Plan Review Details - Permit 16050298
Plan Review Stops For Permit 16050298
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-19 Cont ID  
Sent By cpuell Date 2016-05-19 Time 17:26 Rev Time 0.00
Received By cpuell Date 2016-05-19 Time 14:52 Sent To  
Notes
2016-05-19 14:52:38RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-12 Cont ID  
Sent By lmarchan Date 2016-05-12 Time 07:58 Rev Time 0.00
Received By lmarchan Date 2016-05-06 Time 10:33 Sent To  
Notes
2016-05-09 10:34:35MECH - $5000

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-19 Cont ID  
Sent By jvalido Date 2016-05-19 Time 15:54 Rev Time 0.00
Received By jvalido Date 2016-05-19 Time 15:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-11 Cont ID  
Sent By jvalido Date 2016-05-11 Time 18:53 Rev Time 0.00
Received By jvalido Date 2016-05-11 Time 18:47 Sent To  
Notes
2016-05-11 18:53:43CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 (1) PROVIDE CFM AMOUNTS OF EACH SUPPLY GRILL.
 (2) PROVIDE RETURN AIR GRILL SIZES. (1" UNDER CUT OF
 DOORS IS NOT SUFFICIENT FOR AIR RETURN).
  