| 2016-05-10 12:44:10 | 1ST REVIEW: FBC 2014 5TH ED |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BLDG. PLANS EXAMINER ? PX3169 |
| | (561) 805-7918 |
| | [email protected] |
| | |
| | 1. CORRECT CODE REFERENCE ON PG. S-2 FROM FBC 2010 TO |
| | FBC 2014 5TH ED. |
| | 2. PROVIDE THREE (3) COPIES OF RESIDENT INSPECTOR |
| | AGREEMENT WITH RESUME'S OF THRESHOLD INSPECTOR AND T.I. |
| | REP. (468 INSPECTOR). |
| | |
| | 110.3.7.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL |
| | INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A |
| | STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER OR |
| | ARCHITECT OF RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLANS IS TO PROVIDE SPECIFIC |
| | INSPECTION PROCEDURES AND SCHEDULES SO THAT THE |
| | BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. THE SPECIAL |
| | INSPECTOR MAY NOT SERVE AS A |
| | SURROGATE IN CARRYING OUT THE RESPONSIBILITIES OF THE |
| | BUILDING OFFICIAL, THE ARCHITECT OR |
| | THE ENGINEER OF RECORD. THE CONTRACTOR?S CONTRACTUAL OR |
| | STATUTORY OBLIGATIONS ARE NOT |
| | RELIEVED BY ANY ACTION OF THE SPECIAL INSPECTOR. |
| | |
| | 110.3.7.4.1 THE SPECIAL INSPECTOR, UPON COMPLETION OF |
| | THE BUILDING AND PRIOR TO THE |
| | ISSUANCE OF A CERTIFICATE OF OCCUPANCY, FILE A SIGNED |
| | AND SEALED STATEMENT WITH THE |
| | ENFORCEMENT AGENCY IN SUBSTANTIALLY THE FOLLOWING FORM: |
| | ?TO THE BEST OF MY KNOWLEDGE |
| | AND BELIEF, THE ABOVE DESCRIBED CONSTRUCTION OF ALL |
| | STRUCTURAL LOAD-BEARING COMPONENTS |
| | COMPLIES WITH THE PERMITTED DOCUMENTS, AND THE SHORING |
| | AND RESHORING CONFORMS TO THE |
| | SHORING AND RESHORING PLANS SUBMITTED TO THE |
| | ENFORCEMENT AGENCY. |
| | |
| | 110.3.7.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL |
| | INSPECTOR TO CONDUCT THE |
| | MINIMUM STRUCTURAL INSPECTION OF THRESHOLD BUILDINGS |
| | REQUIRED BY THIS CODE, SECTION 553.73, FLORIDA |
| | STATUTES, WITHOUT DUPLICATIVE INSPECTION BY THE |
| | BUILDING DEPARTMENT. THE BUILDING OFFICIAL IS |
| | RESPONSIBLE FOR ENSURING THAT ANY PERSON CONDUCTING |
| | INSPECTIONS IS QUALIFIED AS A BUILDING INSPECTOR UNDER |
| | PART XII OF CHAPTER 468, FLORIDA STATUTES, OR CERTIFIED |
| | AS A SPECIAL INSPECTOR UNDER CHAPTER 471 OR 481, |
| | FLORIDA STATUTES. INSPECTIONS OF THRESHOLD BUILDINGS |
| | REQUIRED BY SECTION 553.79(5), FLORIDA STATUTES, ARE IN |
| | ADDITION TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | |