Plan Review Details - Permit 16050291
Plan Review Stops For Permit 16050291
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-09-07 Cont ID  
Sent By cthroop Date 2016-09-07 Time 13:57 Rev Time 0.00
Received By cthroop Date 2016-09-07 Time 13:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-08-05 Cont ID  
Sent By skennedy Date 2016-08-05 Time 10:36 Rev Time 0.00
Received By skennedy Date 2016-08-03 Time 16:43 Sent To  
Notes
2016-08-05 10:37:031ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 ZONING SETBACK IS NOT MET SO ENCLOSURE DESIGN DOES NOT
 FIT. RE-SUBMIT FULL SCREEN ENCLOSURE DESIGN TO FIT THE
 SETBACK REQUIREMENT. YOU MAY CHOOSE TO GO FORWARD WITH
 THE POOL DECK DESIGN. PLEASE RE-SUBMIT IN THAT EVENT
 WITH ALTERNATE POOL BARRIER DETAILS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-17 Cont ID  
Sent By skennedy Date 2016-06-17 Time 16:43 Rev Time 0.00
Received By skennedy Date 2016-06-17 Time 16:43 Sent To  
Notes
2016-06-17 16:43:252ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 FAILED PREVIOUS COMMENTS WERE NOT ADDRESSED AS FOLLOWS:
  
 FBC 107 PLEASE PROVIDE ON THE PLAN SPECIFICATIONS TO
 DETAIL THE PROPOSED NEW POOL DECK/CONCRETE SLAB TO
 DEMONSTRATE COMPLIANCE WITH APPLICABLE CRITERIA AS
 FOLLOWS:
  
 SPECIFY THE MINIMUMN CONCRETE COMPRESSIVE PSI STRENGTH,
 THINKNESS, AND REINFORCEMENT OF THE SLAB ON GRADE AND
 FOOTINGS.
  
 SPECIFY THE DIMENSIONS AND REINFORCEMENT OF THE
 FOOTINGS.
  
 R4501.6.1 CONFORMANCE STANDARD.
 DESIGN, CONSTRUCTION AND WORKMANSHIP SHALL BE IN
 CONFORMITY WITH THE REQUIREMENTS OF ANSI/NSPI 3;
 ANSI/APSP/ICC 4; ANSI/ APSP/ ICC 5; ANSI/ APSP/ICC 6;
 AND ANSI/APSP 7.
  
 DEMONSTRATE POSITIVE DRAINAGE OF DECK AWAY FROM POOL
 AND HOUSE FOUNDATION.
  
 DEMONSTRATE TERMITE PROTECTION AT HOUSE PERIMETER PER
 FBCR318.1.6
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CHEMICAL SOIL TREATMENTS SHALL ALSO BE
 APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE WITHIN 1
 FOOT (305 MM) OF THE PRIMARY STRUCTURE SIDEWALLS. ALSO,
 A VERTICAL CHEMICAL BARRIER SHALL BE APPLIED PROMPTLY
 AFTER CONSTRUCTION IS COMPLETED, INCLUDING INITIAL
 LANDSCAPING AND IRRIGATION/SPRINKLER INSTALLATION. ANY
 SOIL DISTURBED AFTER THE CHEMICAL VERTICAL BARRIER IS
 APPLIED SHALL BE PROMPTLY RETREATED.
  
 R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENT.
 RESIDENTIAL SWIMMING POOLS SHALL COMPLY WITH SECTIONS
 R4501.17.1 THROUGH R4501.17.3.
 DEMONSTRATE COMPLIANCE WITH THE LATCHING REQUIREMENTS
 FOR THE SCREEN DOOR.
  
 THE CLAIMED VALUE OF $11,900.00 APPEARS LOW FOR THE
 PROPOSED SCOPE OF WORK. PLEASE RE-ASSESS THE VALUE OR
 DEMONSTRATE HOW THE FIGURE WAS ARRIVED UPON.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-07 Cont ID  
Sent By skennedy Date 2016-06-07 Time 18:36 Rev Time 0.00
Received By skennedy Date 2016-06-07 Time 18:02 Sent To  
Notes
2016-06-07 18:26:481ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 DENIED
  
 FBC 107 PLEASE PROVIDE ON THE PLAN SPECIFICATIONS TO
 DETAIL THE PROPOSED NEW POOL DECK/CONCRETE SLAB TO
 DEMONSTRATE COMPLIANCE WITH APPLICABLE CRITERIA AS
 FOLLOWS:
  
 SPECIFY THE MINIMUMN CONCRETE COMPRESSIVE PSI STRENGTH,
 THINKNESS, AND REINFORCEMENT OF THE SLAB ON GRADE AND
 FOOTINGS.
  
 SPECIFY THE DIMENSIONS AND REINFORCEMENT OF THE
 FOOTINGS.
  
 R4501.6.1 CONFORMANCE STANDARD.
 DESIGN, CONSTRUCTION AND WORKMANSHIP SHALL BE IN
 CONFORMITY WITH THE REQUIREMENTS OF ANSI/NSPI 3;
 ANSI/APSP/ICC 4; ANSI/ APSP/ ICC 5; ANSI/ APSP/ICC 6;
 AND ANSI/APSP 7.
  
 DEMONSTRATE POSITIVE DRAINAGE OF DECK AWAY FROM POOL
 AND HOUSE FOUNDATION.
  
 DEMONSTRATE TERMITE PROTECTION AT HOUSE PERIMETER PER
 FBCR318.1.6
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CHEMICAL SOIL TREATMENTS SHALL ALSO BE
 APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE WITHIN 1
 FOOT (305 MM) OF THE PRIMARY STRUCTURE SIDEWALLS. ALSO,
 A VERTICAL CHEMICAL BARRIER SHALL BE APPLIED PROMPTLY
 AFTER CONSTRUCTION IS COMPLETED, INCLUDING INITIAL
 LANDSCAPING AND IRRIGATION/SPRINKLER INSTALLATION. ANY
 SOIL DISTURBED AFTER THE CHEMICAL VERTICAL BARRIER IS
 APPLIED SHALL BE PROMPTLY RETREATED.
  
 R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENT.
 RESIDENTIAL SWIMMING POOLS SHALL COMPLY WITH SECTIONS
 R4501.17.1 THROUGH R4501.17.3.
 DEMONSTRATE COMPLIANCE WITH THE LATCHING REQUIREMENTS
 FOR THE SCREEN DOOR.
  
  
 THE CLAIMED VALUE OF $11,900.00 APPEARS LOW FOR THE
 PROPOSED SCOPE OF WORK. PLEASE RE-ASSESS THE VALUE OR
 DEMONSTRATE HOW THE FIGURE WAS ARRIVED UPON.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-07 Cont ID  
Sent By mvaldes Date 2016-09-07 Time 14:11 Rev Time 0.00
Received By mvaldes Date 2016-09-07 Time 14:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-06-17 Cont ID  
Sent By skennedy Date 2016-06-17 Time 16:39 Rev Time 0.00
Received By skennedy Date 2016-06-17 Time 16:39 Sent To  
Notes
2016-06-17 16:42:192ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 DENIED COMMENTS FROM FIRST REVIEW WERE NOT ADDRESSED AS
 FOLLOWS:
  
 PLEASE DEMONSTRATE THE EXISTENCE OF PROVIDE DETAIL TO
 ASSURE THE INSTALLATION OF AN EQUIPOTENTIAL BONDING
 GRID AT THE PERIMETER SURFACES THAT EXTEND LESS THAN 3
 FEET (914 MM) BEYOND THE INSIDE WALL OF THE POOL
  
 SECTION E4204 BONDING
  
 E4204.1 PERFORMANCE.
 THE EQUIPOTENTIAL BONDING REQUIRED BY THIS SECTION
 SHALL BE INSTALLED TO REDUCE VOLTAGE GRADIENTS IN THE
 POOL AREA AS PRESCRIBED.
  
 2. PERIMETER SURFACES. THE PERIMETER SURFACE SHALL
 EXTEND FOR 3 FEET (914 MM) HORIZONTALLY BEYOND THE
 INSIDE WALLS OF THE POOL AND SHALL INCLUDE UNPAVED
 SURFACES, POURED CONCRETE SURFACES AND OTHER TYPES OF
 PAVING. PERIMETER SURFACES THAT EXTEND LESS THAN 3 FEET
 (914 MM) BEYOND THE INSIDE WALL OF THE POOL AND THAT
 ARE SEPARATED FROM THE POOL BY A PERMANENT WALL OR
 BUILDING 5 FEET (1524 MM) OR MORE IN HEIGHT SHALL
 REQUIRE EQUIPOTENTIAL BONDING ON THE POOL SIDE OF THE
 PERMANENT WALL OR BUILDING. BONDING TO PERIMETER
 SURFACES SHALL BE PROVIDED AS SPECIFIED IN ITEM 2.1 OR
 2.2 AND SHALL BE ATTACHED TO THE POOL, SPA, OR HOT TUB
 REINFORCING STEEL OR COPPER CONDUCTOR GRID AT A MINIMUM
 OF FOUR POINTS UNIFORMLY SPACED AROUND THE PERIMETER OF
 THE POOL, SPA, OR HOT TUB. FOR NONCONDUCTIVE POOL
 SHELLS, BONDING AT FOUR POINTS SHALL NOT BE REQUIRED.
  
 7. ALL FIXED METAL PARTS INCLUDING, BUT NOT LIMITED TO,
 METAL-SHEATHED CABLES AND RACEWAYS, METAL PIPING, METAL
 AWNINGS, METAL FENCES AND METAL DOOR AND WINDOW
 FRAMES.WITHIN 5 FEET (1524 MM) HORIZONTALLY FROM THE
 INSIDE WALLS OF THE POOL.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-07 Cont ID  
Sent By skennedy Date 2016-06-07 Time 18:27 Rev Time 0.00
Received By skennedy Date 2016-06-07 Time 18:27 Sent To  
Notes
2016-06-07 18:36:451ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 DENIED
  
 PLEASE DEMONSTRATE THE EXISTENCE OF PROVIDE DETAIL TO
 ASSURE THE INSTALLATION OF AN EQUIPOTENTIAL BONDING
 GRID AT THE PERIMETER SURFACES THAT EXTEND LESS THAN 3
 FEET (914 MM) BEYOND THE INSIDE WALL OF THE POOL
  
 SECTION E4204 BONDING
  
 E4204.1 PERFORMANCE.
 THE EQUIPOTENTIAL BONDING REQUIRED BY THIS SECTION
 SHALL BE INSTALLED TO REDUCE VOLTAGE GRADIENTS IN THE
 POOL AREA AS PRESCRIBED.
  
 2. PERIMETER SURFACES. THE PERIMETER SURFACE SHALL
 EXTEND FOR 3 FEET (914 MM) HORIZONTALLY BEYOND THE
 INSIDE WALLS OF THE POOL AND SHALL INCLUDE UNPAVED
 SURFACES, POURED CONCRETE SURFACES AND OTHER TYPES OF
 PAVING. PERIMETER SURFACES THAT EXTEND LESS THAN 3 FEET
 (914 MM) BEYOND THE INSIDE WALL OF THE POOL AND THAT
 ARE SEPARATED FROM THE POOL BY A PERMANENT WALL OR
 BUILDING 5 FEET (1524 MM) OR MORE IN HEIGHT SHALL
 REQUIRE EQUIPOTENTIAL BONDING ON THE POOL SIDE OF THE
 PERMANENT WALL OR BUILDING. BONDING TO PERIMETER
 SURFACES SHALL BE PROVIDED AS SPECIFIED IN ITEM 2.1 OR
 2.2 AND SHALL BE ATTACHED TO THE POOL, SPA, OR HOT TUB
 REINFORCING STEEL OR COPPER CONDUCTOR GRID AT A MINIMUM
 OF FOUR POINTS UNIFORMLY SPACED AROUND THE PERIMETER OF
 THE POOL, SPA, OR HOT TUB. FOR NONCONDUCTIVE POOL
 SHELLS, BONDING AT FOUR POINTS SHALL NOT BE REQUIRED.
  
 7. ALL FIXED METAL PARTS INCLUDING, BUT NOT LIMITED TO,
 METAL-SHEATHED CABLES AND RACEWAYS, METAL PIPING, METAL
 AWNINGS, METAL FENCES AND METAL DOOR AND WINDOW
 FRAMES.WITHIN 5 FEET (1524 MM) HORIZONTALLY FROM THE
 INSIDE WALLS OF THE POOL.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-05-27 Cont ID  
Sent By njwira Date 2016-06-07 Time 15:13 Rev Time 1.00
Received By mgonzale Date 2016-05-27 Time   Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-09-07 Cont ID  
Sent By mvaldes Date 2016-09-07 Time 14:11 Rev Time 0.00
Received By mvaldes Date 2016-09-07 Time 12:49 Sent To  
Notes
2016-09-07 12:50:07RESUB ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-05 Cont ID  
Sent By skennedy Date 2016-08-05 Time   Rev Time 0.00
Received By skennedy Date 2016-08-02 Time 16:42 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-17 Cont ID  
Sent By skennedy Date 2016-06-17 Time 16:49 Rev Time 0.00
Received By skennedy Date 2016-06-16 Time 12:52 Sent To  
Notes
2016-06-16 12:53:10RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-27 Cont ID  
Sent By spalmer Date 2016-05-27 Time 11:21 Rev Time 0.00
Received By spalmer Date 2016-05-06 Time 10:35 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-08-04 Cont ID  
Sent By skennedy Date 2016-08-05 Time 10:37 Rev Time 0.00
Received By njwira Date 2016-08-04 Time 10:23 Sent To B
Notes
2016-08-04 10:24:368/3/16- PASSED
  
 2FT. SIDE SETBACK MUST BE MET FALLOWING CONTRACTOR
 AGREEMENT VERBALLY.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-06-17 Cont ID  
Sent By njwira Date 2016-06-17 Time 09:34 Rev Time 0.00
Received By njwira Date 2016-06-17 Time 09:34 Sent To B
Notes
2016-07-25 11:41:37CHANGE MADE TO THE ORDINANCE WAS NOT IN THE COMPUTER
 PASS ONCE RECEIVED.
2016-06-17 16:49:276/17/16- FAILED
  
 1. NEED TO SHOW THE 2FT. SIDE SETBACK ON THE WALL SIDE
 IN THE DRAWING.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-07 Cont ID  
Sent By spalmer Date 2016-05-27 Time 11:21 Rev Time 0.00
Received By njwira Date 2016-05-12 Time 09:39 Sent To ENG
Notes
2016-06-07 15:12:526/7/16- FAILED
  
 1. REAR SETBACK MUST BE AT LEAST 3FT. AND THE SCREEN
 ENCLOSURE IS ON THE PROPERTY LINE.
 2. SCREEN ENCLOSURE MUST BE 2FT. FROM THE NON-ZERO
 PROPERTY LINE AND THERE IS NO MEASUREMENT.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  