
Notes
2016-05-16 12:45:13RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-12 Cont ID  
Sent By mvaldes Date 2016-05-12 Time 09:47 Rev Time 0.00
Received By mvaldes Date 2016-05-09 Time 16:11 Sent To  
Notes
2016-05-09 16:11:34ROUTED TO ELECTRICAL INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved