Plan Review Details - Permit 16050242
Plan Review Stops For Permit 16050242
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-08 Cont ID  
Sent By jwitmer Date 2016-06-08 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2016-06-08 Time 07:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-13 Cont ID  
Sent By jwitmer Date 2016-05-13 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2016-05-13 Time 09:42 Sent To  
Notes
2016-05-13 09:46:11BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050242
 ADD: ????????????????????
 CONT: JORGE HERNANDEZ
 TEL: 954-266-9219
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 13/16
 ACTION: DENIED
  
 1) UNKWOWN ADDRESS, ASSUMED. THE PERMIT APPLICATION THE
 OWNER INFORMATION IS FILED OUT AND ADDRESS BUT THE
 ADDRESS OF THE PREOPERTY IS BLANK!!! THE PLANS IN THE
 TITLEBLOCK INDICATE WORK IS BEING COMPLETED AT 1701 S.
 FLAGLER DR. SUITE: 1506. A HOLD WILL BE PUT ON THE
 PERMIT ISSUANCE UNTIL THE ADDRESS IS FILED IN BY THE
 CONTRACTOR ON THE PERMIT APPLICATION.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJECT.
  
 2) SHEET 1.1 INDICATES THIS IS A 18 STORIES HIGH-RISE/
 R-2 OCCUPANCY. BUILDING TYPE IS LABELED AS A TYPE 5B.
 REVIEW 2014 FBC-B TABLE 503.
  
 3) SHEET 1.1 INDICATES NEW TILE FLOORS WITH THE USE OF
 PROFLEX 90 MSC WITH A STC OF 72. PLEASE PROVIDE THE
 TEST REPORTS!!! IN THE PROFLEX PRODUCT LINE ONLY THE
 PROFLEX RCU-500 MEETS ALL (3) TEST REQUIREMENTS ON A 6
 INCH SLAB.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 3A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-09 Cont ID  
Sent By mvaldes Date 2016-06-09 Time 17:18 Rev Time 0.00
Received By mvaldes Date 2016-06-09 Time 17:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-14 Cont ID  
Sent By vperez Date 2016-05-14 Time 13:10 Rev Time 0.00
Received By vperez Date 2016-05-14 Time 13:10 Sent To P
Notes
2016-05-14 13:10:41INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE A PROJECT ADDRESS.
 2. SHOW 2 SMALL APPLIANCE CIRCUIT?S IN THE KITCHEN AREA
 ON ELECTRICAL CALCULATIONS SHOWN PER FBC RES E3703.2
 3. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-17 Cont ID  
Sent By ccole Date 2016-06-17 Time 14:18 Rev Time 0.00
Received By ccole Date 2016-05-31 Time 14:15 Sent To  
Notes
2016-05-31 14:15:51B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-16 Cont ID  
Sent By vperez Date 2016-05-16 Time 09:10 Rev Time 0.00
Received By tklarge Date 2016-05-14 Time 13:11 Sent To  
Notes
2016-05-14 13:12:35PLUMBING SIGNED OFF PLANS, NO RESULTS IN SYSTEM 5/14
2016-05-05 17:18:33B20

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-06-17 Cont ID  
Sent By ccole Date 2016-06-17 Time 14:18 Rev Time 0.00
Received By ccole Date 2016-06-17 Time 14:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-06-06 Cont ID  
Sent By ccole Date 2016-06-06 Time 16:44 Rev Time 0.00
Received By ccole Date 2016-06-06 Time 16:44 Sent To  
Notes
2016-06-06 16:50:452ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050242
 6/6/16
  
 1) INDICATE THE SIZE OF THE RETURN DUCT CONNECTING THE
 LIVING ROOM GRILL WITH THE AIR HANDLER.
  
 2) IT APPEARS THAT THE TRANSFER GRILL OVER THE NEW
 BEDROOM DOOR SHOULD INDICATE 150 CFM'S RATHER THAN 100
 CFM'S BASED ON THE AMOUNT OF SUPPLY CFM'S ENTERING THE
 ROOM. IT APPEARS THAT THIS TRANSFER AIR IS TO THEN BE
 CONVEYED TO THE LIVING ROOM RETURN GRILL?- PLEASE
 CLARIFY.
  
 3) INDICATE THE CAPACITY OF THE EXISTING AC SYSTEM
 (COOLING AND HEATING BTUH, AND SUPPLY CFMS) AND
 INDICATE HOW THE SUPPLY AIR TO THE NEW ROOM LAYOUTS WAS
 DETERMINED OR SIZED. IT APPEARS THAT THE CFM TOTALS FOR
 THE LIVING ROOM AND KITCHEN MAY BE INADEQUATE PER SF.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-11 Cont ID  
Sent By ccole Date 2016-05-11 Time 12:07 Rev Time 0.00
Received By ccole Date 2016-05-11 Time 08:25 Sent To  
Notes
2016-05-11 08:39:361ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050242
 5/11/16
  
 1) PROVIDE THE PROJECT ADDRESS ON THE PERMIT
 APPLICATION. PLEASE NOTE A SUB-PERMIT FOR THE AC WORK
 MUST BE SUBMITTED.
 2) REFER TO SECTION 601.5 FBC-14 MECHANICAL AND
 INDICATE HOW MANY CFM'S OF AIR IS TO BE TRANSFERRED
 THROUGH THE 10X16 GRILL, AND CLARIFY HOW THAT AIR, AND
 THE SUPPLY AIR INTO THE BEDROOM WILL BE RETURNED TO THE
 AIR HANDLER.
 3) THE 6X8 DUCT IS UNDERSIZED FOR 300 CFM'S OF SUPPLY
 AIR PER ASHRAE STANDARD DUCT SIZING.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 RANGE AND HOOD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-16 Cont ID  
Sent By tklarge Date 2016-06-16 Time 12:25 Rev Time 0.00
Received By tklarge Date 2016-06-16 Time 12:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-11 Cont ID  
Sent By tklarge Date 2016-05-11 Time 09:09 Rev Time 0.00
Received By tklarge Date 2016-05-11 Time 11:49 Sent To  
Notes
***NONE***