Plan Review Details - Permit 16050281
Plan Review Stops For Permit 16050281
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-02 Cont ID  
Sent By   Date 2016-06-02 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2016-06-02 Time 06:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-07 Cont ID  
Sent By jwitmer Date 2016-05-07 Time 14:32 Rev Time  
Received By jwitmer Date 2016-05-07 Time 14:01 Sent To  
Notes
2016-05-07 14:32:15BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050281
 ADD: 1200 S. FLAGLER DR. SUITE # 801
 CONT: FOWLER BUILDING
 TEL: 772-486-5350
 E-MAIL: [email protected]
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. MAY 07/2014
 ACTION: DENIED
  
 1) THE PLANS SUBMITTED ARE NOT DRAFTSMAN QUALITY PLANS
 NOR DOES THE PLAN ITSELF PROVIDE DETAILS AS REQUIRED TO
 BUILD BY.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS,
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORDS MANAGEMENT.
  
 2) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5..1.1 COMMERCIAL BUILDINGS:
 FLOOR PLAN TO SCALE WITH DIMENSIONS.
 DETAILS FOR DROPPED CEILINGS AND SOFFITS. HOW LOW WILL
 THE DROPPED CEILINGS AND SOFFITS BE FROM FINISH FLOOR.
 WHAT FRAMING MATERIALSS WILL BE USED, WHAT SIZE OR
 GAUGE MATERIALS, AT WHAT CENTERS WILL THE FRAMING
 MEMBERS BE, HOW LONG OF SPANS WILL THE FRAMING MEMBERS
 NEED TO CARRY, WHAT TYPE OF FINISH MATERIALS AND
 THICKNEES WILL BE ON THE FRAMING MEMBERS, WHAT TYPE OF
 ANCHORS WILL BE USED FOR ANCHORING INTO THE WALL
 FRAMING AS WELL AS THE CONCRETE FLOOR CEILING ASSEMBLY.
 DOES THIS BUILDING HAVE A POST-TENSION CABLING FLOOR
 SYSTEM AND IF SO, PLEASE PROVIDE A COPY OF THE X-RAY
 REPORT. AT WHAT DEFLECTION HAS THE DROPPED CEILING AND
 OR SOFFITS BEEN DESIGNED TO AND DOES THIS SYSTEM
 REQUIRE A STIM BACK SYSTEM FOR THE SPANS. 107.2.1.3
 ADDITIONAL INFORMATION NOT PROVIDED IN THIS REVIEW.
  
 3) NOTED FLOOR UNDERLAYMENT WAS COMPLETED UNDER PERMIT
 15090035 INSPECTED ON 10/18/15 WITH # 143 MISC.
 INSPECTION. NOTE A 104 FINAL WILL NEED TO BE CALLED IN
 OTHERWISE THIS PERMIT WILL EXPIRE AND HAVE TO BE
 RENEWED!!!!
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2016-05-20 Cont ID  
Sent By vperez Date 2016-05-20 Time 15:16 Rev Time 0.00
Received By vperez Date 2016-05-20 Time 15:15 Sent To  
Notes
2016-05-20 15:17:00INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. ELECTRICAL UNDER SEPARATE PERMIT
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-18 Cont ID  
Sent By vperez Date 2016-05-18 Time 12:27 Rev Time 0.00
Received By vperez Date 2016-05-18 Time 12:27 Sent To  
Notes
2016-05-18 12:29:04INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 EXISTING FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE ELECTRICAL DRAWINGS REFLECTING ALL
 SCOPE AS SHOWN ON SCOPE OF WORK SHEETS FOR A COMPLETE
 ELECTRICAL REVIEW. FBC 107.3.5 MINIMUM PLAN REVIEW
 COMMENTS.
 2. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE
 FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-02 Cont ID  
Sent By   Date 2016-06-02 Time 06:59 Rev Time 0.00
Received By lmarchan Date 2016-05-19 Time 13:16 Sent To  
Notes
2016-05-20 13:16:50RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-18 Cont ID  
Sent By vperez Date 2016-05-18 Time 12:29 Rev Time 0.00
Received By vperez Date 2016-05-18 Time 12:29 Sent To  
Notes
2016-05-06 14:39:00B16

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-05-16 Cont ID  
Sent By ccole Date 2016-05-16 Time 11:23 Rev Time 0.00
Received By ccole Date 2016-05-16 Time 11:23 Sent To  
Notes
2016-05-16 11:24:28SEPARATE AC PERMIT #16050114

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-23 Cont ID  
Sent By gjohnson Date 2016-05-23 Time 13:13 Rev Time 0.00
Received By gjohnson Date 2016-05-23 Time 13:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-11 Cont ID  
Sent By gjohnson Date 2016-05-11 Time 15:20 Rev Time 0.00
Received By gjohnson Date 2016-05-11 Time 15:20 Sent To  
Notes
2016-05-11 15:28:581ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1. PLANS SHALL COMPLY WITH WPB AMEND. TO FBC
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF
 FLORIDA STATUTES.
  
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES
 AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
  
 2. PROVIDE DETAIL ON SHOWER DRAIN IN GUEST BATH WILL IT
 BE MOVED. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 3. PROVIDE DETAIL ON PLUMBING WORK IN LAUNDRY ROOM. PER
 WPB AMEND. TO FBC SEC. 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
  
  
 DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A
 COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME,
 THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF
 PLANS.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  