Plan Review Details - Permit 16050108
Plan Review Stops For Permit 16050108
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-17 Cont ID  
Sent By cthroop Date 2016-06-17 Time 14:05 Rev Time 0.00
Received By cthroop Date 2016-06-17 Time 14:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By cthroop Date 2016-06-06 Time 14:09 Rev Time 0.00
Received By cthroop Date 2016-06-03 Time 14:33 Sent To  
Notes
2016-06-06 14:14:11BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-7918
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 DATE: 6/6/16
 ACTION: FAIL
  
 1. COMPLY WITH THE REQUIREMENTS OF THE ROOFING AND NFIP
 REVIEW.
 2. PROVIDE SITE DRAINAGE PLAN.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-06-01 Cont ID  
Sent By mvaldes Date 2016-06-01 Time 17:50 Rev Time 0.00
Received By mvaldes Date 2016-06-01 Time 14:10 Sent To  
Notes
2016-06-01 17:53:00REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
  
  
 THE GENERATOR SHALL BE UNDER A SEPERATE PERMIT WITH
 SHOP DRAWINGS. PROVIDE MANUFACTURE SPECS CUT SHEETS ON
 ATS & GENERATOR.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-05-09 Cont ID  
Sent By gjohnson Date 2016-05-09 Time 17:05 Rev Time 0.00
Received By gjohnson Date 2016-05-09 Time 17:05 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-06-16 Cont ID  
Sent By fmittner Date 2016-06-16 Time 14:09 Rev Time 0.00
Received By fmittner Date 2016-06-16 Time 14:09 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-05-25 Cont ID  
Sent By fmittner Date 2016-05-25 Time 11:41 Rev Time 0.00
Received By fmittner Date 2016-05-25 Time 11:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-21 Cont ID  
Sent By cthroop Date 2016-06-21 Time 15:52 Rev Time 0.00
Received By cthroop Date 2016-06-21 Time 15:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-21 Cont ID  
Sent By cpuell Date 2016-06-21 Time 08:23 Rev Time 0.00
Received By cpuell Date 2016-06-14 Time 13:26 Sent To  
Notes
2016-06-14 13:26:35ROUTED TO ZONING INBOX PER SAK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-06 Cont ID  
Sent By cthroop Date 2016-06-06 Time 13:15 Rev Time 0.00
Received By cthroop Date 2016-05-03 Time 08:32 Sent To  
Notes
2016-05-05 08:33:03R26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-06-17 Cont ID  
Sent By cthroop Date 2016-06-17 Time 14:05 Rev Time 0.00
Received By cthroop Date 2016-06-17 Time 14:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-06-03 Cont ID  
Sent By skennedy Date 2016-06-03 Time 17:51 Rev Time 0.00
Received By skennedy Date 2016-06-03 Time 17:51 Sent To  
Notes
2016-06-03 17:52:311ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-06-21 Cont ID  
Sent By jvalido Date 2016-06-21 Time 15:46 Rev Time 0.00
Received By jvalido Date 2016-06-21 Time 15:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-06-20 Cont ID  
Sent By jvalido Date 2016-06-20 Time 16:34 Rev Time 0.00
Received By jvalido Date 2016-06-20 Time 15:25 Sent To  
Notes
2016-06-20 16:33:18FLORIDA ENERGY CODE
 FORM R405-2014 IS NOT SIGNED OR DATED. PROVIDE
 SIGNATURE OF OWNER/AGENT.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-01 Cont ID  
Sent By jvalido Date 2016-06-01 Time 17:36 Rev Time 0.00
Received By jvalido Date 2016-06-01 Time 16:06 Sent To  
Notes
2016-06-01 17:34:35FLORIDA ENERGY CODE
 FORM R405-2014 IS NOT SIGNED OR DATED. PROVIDE
 SIGNATURE OF OWNER/AGENT.
  
 AS PER THE TRANE DUCTULATOR THE MASTER BATHROOM AND
 COOPER'S BATHROOM EXHAUST DUCT MUST BE 6" FOR 100 CFM.
  
 AHU #2 AND AHU #3 SUPPLY AIR THROUGH THE OUTLETS ON THE
 PLANS EXCEED EACH SPECIFIC AHU MAXIMUM AMOUNT OF CFM ON
 EQUIPMENT SCHEDULE. CHECK CFM QUANTITIES AND MAKE
 CORRECTIONS.
  
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED
 WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE
 EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE
 EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE
 AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2016-06-17 Cont ID  
Sent By cthroop Date 2016-06-17 Time 14:05 Rev Time 0.00
Received By cthroop Date 2016-06-17 Time 14:05 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By cthroop Date 2016-06-06 Time 13:38 Rev Time 0.00
Received By cthroop Date 2016-06-06 Time 13:38 Sent To  
Notes
2016-06-06 13:59:21BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-7918
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 DATE: 6/6/16
 ACTION: FAIL
  
 1. REFER TO PG. A001 - LOWEST FFE-HABITABLE SPACE IS
 STATED AS 7.0' NGVD. CITY OF WPB REQUIRES 6" OF FREE
 BOARD. CHANGE FFE TO 7.5'.
 2. REFER TO PG A001 - SITE PLAN NOTE # 2 STATES MECH.
 EQUIPT. TO BE AT OR ABOVE 7.0'. MECH. EQUIPT. TO BE
 7.5'.
 3. PROVIDE SITE PLAN PER FBC 107.
  
 SECTION R322 FLOOD-RESISTANT CONSTRUCTION
 R322.1 GENERAL.
 BUILDINGS AND STRUCTURES CONSTRUCTED IN WHOLE OR IN
 PART IN FLOOD HAZARD AREAS (INCLUDING A OR V ZONES) AS
 ESTABLISHED IN TABLE R301.2(1) SHALL BE DESIGNED AND
 CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS CONTAINED
 IN THIS SECTION. BUILDINGS AND STRUCTURES LOCATED IN
 WHOLE OR IN PART IN IDENTIFIED FLOODWAYS SHALL BE
 DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ASCE 24.
  
 FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY.
 IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL SHOW
 CONSTRUCTION TO BE DEMOLISHED AND THE LOCATION AND SIZE
 OF EXISTING STRUCTURES AND CONSTRUCTION THAT ARE TO
 REMAIN ON THE SITE OR PLOT. THE BUILDING OFFICIAL IS
 AUTHORIZED TO WAIVE OR MODIFY THE REQUIREMENT FOR A
 SITE PLAN WHEN THE APPLICATION FOR PERMIT IS FOR
 ALTERATION OR REPAIR OR WHEN OTHERWISE WARRANTED.
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-09 Cont ID  
Sent By gjohnson Date 2016-05-09 Time 17:04 Rev Time 0.00
Received By gjohnson Date 2016-05-09 Time 17:04 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-06-17 Cont ID  
Sent By cthroop Date 2016-06-17 Time 14:05 Rev Time 0.00
Received By cthroop Date 2016-06-17 Time 14:05 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By cthroop Date 2016-06-06 Time 13:23 Rev Time 0.00
Received By cthroop Date 2016-06-06 Time 13:23 Sent To  
Notes
2016-06-06 13:25:59BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-7918
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 DATE: 6/6/16
 ACTION: FAIL
  
 1. PROVIDE PRODUCT APPROVALS FOR FLAT ROOF ASSEMBLIES.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  
  
  
  
2016-06-03 17:50:57ROOFING REVIEW

Review Stop Z ZONING
Rev No 2 Status P Date 2016-06-17 Cont ID  
Sent By fmittner Date 2016-06-17 Time 15:55 Rev Time 0.00
Received By fmittner Date 2016-06-17 Time 15:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-25 Cont ID  
Sent By fmittner Date 2016-05-25 Time 11:41 Rev Time 0.00
Received By fmittner Date 2016-05-25 Time 11:41 Sent To  
Notes
***NONE***