Plan Review Details - Permit 16050233
Plan Review Stops For Permit 16050233
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-06-24 Cont ID  
Sent By jwitmer Date 2016-06-24 Time 08:44 Rev Time 0.00
Received By jwitmer Date 2016-06-24 Time 07:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-07 Cont ID  
Sent By jwitmer Date 2016-06-07 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2016-06-07 Time 07:30 Sent To  
Notes
2016-06-07 07:43:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050233
 ADD: 1401 FORUM WAY SUITE: 810
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-833-0164
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 07/2016
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) RESPONSE INDICATES NOTED, BUT THE NEW SHEETS WERE
 NOT INSERTED INTO THE PLAN REVIEW SET OF PLANS AND OLD
 SHEETS REMOVED AS REQUESTED, THIS IS THE CONTRACTORS
 RESPONSIBILITY!!!!!
 1ST REVIEW COMMENT.WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-13 Cont ID  
Sent By jwitmer Date 2016-05-13 Time 17:27 Rev Time 0.00
Received By jwitmer Date 2016-05-13 Time 16:53 Sent To  
Notes
2016-05-13 17:17:33BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050233
 ADD: 1401 FORUM WAY SUITE: 810
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-833-0164
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 13/2016
 ACTION: DENIED
  
 1) SHEET A-1.0 INDICATES THE USE OF 2 4X4 FIRE
 RETARDANT TREATED POST FOR SUPPORTING OF X-RAY
 EQUIPMENT. THE PLANS ARE DEFICIENT IN HOW THE POST ARE
 TO BE ANCHORED TO THE CONCRETE FLOOR SLAB AND TO THE
 CONCRETE FLOOR SYSTEM ABOVE? IS THIS BUILDING A
 POST-STRESSED CABLE FLOOR SYSTEM OR A CONVENTIONAL
 SLAB? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET A-1.0 DOES NOT PROVIDE INFORMATION INREGAURDS
 TO ACCESSIBILITY;
 2A) 2014 FBC-ACCESSIBILITY CODE 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2B) 2014 ACCESS. CODE 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3
 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-06-27 Cont ID  
Sent By mvaldes Date 2016-06-27 Time 15:01 Rev Time 0.00
Received By mvaldes Date 2016-06-27 Time 14:40 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-15 Time 08:45 Rev Time 0.00
Received By mvaldes Date 2016-06-15 Time 08:20 Sent To  
Notes
2016-06-15 08:49:312ND REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PLEASE PROVIDE X-RAY EQUIPMENT MANUFACTURE
 SPECIFICATION CUT SHEETS ( 2ND REQUEST )
  
 - LOAD CALCS AND PANEL SCHEDULE REFLECT SINGLE PHASE
 VOLTAGE AND RISER DIAGRAM SHOWS THREE PHASE ? PLEASE
 CLARIFY AND MATCH INFORMATION. ( 2ND REQUEST )

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-12 Cont ID  
Sent By vperez Date 2016-05-12 Time 11:48 Rev Time 0.00
Received By vperez Date 2016-05-12 Time 10:16 Sent To  
Notes
2016-05-12 12:55:24INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE A GENERAL NOTE TO INDICATE NEC 517.13
 SEE VERBIAGE IN CODE FOR REDUNDANT GROUNDING AND PART V
 OF THE NEC 517 REGARDING X-RAY EQUIPMENT.
 2. PROVIDE SPECS OF X-RAY EQUIPMENT BEING INSTALLED.
 FBC 107.3.5
 3. CLARIFY IF THE VOLTAGE TO TENANT IS SINGLE PHASE OR
 3 PHASE. SEE PANEL SCHEDULE SHOWS SINGLE PHASE BUT
 VACUUM PUMP AND AIR COMP. EQUIPMENT IS SHOWN ON A
 SINGLE BREAKER 230VOLTS. PLEASE CORRECT TO SHOW
 ADEQUATE LOADS AND VOLTAGES. FBC 107.3.5
 4. ALL RECEPTACLES WITHIN 6FT OF SINKS TO HAVE GFCI
 PROTECTION, LABEL FLOOR PLANS SEE WORK AREA AND DENTAL
 CHAIRS. NEC 210.8B7
 5. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE
 FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-06-24 Cont ID  
Sent By pleduc Date 2016-06-24 Time   Rev Time 0.00
Received By pleduc Date 2016-06-24 Time 14:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-05-31 Cont ID  
Sent By pleduc Date 2016-05-31 Time   Rev Time 0.00
Received By pleduc Date 2016-05-31 Time 14:21 Sent To  
Notes
2016-05-31 15:36:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) FIRE COULD NOT PASS AND STAMP THESE SUBMITTED PLANS.
  
 A. THE PLANS WERE NOT COLLATED. THE NEW SHEETS SHALL BE
 INSERTED WERE APPROPRIATE AND SECURED.
  
 B. THE NEW SHEETS DID NOT MATCH ADDRESSES, TITLE BLOCK
 AND SHEET NUMBERS.
  
 2) PLEASE REVIEW AND ENSURE THE ABOVE NOTED POINTS ARE
 CORRECTED AND RESUBMITTED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-09 Cont ID  
Sent By pleduc Date 2016-05-09 Time   Rev Time 0.00
Received By pleduc Date 2016-05-09 Time 15:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-28 Cont ID  
Sent By gjohnson Date 2016-06-28 Time 15:25 Rev Time 0.00
Received By gjohnson Date 2016-06-21 Time 08:52 Sent To  
Notes
2016-06-22 08:53:07B29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-15 Time 08:52 Rev Time 0.00
Received By mvaldes Date 2016-05-27 Time 16:03 Sent To  
Notes
2016-05-27 16:04:01B29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-13 Cont ID  
Sent By jwitmer Date 2016-05-13 Time 17:27 Rev Time 0.00
Received By jwitmer Date 2016-05-05 Time 14:54 Sent To  
Notes
2016-05-05 14:55:54B03

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-06-24 Cont ID  
Sent By ccole Date 2016-06-24 Time 16:44 Rev Time 0.00
Received By ccole Date 2016-06-24 Time 16:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-06-02 Cont ID  
Sent By ccole Date 2016-06-02 Time 14:56 Rev Time 0.00
Received By ccole Date 2016-06-02 Time 14:27 Sent To  
Notes
2016-06-02 15:03:092ND REVIEW: FBC 2014 MECHANICAL, EXISTING
 PERMIT #16050233
 5/11/2016
  
 COMMENTS #1, & 2B FROM THE 1ST REVIEW STILL EXIST. I
 HAVE RE-PRINTED THEM BELOW. PLEASE REVIEW AND REVISE
 THE PLAN ACCORDINGLY.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 PROPOSED OCCUPANCY IN COMPLIANCE WITH TABLE 403.3
 FBC-14 MECHANICAL.
 2 B) PROVIDE THE SUPPLY AND RETURN CFM'S AT EACH
 DIFFUSER AND GRILL.
 3) RETURN AIR FROM THE EQUIPMENT CLOSET IS PROHIBITED
 PER SECTION 918.6 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-11 Cont ID  
Sent By ccole Date 2016-05-11 Time 09:30 Rev Time 0.00
Received By ccole Date 2016-05-11 Time 09:30 Sent To  
Notes
2016-05-11 10:17:031ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050233
 5/11/2016
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 PROPOSED OCCUPANCY IN COMPLIANCE WITH TABLE 403.3
 FBC-14 MECHANICAL.
 2) SHEET MEP-2: THE HVAC PLAN IS INCOMPLETE: A) LABEL
 ALL DIFFUSERS AND RETURN GRILLS AS EITHER NEW (N),
 EXISTING (E), OR RELOCATED (R). B) PROVIDE THE SUPPLY
 AND RETURN CFM'S AT EACH DIFFUSER AND GRILL. C) SHOW
 NEW DUCT INSTALLATIONS OR RELOCATIONS.
 3) PROVIDE AN AIR DEVICE SCHEDULE.
 4) PROVIDE DUCT HANGING AND CONNECTION DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-06-28 Cont ID  
Sent By gjohnson Date 2016-06-28 Time 15:24 Rev Time 0.00
Received By gjohnson Date 2016-06-28 Time 15:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2016-06-13 Time   Rev Time 0.00
Received By   Date 2016-06-13 Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-11 Cont ID  
Sent By gjohnson Date 2016-05-11 Time 10:58 Rev Time 0.00
Received By gjohnson Date 2016-05-11 Time 10:24 Sent To  
Notes
2016-05-11 11:55:061ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.DRAIN NOT SHOWN FOR EXAM ROOM 3 PLEASE CLARIFY . PER
 WPB AMEND TO FBC SEC. 107.2.1
  
 2.DRAIN NOT SHOWN FOR BREAKROOM /FUTURE EXAM PLEASE
 CLARIFY. PER WPB AMEND TO FBC SEC. 107.2.1
  
 3. A VENT IS REQUIRED ON 2IN DRAIN FOR EXAM CHAIRS. PER
 FBC PL SEC. 901.2.1
  
 4. PROVIDE A RISER DIAGRAM FOR THE WATER, VACUUM AND
 COMPRESSED AIR SYSTEMS. PER WPB AMEND. TO FBC SEC.
 107.3.5.1.3(13)
  
 5.SHOW VACUUM AND COMPRESSED AIR ON PLAN VIEW. PER WPB
 AMEND TO FBC SEC. 107.2.1
  
 6. PROVIDE MANUFACTURE SPECS ON ALL EQUIPMENT. PER WPB
 AMEND TO FBC SEC. 107.2.1
  
 7. SHOW VENTING FOR VACUUM SYSTEM. SHALL COMPLY WITH
 FBC PL 713.6
  
 8. BACK FLOW DEVICE REQUIRED FOR EXAM CHAIR WATER
 CONNECTION. PER FBC PL SEC. 608.3.1
  
 9. IF THE VACUUM SYSTEM REQUIRES A DRAIN INCLUDE IT ON
 THE PLAN VIEW AND SANITARY RISER. PER WPB AMEND TO FBC
 SEC. 107.2.1
  